At-A-Glance
Automatic Time Switch Acceptance |
Use Form NRCA-LTI-02-A |
Purpose of the Test |
The purpose of this test is to ensure that all non-exempt lights, per §130.1(c)1, are automatically turned off at a predetermined time and individual lighting circuits can be manually enabled, if necessary, during scheduled OFF periods (i.e., a lighting “sweep”). |
Benefits of the Test |
An automated control to turn off lighting during typically unoccupied periods of time prevents energy waste. |
Instrumentation |
This test verifies the functionality of installed automatic time switch controls visually and does not require special instrumentation. |
Test Conditions |
All luminaires and override switches controlled by the time switch control system must be wired and powered. |
Lighting control system must be installed and ready for system operation, including completion of all start-up procedures, per manufacturer’s recommendations. |
Preferably, the space is unoccupied during the test to prevent conflicts with other trades. |
Document the initial conditions before overrides or manipulation of the BAS. All systems must be returned to normal at the end of the test. |
Estimated Time to Complete |
Construction Inspection: 0.5 to 2 hours (depending on familiarity with lighting control programming language) |
Equipment Test: 2 to 6 hours (depending on familiarity with lighting control programming language, number of lighting circuits and override switches to be tested, and programmed time delay between ON and OFF signals) |
Acceptance Criteria |
Automatic time switch controls are programmed with acceptable weekday, weekend, and holiday schedules, per building occupancy profile. |
The correct date and time are properly set in the lighting controller. |
Have program backup capabilities that prevent the loss of the device’s schedules for at least 7 days, and the device’s time and date setting for at least 72 hours is power is interrupted |
All lights can be turned ON manually or turn ON automatically during the occupied time schedule. |
All lights turn OFF at the preprogrammed, scheduled times. |
The manual override switch is functional and turns associated lights ON when activated. |
Override time limit is no more than 2 hours, except for spaces exempt per §131(c)3.B. |
If annunciator is installed, verify it is installed properly and verify the annunciator warning to the occupants that the lights are about to turn OFF functions correctly. |
Ensure that occupant sensors have been certified to the Energy Commission in accordance with the applicable provision in §110.9. Verify that model numbers of all occupant sensors are 'listed on the Energy Commission database as “Certified Appliances & Control Devices.” |
http://www.energy.ca.gov/appliances/database/
|
Potential Issues and Cautions |
The manual override time limit can be adjusted to minimize test time, but the time limit setting must be reset upon completion of the test (not to exceed 2 hours). |
It is preferable to perform the test when the spaces are unoccupied. Turning the lights OFF when other occupants are present can cause problems and unsafe working conditions. |
Purpose (Intent) of the Test
The purpose of this test is to ensure that all non-exempt lights per §130.1(c) are automatically turned off at a predetermined time and individual lighting circuits can be manually enabled, if necessary, during scheduled OFF periods. The most common term for this control strategy is a lighting “sweep”.
Construction Inspection
•Automatic time switch control is programmed with acceptable weekday, weekend, and holiday schedules. Non-exempt lights should be scheduled OFF a reasonable time after the space is typically unoccupied (i.e., 1 or 2 hours after most people have already left the space).
• Verify schedule and other programming parameter documentation was provided to the owner. This information will be used to verify system operation. The documentation should include weekday, weekend, and holiday schedules as well as sweep frequency and/or override time period. Sweep frequency or override time period refers to how often the OFF signal is sent through the system and commands the lights OFF again.
• Verify correct date and time is properly set in the time switch. Lights will not be controlled correctly if the programmed date and time do not match actual values.
• Verify the battery is installed and energized. The device shall have program backup capabilities that prevent the loss of schedules for at least 7 days, and the time and date settings for at least 72 hours if power is interrupted.
• Override time limit is no more than 2 hours. When the lights are switched off, each lighting circuit can be turned back on manually. Most systems will either send out another OFF signal through the entire lighting network to command all lights back off, or consist of an override timer that will expire and turn off the lights that were manually turned on. Regardless of the control strategy, lights that were manually turned ON during an OFF period should only be operating for up to 2 hours before they are automatically turned off again.
• Verify that override switch is readily accessible and located so that a person using the device can see the lights being controlled--for example, individual override switch per enclosed office or centrally located switch when serving an open office space.
• Verify that model numbers of all automatic time switch controls are 'listed on the Energy Commission database as “Certified Appliances & Control Devices.” http://www.energy.ca.gov/appliances/database/
Functional Testing
Step 1: Simulate occupied condition.
Set ON time schedule to include actual time or adjust time to be within the ON time schedule (whichever is easier).
Verify and Document
• All lights can be enabled. Some systems may turn the lights on automatically at the scheduled time, but others may require that lights be turned on manually using their respective area control switch.
• Verify the local lighting circuit switch only operates lights in the area in which the switch is located. This is particularly important in enclosed spaces to ensure only lights within the enclosed space are controlled. However, switches serving open spaces should also control only lights in the designated zone.
Step 2: Simulate unoccupied condition.
Set the OFF time schedule to include the actual time, or adjust the time to be within the OFF time schedule (whichever is easier).
Verify and Document
• All non-exempt lights turn off. Most systems warn occupants that the lights are about to turn off by sending a pulse through the lighting circuits to “flicker” the lights or provide another form of visual or audible annunciation.
• Manual override switch is functional. Enabling the manual override switch allows only the lights in the selected space where the switch is located to turn ON. This is particularly important in enclosed spaces to ensure only lights within the enclosed space are controlled, however, switches serving open spaces should also control only lights in the designated zone. The lights should remain ON throughout the override time period (refer to §130.1(c)3B for maximum override times) and the system indicates that the lights are about to be turned off again.
• All non-exempt lights turn off when the next OFF signal is supplied to the lighting control circuits or the override time has expired. In order to reduce testing time associated with the complete OFF-Manual override-OFF sequence, it is recommended that the override time be shortened so that the entire sequence can be witnessed within a reasonable amount of time.
• The device has program backup capabilities that prevent the loss of schedules for at least 7 days, and the loss of time and date setting for at least 72 hours if power is interrupted.
Step 3: Return system back to normal operating condition.
Ensure all schedules, setpoints, operating conditions, and control parameters are placed back at their initial conditions. Ensure the override time period is no more than 2 hours.
It is also good practice to leave a schedule in the time clock itself for easy reference and to leave a blank schedule form so that the users can document any schedule changes. See the example below.