13.76   Test Procedure: NA7.5.10 Automatic Demand Shed Control Acceptance

Construction Inspection

That the EMCS interface enable activation of the central demand shed controls.

Functional Testing

Step 1 Engage the global demand shed system.

•      This can be done by either jumping the digital contact or simply overriding its condition in the EMCS front end. Wait 5-10 minutes to let the changes take effect.

Verify and Document

•      That the cooling setpoints in the non-critical spaces increase by the proper amount.

•      That the cooling setpoints in the critical spaces do not change.

 

Step 2 Disengage the global demand shed system.

•      This can be done by either removing the jumper from the digital contact or simply releasing the override of the point in the EMCS front end. Wait 5-10 minutes to let the changes take effect.

Verify and Document

•      That the cooling setpoints in the non-critical spaces return to their original setpoint.

•      That the cooling setpoints in the critical spaces do not change.