City |
Climate Zone |
Latitude |
Elevation (ft) |
Longitude |
Cooling |
|
|
|
Heating | |||||||||||||||||||
|
0.10% |
0.50% |
1.00% |
2.00% |
Design Wetbulb 0.1% |
Design Wetbulb 0.5% |
Outdoor Daily Range |
Winter Median of Extremes |
Design Drybulb (0.2%) |
Design Drybulb (0.6%) |
HDD* | ||||||||||||||||||
|
DB |
MCWB |
DB |
MCWB |
DB |
MCWB |
DB |
MCWB | |||||||||||||||||||||
|
Galt |
12 |
38.2 |
40 |
121.3 |
101 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
38 |
23 |
28 |
31 |
1240 | |||||||||
|
Garden Acres |
12 |
38 |
20 |
121.3 |
103 |
71 |
98 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
35 |
24 |
28 |
30 |
1334 | |||||||||
|
Garden Grove |
8 |
33.6 |
85 |
117.9 |
98 |
70 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
23 |
31 |
36 |
38 |
| |||||||||
|
Gardena |
8 |
33.9 |
40 |
118.3 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
| |||||||||
|
George AFB |
14 |
34.6 |
2875 |
117.4 |
105 |
67 |
102 |
65 |
101 |
64 |
98 |
62 |
70 |
68 |
31 |
19 |
23 |
26 |
2887 | |||||||||
|
Georgetown RS |
12 |
38.9 |
3001 |
120.8 |
98 |
64 |
95 |
63 |
94 |
63 |
90 |
61 |
68 |
66 |
31 |
18 |
24 |
27 |
| |||||||||
|
Giant Forest |
16 |
36.6 |
6412 |
118.8 |
84 |
56 |
81 |
55 |
80 |
55 |
77 |
53 |
60 |
58 |
26 |
5 |
13 |
18 |
| |||||||||
|
Gillespie Field |
10 |
32.8 |
385 |
117.0 |
98 |
71 |
91 |
70 |
89 |
70 |
85 |
68 |
73 |
71 |
30 |
24 |
29 |
32 |
| |||||||||
|
Gilroy |
4 |
37 |
194 |
121.6 |
101 |
70 |
93 |
68 |
91 |
67 |
86 |
65 |
72 |
69 |
25 |
23 |
28 |
31 |
| |||||||||
|
Glen Avon |
10 |
34 |
827 |
117.5 |
105 |
70 |
101 |
69 |
99 |
69 |
95 |
67 |
74 |
72 |
35 |
28 |
33 |
35 |
| |||||||||
|
Glendale |
9 |
34.2 |
563 |
118.3 |
101 |
70 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
28 |
30 |
35 |
37 |
| |||||||||
|
Glendora |
9 |
34.1 |
822 |
117.9 |
102 |
69 |
98 |
68 |
96 |
68 |
92 |
67 |
73 |
71 |
35 |
30 |
35 |
37 |
| |||||||||
|
Glennville |
16 |
35.7 |
3140 |
118.7 |
97 |
67 |
94 |
66 |
93 |
66 |
90 |
64 |
70 |
68 |
43 |
11 |
18 |
23 |
4423 | |||||||||
|
Gold Rock Rch |
15 |
32.9 |
485 |
114.8 |
113 |
73 |
110 |
72 |
109 |
72 |
106 |
70 |
79 |
77 |
28 |
31 |
36 |
38 |
| |||||||||
|
Golden Hills |
16 |
35.1 |
4000 |
118.5 |
97 |
66 |
93 |
65 |
92 |
65 |
89 |
64 |
69 |
67 |
33 |
13 |
20 |
24 |
| |||||||||
|
Granada Hills |
6 |
34.4 |
1032 |
118.5 |
100 |
70 |
95 |
68 |
93 |
68 |
89 |
66 |
73 |
70 |
37 |
28 |
31 |
34 |
664 | |||||||||
|
Grand Terrace |
10 |
34.1 |
1000 |
117.3 |
105 |
70 |
102 |
68 |
101 |
68 |
97 |
67 |
74 |
72 |
35 |
28 |
33 |
36 |
611 | |||||||||
|
Grant Grove |
13 |
36.7 |
6600 |
119 |
82 |
56 |
78 |
55 |
77 |
54 |
74 |
52 |
59 |
57 |
26 |
6 |
14 |
19 |
7044 | |||||||||
|
Grass Valley |
11 |
39.2 |
2400 |
121.1 |
99 |
67 |
96 |
65 |
95 |
65 |
91 |
63 |
69 |
67 |
29 |
19 |
25 |
28 |
| |||||||||
|
Graton |
2 |
38.4 |
200 |
122.9 |
95 |
68 |
91 |
67 |
88 |
66 |
82 |
64 |
70 |
68 |
34 |
22 |
28 |
31 |
3409 | |||||||||
|
Greenacres |
13 |
35.3 |
400 |
119.1 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
934 | |||||||||
|
Greenfield |
4 |
36.2 |
287 |
121.2 |
92 |
67 |
88 |
65 |
87 |
65 |
84 |
64 |
70 |
68 |
32 |
22 |
27 |
30 |
1020 | |||||||||
|
Grossmont |
7 |
32.7 |
530 |
117 |
96 |
69 |
89 |
68 |
88 |
68 |
84 |
66 |
71 |
69 |
23 |
31 |
36 |
38 |
| |||||||||
|
Grover City |
5 |
35.1 |
100 |
120.6 |
93 |
69 |
86 |
64 |
84 |
64 |
80 |
62 |
67 |
65 |
18 |
30 |
34 |
37 |
| |||||||||
|
Guadalupe |
5 |
35 |
85 |
120.6 |
92 |
66 |
86 |
64 |
84 |
64 |
79 |
62 |
67 |
65 |
18 |
28 |
32 |
35 |
1035 | |||||||||
|
Hacienda Hts |
9 |
34 |
300 |
118 |
100 |
69 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
28 |
31 |
36 |
38 |
| |||||||||
|
Haiwee |
16 |
36.1 |
3825 |
118 |
102 |
65 |
99 |
64 |
98 |
64 |
95 |
62 |
68 |
66 |
27 |
15 |
22 |
26 |
3700 | |||||||||
|
Half Moon Bay |
3 |
37.5 |
60 |
122.4 |
83 |
64 |
76 |
62 |
74 |
61 |
69 |
59 |
65 |
63 |
15 |
32 |
37 |
39 |
3843 | |||||||||
|
Hamilton AFB |
2 |
38.1 |
3 |
122.5 |
95 |
69 |
88 |
67 |
86 |
67 |
81 |
65 |
73 |
70 |
28 |
27 |
30 |
32 |
3311 | |||||||||
|
Hanford |
13 |
36.3 |
242 |
119.7 |
102 |
71 |
99 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
37 |
22 |
28 |
31 |
2736 | |||||||||
|
Happy Camp RS |
16 |
41.8 |
1150 |
123.4 |
103 |
67 |
97 |
66 |
96 |
66 |
92 |
65 |
69 |
67 |
41 |
18 |
24 |
27 |
4263 | |||||||||
|
Hat Creek PH 1 |
16 |
40.9 |
3015 |
121.6 |
99 |
65 |
96 |
64 |
95 |
64 |
91 |
62 |
68 |
66 |
48 |
2 |
7 |
17 |
5689 | |||||||||
|
Hawaiian Gardens |
8 |
33.8 |
75 |
118.1 |
97 |
70 |
91 |
69 |
89 |
69 |
84 |
67 |
72 |
70 |
23 |
32 |
37 |
39 |
| |||||||||
|
Hawthorne |
8 |
33.9 |
70 |
118.4 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
16 |
37 |
40 |
42 |
| |||||||||
|
Hayfield Pumps |
14 |
33.7 |
1370 |
115.6 |
112 |
71 |
108 |
70 |
107 |
70 |
104 |
68 |
77 |
75 |
31 |
24 |
29 |
32 |
1529 | |||||||||
|
Hayward |
3 |
37.7 |
530 |
122.1 |
92 |
66 |
86 |
65 |
85 |
64 |
81 |
62 |
68 |
66 |
24 |
26 |
31 |
34 |
2909 | |||||||||
|
Healdsburg |
2 |
38.6 |
102 |
122.9 |
102 |
69 |
95 |
68 |
94 |
68 |
90 |
66 |
71 |
69 |
37 |
26 |
31 |
34 |
2572 | |||||||||
|
Hemet |
10 |
33.7 |
1655 |
117 |
109 |
70 |
104 |
69 |
103 |
69 |
101 |
67 |
74 |
72 |
40 |
20 |
25 |
28 |
| |||||||||
|
Henshaw Dam |
10 |
33.2 |
2700 |
116.8 |
99 |
68 |
94 |
67 |
93 |
67 |
90 |
66 |
71 |
69 |
38 |
15 |
22 |
26 |
3708 | |||||||||
|
Hercules |
3 |
38 |
15 |
122.3 |
91 |
66 |
87 |
65 |
86 |
65 |
82 |
64 |
69 |
67 |
25 |
30 |
35 |
38 |
823 | |||||||||
|
Hermosa Beach |
6 |
33.9 |
16 |
118.4 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
12 |
38 |
42 |
45 |
| |||||||||
|
Hesperia |
14 |
34.4 |
3191 |
117.3 |
105 |
67 |
101 |
65 |
100 |
65 |
97 |
63 |
70 |
68 |
38 |
14 |
21 |
25 |
1654 | |||||||||
|
Hetch Hetchy |
16 |
38 |
3870 |
119.8 |
93 |
62 |
89 |
61 |
88 |
61 |
85 |
59 |
65 |
63 |
32 |
14 |
21 |
25 |
4816 | |||||||||
|
Highland |
10 |
34.1 |
1315 |
117.2 |
106 |
70 |
102 |
69 |
101 |
69 |
97 |
68 |
74 |
72 |
36 |
26 |
31 |
34 |
| |||||||||
|
Hillcrest Center |
16 |
35.4 |
500 |
|
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
| |||||||||
|
Hillsborough |
3 |
37.6 |
352 |
122.3 |
90 |
66 |
82 |
65 |
80 |
65 |
74 |
64 |
68 |
66 |
23 |
30 |
35 |
37 |
| |||||||||
|
Hilt |
16 |
42 |
2900 |
122.6 |
97 |
64 |
93 |
62 |
92 |
62 |
89 |
60 |
66 |
64 |
39 |
5 |
13 |
18 |
| |||||||||
|
Hollister |
4 |
36.9 |
280 |
121.4 |
96 |
68 |
89 |
67 |
87 |
67 |
81 |
65 |
70 |
68 |
30 |
21 |
27 |
30 |
2725 | |||||||||
|
Hollywood |
9 |
34 |
384 |
118.4 |
96 |
70 |
89 |
69 |
87 |
69 |
83 |
67 |
72 |
70 |
20 |
36 |
41 |
44 |
| |||||||||
|
Home Gardens |
10 |
33.9 |
678 |
117.5 |
104 |
70 |
100 |
69 |
98 |
69 |
92 |
67 |
74 |
72 |
35 |
26 |
31 |
34 |
| |||||||||
|
Hoopa |
2 |
41 |
360 |
123.7 |
100 |
67 |
92 |
66 |
91 |
66 |
87 |
64 |
69 |
67 |
25 |
23 |
28 |
31 |
| |||||||||
|
Huntington Beach |
6 |
33.7 |
40 |
117.8 |
91 |
69 |
83 |
67 |
81 |
67 |
76 |
66 |
71 |
69 |
14 |
34 |
38 |
41 |
| |||||||||
|
Huntington Lake |
16 |
37.2 |
7020 |
119.2 |
80 |
55 |
77 |
54 |
76 |
53 |
73 |
51 |
58 |
56 |
25 |
3 |
11 |
16 |
7632 | |||||||||
|
Huntington Park |
8 |
34 |
175 |
118 |
98 |
70 |
90 |
69 |
88 |
69 |
84 |
67 |
72 |
70 |
20 |
38 |
42 |
45 |
| |||||||||
|
Idlewild |
1 |
41.9 |
1250 |
124 |
103 |
68 |
96 |
66 |
95 |
66 |
92 |
65 |
69 |
67 |
40 |
18 |
24 |
27 |
| |||||||||
|
Idria |
4 |
36.4 |
2650 |
120.7 |
97 |
66 |
92 |
65 |
91 |
64 |
87 |
62 |
68 |
66 |
27 |
24 |
29 |
32 |
3128 | |||||||||
|
Idyllwild |
1 |
33.7 |
5397 |
116.7 |
93 |
62 |
89 |
61 |
88 |
61 |
84 |
60 |
67 |
65 |
35 |
9 |
16 |
21 |
| |||||||||
|
Imperial AP |
15 |
32.8 |
-59 |
115.6 |
114 |
74 |
110 |
73 |
109 |
73 |
106 |
72 |
81 |
79 |
31 |
26 |
31 |
34 |
1060 | |||||||||
|
Imperial Beach |
7 |
32.5 |
23 |
117.1 |
87 |
69 |
82 |
68 |
81 |
68 |
78 |
67 |
71 |
69 |
10 |
35 |
39 |
41 |
1839 | |||||||||
|
Imperial CO |
15 |
32.9 |
-64 |
115.6 |
112 |
73 |
108 |
72 |
107 |
72 |
104 |
71 |
80 |
78 |
31 |
29 |
34 |
36 |
976 | |||||||||
|
Independence |
16 |
36.8 |
3950 |
118.2 |
104 |
61 |
101 |
60 |
100 |
60 |
97 |
60 |
65 |
63 |
31 |
12 |
19 |
24 |
| |||||||||
|
Indio |
15 |
33.7 |
11 |
116.3 |
115 |
75 |
112 |
75 |
111 |
75 |
107 |
74 |
81 |
79 |
30 |
24 |
29 |
32 |
1059 | |||||||||
|
Inglewood |
8 |
33.9 |
105 |
118 |
92 |
68 |
85 |
67 |
84 |
67 |
80 |
65 |
70 |
68 |
15 |
37 |
40 |
42 |
| |||||||||
|
Inyokern NAS |
16 |
35.7 |
2440 |
117.8 |
110 |
71 |
106 |
68 |
105 |
68 |
102 |
66 |
75 |
71 |
37 |
15 |
22 |
26 |
2772 | |||||||||
|
Ione |
12 |
38.3 |
298 |
120.9 |
101 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
38 |
23 |
28 |
31 |
| |||||||||
|
Iron Mtn |
11 |
34.1 |
922 |
115.1 |
116 |
75 |
112 |
74 |
111 |
74 |
108 |
73 |
80 |
78 |
26 |
29 |
34 |
36 |
1251 | |||||||||
|
Irvine |
8 |
33.7 |
50 |
118 |
96 |
69 |
88 |
68 |
86 |
68 |
82 |
67 |
72 |
70 |
27 |
33 |
37 |
40 |
| |||||||||
|
Isla Vista |
6 |
34.5 |
40 |
119.9 |
90 |
69 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
20 |
33 |
38 |
40 |
| |||||||||
|
Jess Valley |
16 |
41.3 |
5300 |
120.3 |
92 |
59 |
89 |
58 |
88 |
58 |
84 |
56 |
63 |
61 |
35 |
-7 |
-2 |
4 |
7045 | |||||||||
|
John Wayne AP |
6 |
33.6 |
115 |
117.9 |
98 |
70 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
26 |
33 |
37 |
39 |
1496 | |||||||||
|
Julian Wynola |
14 |
33.1 |
3650 |
116.8 |
96 |
66 |
91 |
64 |
90 |
64 |
87 |
62 |
69 |
67 |
39 |
20 |
24 |
26 |
4049 | |||||||||
|
Kentfield |
2 |
38 |
120 |
122.6 |
97 |
66 |
91 |
65 |
89 |
65 |
84 |
63 |
70 |
68 |
35 |
27 |
32 |
35 |
3009 | |||||||||
|
Kerman |
13 |
36.6 |
216 |
120.1 |
105 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
34 |
24 |
28 |
30 |
1262 | |||||||||
|
Kern River PH 1 |
13 |
35.5 |
970 |
118.8 |
106 |
72 |
103 |
71 |
102 |
71 |
99 |
69 |
75 |
73 |
26 |
30 |
35 |
37 |
1878 | |||||||||
|
Kern River PH 3 |
16 |
35.8 |
2703 |
118.6 |
103 |
69 |
100 |
68 |
99 |
68 |
96 |
66 |
72 |
70 |
34 |
19 |
25 |
28 |
2891 | |||||||||
|
Kettleman Stn |
13 |
36.1 |
508 |
120.1 |
104 |
71 |
100 |
70 |
98 |
70 |
93 |
68 |
74 |
72 |
31 |
26 |
31 |
34 |
2180 | |||||||||
|
King City |
4 |
36.2 |
320 |
121.1 |
94 |
67 |
90 |
65 |
89 |
65 |
85 |
64 |
70 |
68 |
36 |
20 |
26 |
29 |
2639 | |||||||||
|
Kingsburg |
13 |
36.4 |
297 |
119.6 |
104 |
73 |
101 |
71 |
100 |
71 |
97 |
69 |
75 |
73 |
36 |
24 |
30 |
34 |
1300 | |||||||||
|
Klamath |
1 |
41.5 |
25 |
124.1 |
79 |
62 |
71 |
60 |
70 |
60 |
66 |
58 |
64 |
61 |
18 |
26 |
31 |
33 |
4509 | |||||||||
|
Knights Ferry |
12 |
37.8 |
315 |
120.6 |
103 |
70 |
99 |
68 |
98 |
68 |
94 |
67 |
73 |
71 |
37 |
19 |
25 |
28 |
| |||||||||
|
La Canada-Flintridge |
16 |
34.2 |
1365 |
118 |
99 |
69 |
95 |
68 |
93 |
68 |
88 |
66 |
72 |
70 |
30 |
32 |
36 |
38 |
| |||||||||
|
La Crescenta-Montrose |
9 |
34.2 |
1565 |
118 |
98 |
69 |
94 |
68 |
92 |
68 |
87 |
66 |
72 |
70 |
33 |
31 |
35 |
37 |
| |||||||||
|
La Habra |
8 |
33.9 |
305 |
118 |
100 |
69 |
94 |
68 |
92 |
68 |
87 |
67 |
72 |
70 |
27 |
30 |
35 |
37 |
| |||||||||
|
La Habra Heights |
9 |
34 |
400 |
118 |
100 |
69 |
94 |
68 |
92 |
68 |
87 |
67 |
72 |
70 |
27 |
30 |
35 |
37 |
| |||||||||
|
La Mesa |
7 |
32.8 |
530 |
117 |
94 |
70 |
88 |
69 |
87 |
69 |
84 |
67 |
72 |
70 |
23 |
34 |
39 |
41 |
1567 | |||||||||
|
La Mirada |
9 |
33.9 |
115 |
118 |
99 |
70 |
91 |
69 |
89 |
69 |
85 |
68 |
73 |
71 |
26 |
31 |
36 |
38 |
| |||||||||
|
La Palma |
8 |
33.9 |
75 |
118 |
98 |
69 |
92 |
68 |
90 |
68 |
85 |
67 |
72 |
70 |
25 |
31 |
35 |
38 |
| |||||||||
|
La Puente |
9 |
34 |
320 |
118 |
101 |
71 |
97 |
70 |
95 |
70 |
91 |
69 |
74 |
72 |
28 |
31 |
36 |
38 |
| |||||||||
|
La Quinta |
15 |
33.8 |
400 |
116.3 |
116 |
74 |
112 |
73 |
111 |
73 |
108 |
72 |
79 |
78 |
34 |
26 |
32 |
34 |
332 | |||||||||
|
La Riviera |
12 |
38.6 |
190 |
121.3 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
32 |
30 |
35 |
37 |
1025 | |||||||||
|
La Verne |
9 |
34.1 |
1235 |
118 |
101 |
69 |
97 |
68 |
95 |
68 |
91 |
67 |
73 |
71 |
34 |
29 |
34 |
36 |
| |||||||||
|
Ladera Heights |
8 |
34.1 |
100 |
118.4 |
91 |
67 |
84 |
67 |
83 |
67 |
79 |
66 |
71 |
69 |
14 |
37 |
40 |
42 |
383 | |||||||||
|
Lafayette |
12 |
37.9 |
535 |
122.1 |
100 |
69 |
94 |
67 |
92 |
67 |
87 |
66 |
71 |
69 |
32 |
24 |
29 |
32 |
| |||||||||
|
Laguna Beach |
6 |
33.5 |
35 |
117.8 |
91 |
69 |
83 |
68 |
81 |
68 |
76 |
66 |
71 |
69 |
18 |
30 |
33 |
36 |
2222 | |||||||||
|
Laguna Niguel |
6 |
33.6 |
500 |
117.7 |
95 |
67 |
87 |
66 |
85 |
65 |
81 |
63 |
71 |
67 |
22 |
33 |
37 |
40 |
| |||||||||
|
Lake Arrowhead |
16 |
34.2 |
5205 |
117.2 |
90 |
62 |
86 |
61 |
85 |
61 |
81 |
59 |
66 |
64 |
26 |
13 |
20 |
24 |
5310 | |||||||||
|
Lake Elsinore |
10 |
33.7 |
1233 |
117.3 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
22 |
27 |
30 |
827 | |||||||||
|
Lake Los Angeles |
14 |
34.7 |
2300 |
117.8 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
72 |
70 |
35 |
12 |
17 |
20 |
1455 | |||||||||
|
Lake Spaulding |
16 |
39.3 |
5156 |
120.6 |
89 |
58 |
86 |
57 |
85 |
57 |
83 |
55 |
62 |
60 |
34 |
3 |
11 |
16 |
6447 | |||||||||
|
Lakeland Village |
10 |
33.6 |
1233 |
117.3 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
12 |
27 |
30 |
827 | |||||||||
|
Lakeport |
2 |
39 |
1347 |
122.9 |
97 |
67 |
93 |
66 |
92 |
65 |
88 |
63 |
69 |
67 |
41 |
20 |
26 |
29 |
3728 | |||||||||
|
Lakeshore |
16 |
40.9 |
1075 |
119.2 |
104 |
69 |
100 |
68 |
99 |
68 |
95 |
66 |
71 |
69 |
28 |
29 |
34 |
36 |
| |||||||||
|
Lakeside |
10 |
32.8 |
690 |
117 |
95 |
69 |
90 |
68 |
89 |
68 |
86 |
66 |
72 |
70 |
20 |
26 |
31 |
34 |
| |||||||||
|
Lakewood |
8 |
33.9 |
45 |
118 |
98 |
70 |
90 |
68 |
88 |
68 |
84 |
66 |
72 |
70 |
22 |
33 |
37 |
40 |
| |||||||||
|
Lamont |
13 |
35.3 |
500 |
120 |
106 |
72 |
102 |
71 |
101 |
71 |
98 |
69 |
75 |
73 |
34 |
26 |
32 |
35 |
| |||||||||
|
Lancaster |
14 |
34.7 |
2340 |
118.2 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
66 |
72 |
70 |
35 |
12 |
17 |
20 |
| |||||||||
|
Larksfield-Wikiup |
2 |
38.5 |
170 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 | |||||||||
|
Larkspur |
3 |
37.9 |
20 |
122.5 |
97 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
69 |
68 |
34 |
28 |
33 |
35 |
| |||||||||
|
Las Plumas |
11 |
39.7 |
506 |
121.4 |
104 |
71 |
101 |
70 |
100 |
70 |
96 |
68 |
73 |
71 |
32 |
24 |
29 |
32 |
| |||||||||
|
Lathrop |
12 |
37.8 |
22 |
121.3 |
103 |
71 |
98 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
35 |
24 |
28 |
30 |
1300 | |||||||||
|
Lava Beds |
16 |
41.7 |
4770 |
121.5 |
93 |
59 |
89 |
58 |
88 |
58 |
84 |
56 |
63 |
61 |
41 |
-1 |
4 |
11 |
| |||||||||
|
Lawndale |
8 |
33.9 |
66 |
118 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
16 |
37 |
40 |
42 |
| |||||||||
|
Le Grand |
12 |
37.2 |
255 |
120.3 |
101 |
70 |
96 |
68 |
95 |
68 |
91 |
66 |
72 |
70 |
38 |
23 |
28 |
31 |
2696 | |||||||||
|
Lemon Grove |
7 |
32.7 |
437 |
117.2 |
96 |
71 |
88 |
69 |
87 |
69 |
84 |
67 |
72 |
70 |
19 |
34 |
38 |
41 |
| |||||||||
|
Lemoncove |
13 |
36.4 |
513 |
119 |
105 |
72 |
102 |
70 |
101 |
70 |
98 |
68 |
72 |
70 |
38 |
25 |
38 |
41 |
2513 | |||||||||
|
Lemoore NAS |
13 |
36.3 |
228 |
120 |
104 |
72 |
101 |
71 |
100 |
71 |
97 |
69 |
74 |
72 |
37 |
19 |
25 |
28 |
2960 | |||||||||
|
Lennox |
8 |
33.9 |
71 |
117.8 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
16 |
37 |
41 |
44 |
| |||||||||
|
Lincoln Village |
12 |
38 |
12 |
121.3 |
101 |
70 |
96 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
37 |
24 |
28 |
30 |
1334 | |||||||||
|
Linda |
11 |
39 |
60 |
121.6 |
105 |
72 |
102 |
70 |
101 |
70 |
97 |
68 |
74 |
72 |
30 |
27 |
32 |
35 |
1160 | |||||||||
|
Lindsay |
13 |
36.2 |
395 |
119.1 |
105 |
72 |
101 |
71 |
100 |
71 |
97 |
69 |
74 |
72 |
40 |
24 |
29 |
32 |
2634 | |||||||||
|
Little Panoche |
13 |
36.8 |
677 |
120.7 |
100 |
68 |
94 |
67 |
92 |
67 |
86 |
66 |
71 |
69 |
33 |
23 |
28 |
31 |
| |||||||||
|
Live Oak |
11 |
39.2 |
75 |
121.7 |
105 |
70 |
102 |
69 |
101 |
69 |
97 |
69 |
73 |
71 |
36 |
24 |
29 |
32 |
1160 | |||||||||
|
Livermore |
12 |
37.7 |
490 |
122 |
100 |
69 |
95 |
68 |
93 |
68 |
88 |
67 |
71 |
70 |
35 |
22 |
25 |
28 |
3012 | |||||||||
|
Livingston |
12 |
37.3 |
165 |
120.7 |
103 |
72 |
100 |
70 |
99 |
70 |
95 |
68 |
74 |
72 |
39 |
24 |
30 |
34 |
1244 | |||||||||
|
Llano Shawnee |
14 |
34.5 |
3820 |
117.8 |
104 |
68 |
99 |
67 |
98 |
67 |
95 |
65 |
71 |
69 |
31 |
21 |
27 |
31 |
| |||||||||
|
Lodgepole |
16 |
36.6 |
6735 |
118.7 |
84 |
57 |
80 |
56 |
80 |
56 |
78 |
54 |
60 |
58 |
26 |
-4 |
1 |
7 |
| |||||||||
|
Lodi |
12 |
38.1 |
40 |
121.3 |
101 |
70 |
97 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
38 |
23 |
28 |
31 |
2859 | |||||||||
|
Loma Linda |
10 |
34 |
1150 |
117.5 |
106 |
70 |
103 |
69 |
102 |
69 |
99 |
67 |
74 |
72 |
36 |
27 |
32 |
35 |
| |||||||||
|
Lomita |
6 |
33.8 |
56 |
119 |
95 |
69 |
87 |
68 |
85 |
68 |
81 |
66 |
71 |
69 |
18 |
33 |
38 |
40 |
| |||||||||
|
Lompoc |
5 |
34.9 |
95 |
120.5 |
84 |
63 |
77 |
62 |
76 |
62 |
72 |
60 |
65 |
63 |
18 |
26 |
31 |
34 |
2888 | |||||||||
|
Long Beach |
6 |
33.7 |
34 |
118.2 |
97 |
70 |
88 |
68 |
86 |
67 |
82 |
65 |
65 |
63 |
18 |
35 |
31 |
34 |
| |||||||||
|
Long Beach AP |
8 |
33.8 |
25 |
118.2 |
99 |
71 |
90 |
69 |
88 |
68 |
84 |
66 |
73 |
71 |
21 |
33 |
38 |
41 |
1606 | |||||||||
|
Loomis |
11 |
38.8 |
408 |
121.2 |
107 |
71 |
103 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
39 |
21 |
27 |
30 |
| |||||||||
|
Los Alamitos NAS |
8 |
33.8 |
30 |
118.1 |
98 |
71 |
89 |
69 |
87 |
69 |
83 |
68 |
73 |
71 |
23 |
32 |
37 |
39 |
1740 | |||||||||
|
Los Altos |
4 |
37.3 |
163 |
122 |
96 |
68 |
88 |
65 |
86 |
64 |
80 |
62 |
70 |
68 |
26 |
28 |
33 |
35 |
| |||||||||
|
Los Altos Hills |
4 |
37.3 |
183 |
122.1 |
93 |
67 |
85 |
64 |
83 |
64 |
77 |
63 |
68 |
66 |
25 |
28 |
33 |
35 |
1103 | |||||||||
|
Los Angeles AP |
6 |
33.9 |
97 |
118.4 |
91 |
67 |
84 |
67 |
83 |
67 |
79 |
66 |
71 |
69 |
14 |
37 |
40 |
42 |
1819 | |||||||||
|
Los Angeles CO |
9 |
34 |
270 |
118.2 |
99 |
69 |
92 |
68 |
90 |
68 |
86 |
67 |
72 |
70 |
21 |
38 |
41 |
43 |
1245 | |||||||||
|
Los Banos |
12 |
37 |
120 |
120.9 |
100 |
70 |
96 |
68 |
94 |
68 |
88 |
67 |
72 |
70 |
42 |
22 |
28 |
31 |
2616 | |||||||||
|
Los Banos Res |
12 |
37 |
407 |
120.9 |
101 |
70 |
97 |
68 |
95 |
68 |
89 |
67 |
72 |
70 |
42 |
23 |
29 |
31 |
| |||||||||
|
Los Gatos |
4 |
37.2 |
365 |
122 |
98 |
69 |
90 |
67 |
88 |
67 |
82 |
66 |
71 |
69 |
32 |
26 |
31 |
34 |
2741 | |||||||||
|
Los Serranos |
10 |
34.1 |
714 |
117.7 |
104 |
70 |
100 |
69 |
98 |
69 |
94 |
68 |
74 |
72 |
35 |
27 |
32 |
35 |
706 | |||||||||
|
Lucas Vly-Marinwood |
2 |
38.3 |
20 |
122.6 |
79 |
63 |
74 |
62 |
71 |
61 |
65 |
59 |
64 |
62 |
12 |
30 |
35 |
37 |
874 | |||||||||
|
Lucerne Valley |
14 |
34.5 |
2957 |
117 |
105 |
67 |
101 |
66 |
100 |
66 |
98 |
64 |
71 |
69 |
38 |
12 |
19 |
24 |
| |||||||||
|
Lynwood |
8 |
33.9 |
88 |
118 |
98 |
70 |
90 |
69 |
88 |
69 |
83 |
67 |
72 |
70 |
21 |
32 |
37 |
39 |
| |||||||||