13.103 Test Procedure: NA7.10.4 Compressor Variable Speed Controls

Construction Inspection

The field technician should check the following:

      All applicable single open-drive screw compressors dedicated to a suction group have variable speed control.

      All pressure and temperature sensors have been calibrated and read accurately.

      All sensor readings used by the compressor controller convert or calculate to the correct conversion units at the controller (e.g., saturated suction pressure reading is correctly converted to appropriate saturated suction temperature (SST)).

      All compressor motor speed controls are operational and connected to compressor motors.

      All speed controls are in “auto” mode.

      Compressor panel control readings for “RPMs”, “% speed”, “kW”, and “amps” match the readings from the PLC or other control systems.

      Compressor data is correctly entered into the PLC or other control system, to the extent required for proper control (e.g. minimum speed)

      Records showing calibration was performed, what offsets or control system calibration values were used, and documentation of the instrumentation used for calibration.

 

Functional Testing

The system cooling load must be sufficiently high for the test, but the compressor should be not operating at fully capacity.  Artificially increase the load by decreasing the zone setpoint, or decrease the load by increasing the zone setpoint or turning off evaporators as needed to perform the Functional Testing.

Step 1: Override any floating suction pressure functionality before performing functional tests.

Work with the refrigeration contractor or facility staff to disable controls that may interfere with the Functional Testing. 

Step 2: Document current operating conditions.  Note these may be the same as the current setpoint.

      Current suction pressure

      Current saturated suction temperature

Step 3: Document current setpoint: Suction pressure setpoint or saturated suction temperature setpoint.

Program into the control system a target setpoint equal to the current operating condition measured in Step #2.  Allow 5 minutes for system to normalize. This will be referred to as the “test suction pressure/saturated suction temperature setpoint”.

Step 4: Using the control system, increase the test suction setpoint in small increments until the compressor controller modulates to decrease compressor speed. 

An increase of 1psi or 1°F SST will be appropriate.  The increase will need to consider any control deadband or time delay that is in place.

Verify:

      Compressor speed decreases

      Compressor speed continues to decrease to minimum speed

      Any slide valve or other unloading means does not unload until after the compressor has reached its minimum speed.

Step 5: Using the control system, decrease the test suction setpoint in small increments until the compressor controller modulates to increase compressor speed.  A decrease of 1psi or 1°F SST will be appropriate.  The decrease will need to consider any control deadband or time delay that is in place.  You must wait a sufficient amount of time so that any timer or delay can expire.

Verify:

      Any slide valve or other unloading means first goes to 100 percent before compressor speed increases from minimum

      Compressor begins to increase speed

      Compressor speed continues to increase to 100 percent

Step 6: Using the control system, program the suction pressure or saturated suction temperature setpoint back to original settings as documented in Step #3.

Confirm that the control system is restored back to correct control setpoints.

Step 7: Restore any controls that were disabled in Step 1.

Verify that the control system is restored back to original conditions.