City |
Climate Zone |
Latitude |
Elevation (ft) |
Longitude |
Cooling |
|
|
|
Heating | |||||||||||||||||||
|
0.10% |
0.50% |
1.00% |
2.00% |
Design Wetbulb 0.1% |
Design Wetbulb 0.5% |
Outdoor Daily Range |
Winter Median of Extremes |
Design Drybulb (0.2%) |
Design Drybulb (0.6%) |
HDD* | ||||||||||||||||||
|
DB |
MCWB |
DB |
MCWB |
DB |
MCWB |
DB |
MCWB | |||||||||||||||||||||
|
Sacramento AP |
12 |
38.5 |
17 |
121.5 |
104 |
72 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
71 |
35 |
26 |
31 |
33 |
2843 | |||||||||
|
Sacramento CO |
12 |
38.6 |
84 |
121.5 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
32 |
30 |
35 |
37 |
| |||||||||
|
Saint Helena |
2 |
38.5 |
225 |
122.5 |
102 |
70 |
98 |
69 |
97 |
69 |
93 |
67 |
72 |
70 |
40 |
22 |
28 |
31 |
2878 | |||||||||
|
Saint Mary's College |
12 |
37.8 |
623 |
122.1 |
98 |
69 |
93 |
68 |
91 |
68 |
86 |
66 |
71 |
69 |
28 |
21 |
27 |
30 |
3543 | |||||||||
|
Salinas 3 E |
3 |
36.7 |
85 |
121.6 |
86 |
66 |
83 |
65 |
82 |
64 |
79 |
62 |
68 |
66 |
20 |
26 |
31 |
34 |
| |||||||||
|
Salinas AP |
3 |
36.7 |
69 |
121.6 |
85 |
67 |
82 |
65 |
81 |
64 |
78 |
62 |
69 |
66 |
20 |
28 |
33 |
35 |
2959 | |||||||||
|
Salt Springs PH |
16 |
38.5 |
3700 |
120.2 |
95 |
62 |
92 |
61 |
91 |
61 |
87 |
59 |
66 |
64 |
27 |
19 |
25 |
28 |
3857 | |||||||||
|
Salyer RS |
16 |
40.9 |
623 |
123.6 |
102 |
69 |
95 |
67 |
93 |
66 |
87 |
64 |
70 |
68 |
33 |
22 |
28 |
31 |
| |||||||||
|
San Anselmo |
2 |
38 |
50 |
122 |
95 |
67 |
89 |
66 |
87 |
66 |
82 |
65 |
70 |
68 |
32 |
26 |
31 |
33 |
| |||||||||
|
San Antonio Canyon |
10 |
34.2 |
2394 |
117.7 |
100 |
68 |
96 |
67 |
94 |
67 |
90 |
65 |
72 |
70 |
33 |
29 |
35 |
39 |
| |||||||||
|
San Antonio Mission |
4 |
36 |
1060 |
117.7 |
99 |
69 |
94 |
68 |
92 |
68 |
88 |
67 |
71 |
69 |
28 |
19 |
25 |
28 |
| |||||||||
|
San Bernardino |
10 |
34.1 |
1125 |
117.3 |
106 |
70 |
102 |
69 |
101 |
69 |
98 |
68 |
75 |
72 |
39 |
27 |
31 |
33 |
1777 | |||||||||
|
San Bruno |
3 |
37.7 |
20 |
122.4 |
86 |
66 |
80 |
64 |
78 |
64 |
73 |
62 |
67 |
65 |
23 |
30 |
35 |
38 |
3042 | |||||||||
|
San Carlos |
3 |
37.5 |
26 |
122.3 |
92 |
67 |
88 |
65 |
86 |
65 |
82 |
63 |
68 |
66 |
28 |
28 |
33 |
35 |
| |||||||||
|
San Clemente |
6 |
33.4 |
208 |
118.6 |
91 |
68 |
85 |
67 |
84 |
67 |
80 |
66 |
71 |
69 |
12 |
31 |
35 |
37 |
| |||||||||
|
San Diego AP |
7 |
32.7 |
13 |
117.2 |
88 |
70 |
83 |
69 |
82 |
69 |
78 |
68 |
72 |
70 |
13 |
38 |
42 |
44 |
1507 | |||||||||
|
San Dimas |
9 |
34 |
955 |
118.4 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
72 |
35 |
30 |
35 |
37 |
| |||||||||
|
San Fernando |
9 |
34.3 |
977 |
118.5 |
104 |
71 |
99 |
70 |
98 |
70 |
94 |
68 |
74 |
72 |
37 |
30 |
35 |
37 |
1800 | |||||||||
|
San Francisco AP |
3 |
37.6 |
8 |
122.4 |
89 |
66 |
83 |
64 |
80 |
63 |
74 |
61 |
67 |
64 |
20 |
31 |
35 |
38 |
3042 | |||||||||
|
San Francisco CO |
3 |
37.8 |
52 |
122.4 |
84 |
65 |
79 |
63 |
77 |
62 |
71 |
60 |
66 |
63 |
14 |
38 |
41 |
44 |
3080 | |||||||||
|
San Gabriel FD |
9 |
34.1 |
450 |
118.1 |
99 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
30 |
30 |
35 |
37 |
1532 | |||||||||
|
San Gregorio 2 SE |
3 |
37.3 |
275 |
122.4 |
87 |
66 |
81 |
63 |
79 |
63 |
74 |
61 |
68 |
65 |
30 |
27 |
32 |
35 |
| |||||||||
|
San Jacinto |
10 |
33.8 |
1535 |
117 |
110 |
70 |
105 |
69 |
104 |
69 |
102 |
68 |
75 |
73 |
41 |
20 |
26 |
29 |
2376 | |||||||||
|
San Jose |
4 |
37.4 |
67 |
121.9 |
94 |
68 |
86 |
66 |
84 |
66 |
78 |
64 |
70 |
68 |
26 |
29 |
34 |
36 |
2438 | |||||||||
|
San Leandro |
3 |
37.7 |
45 |
122.2 |
89 |
67 |
83 |
64 |
81 |
64 |
76 |
62 |
69 |
66 |
22 |
28 |
33 |
35 |
| |||||||||
|
San Lorenzo |
3 |
37.7 |
45 |
122.1 |
89 |
67 |
83 |
64 |
81 |
64 |
76 |
62 |
69 |
66 |
23 |
28 |
33 |
36 |
| |||||||||
|
San Luis Dam |
12 |
37.1 |
277 |
121.1 |
97 |
68 |
91 |
66 |
90 |
66 |
86 |
64 |
70 |
68 |
32 |
25 |
30 |
33 |
| |||||||||
|
San Luis Obispo |
5 |
35.3 |
320 |
120.7 |
94 |
63 |
87 |
63 |
85 |
63 |
81 |
62 |
67 |
65 |
26 |
30 |
33 |
35 |
2498 | |||||||||
|
San Marcos |
10 |
33.1 |
567 |
117.2 |
97 |
69 |
98 |
68 |
94 |
68 |
84 |
67 |
72 |
70 |
29 |
26 |
31 |
34 |
662 | |||||||||
|
San Marino |
9 |
34.2 |
300 |
118.1 |
100 |
69 |
95 |
68 |
93 |
68 |
88 |
66 |
73 |
71 |
28 |
30 |
35 |
37 |
| |||||||||
|
San Mateo |
3 |
37.5 |
21 |
122.3 |
92 |
67 |
84 |
65 |
82 |
65 |
76 |
63 |
68 |
66 |
24 |
31 |
36 |
38 |
2655 | |||||||||
|
San Nicholas Island |
6 |
33.2 |
504 |
119.5 |
85 |
66 |
78 |
65 |
76 |
65 |
70 |
64 |
69 |
67 |
11 |
39 |
43 |
45 |
2454 | |||||||||
|
San Pablo |
3 |
37.6 |
30 |
122.3 |
90 |
65 |
84 |
63 |
82 |
63 |
77 |
61 |
69 |
66 |
17 |
29 |
34 |
37 |
| |||||||||
|
San Pedro |
6 |
33.7 |
10 |
118.3 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
72 |
70 |
13 |
35 |
31 |
34 |
1819 | |||||||||
|
San Rafael |
2 |
38 |
40 |
122.6 |
96 |
67 |
90 |
65 |
88 |
65 |
83 |
63 |
71 |
68 |
29 |
30 |
35 |
37 |
2440 | |||||||||
|
San Ramon |
12 |
37.7 |
360 |
122 |
99 |
69 |
93 |
67 |
91 |
67 |
86 |
65 |
70 |
68 |
35 |
24 |
29 |
32 |
1369 | |||||||||
|
Sandberg |
16 |
34.8 |
4517 |
118.7 |
95 |
63 |
91 |
61 |
90 |
61 |
87 |
59 |
67 |
65 |
32 |
17 |
21 |
24 |
4427 | |||||||||
|
Sanger |
13 |
36.7 |
364 |
119.6 |
105 |
72 |
101 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
37 |
24 |
30 |
34 |
| |||||||||
|
Santa Ana FS |
8 |
33.8 |
115 |
117.8 |
98 |
70 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
26 |
33 |
35 |
38 |
1430 | |||||||||
|
Santa Barbara AP |
6 |
34.4 |
9 |
119.8 |
90 |
69 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
20 |
29 |
34 |
36 |
2487 | |||||||||
|
Santa Barbara CO |
6 |
34.4 |
5 |
119.7 |
91 |
69 |
84 |
67 |
82 |
67 |
78 |
65 |
70 |
68 |
22 |
33 |
38 |
40 |
1994 | |||||||||
|
Santa Clara Univ |
4 |
37.4 |
88 |
121.9 |
90 |
67 |
87 |
65 |
86 |
65 |
82 |
63 |
69 |
67 |
30 |
29 |
34 |
36 |
2566 | |||||||||
|
Santa Clarita |
9 |
34.4 |
1300 |
118.5 |
103 |
71 |
98 |
70 |
97 |
70 |
93 |
68 |
74 |
72 |
36 |
30 |
35 |
37 |
| |||||||||
|
Santa Cruz |
3 |
37 |
125 |
122 |
94 |
68 |
88 |
66 |
86 |
66 |
81 |
64 |
69 |
67 |
28 |
27 |
32 |
35 |
3136 | |||||||||
|
Santa Fe Springs |
9 |
33.9 |
280 |
118.1 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
36 |
38 |
| |||||||||
|
Santa Maria AP |
5 |
34.9 |
236 |
120.5 |
90 |
66 |
83 |
64 |
82 |
63 |
78 |
61 |
67 |
65 |
23 |
25 |
31 |
33 |
3053 | |||||||||
|
Santa Monica |
6 |
34 |
15 |
118.5 |
85 |
67 |
78 |
66 |
76 |
66 |
72 |
64 |
69 |
67 |
15 |
39 |
44 |
46 |
1873 | |||||||||
|
Santa Paula |
9 |
34.4 |
263 |
119.1 |
101 |
71 |
94 |
70 |
92 |
70 |
87 |
68 |
73 |
71 |
28 |
28 |
33 |
35 |
2030 | |||||||||
|
Santa Rosa |
2 |
38.5 |
167 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
2980 | |||||||||
|
Santee |
10 |
32.8 |
400 |
117 |
96 |
69 |
91 |
68 |
90 |
68 |
87 |
67 |
72 |
70 |
20 |
25 |
30 |
33 |
| |||||||||
|
Saratoga |
4 |
37.3 |
500 |
122 |
96 |
67 |
88 |
66 |
86 |
66 |
80 |
65 |
70 |
68 |
31 |
27 |
32 |
35 |
| |||||||||
|
Sausalito |
3 |
37.9 |
10 |
122.5 |
85 |
66 |
80 |
65 |
78 |
65 |
73 |
63 |
67 |
65 |
12 |
30 |
34 |
36 |
| |||||||||
|
Sawyer's Bar RS |
16 |
41.3 |
2169 |
123.1 |
100 |
66 |
95 |
65 |
93 |
64 |
88 |
62 |
68 |
66 |
38 |
14 |
21 |
25 |
4102 | |||||||||
|
Scotia |
1 |
40.5 |
139 |
124.4 |
78 |
61 |
74 |
60 |
73 |
60 |
69 |
58 |
63 |
61 |
19 |
28 |
33 |
35 |
3954 | |||||||||
|
Scotts Valley |
3 |
37 |
400 |
122 |
94 |
68 |
88 |
66 |
86 |
66 |
81 |
64 |
69 |
67 |
28 |
27 |
32 |
35 |
1097 | |||||||||
|
Seal Beach |
6 |
33.8 |
21 |
118.1 |
94 |
69 |
86 |
68 |
84 |
67 |
80 |
65 |
71 |
69 |
15 |
35 |
40 |
42 |
1519 | |||||||||
|
Seaside |
3 |
36.6 |
17 |
122.9 |
85 |
66 |
79 |
64 |
77 |
64 |
73 |
62 |
67 |
65 |
20 |
30 |
35 |
37 |
| |||||||||
|
Sebastapol |
2 |
38.4 |
102 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 | |||||||||
|
Selma |
13 |
36.6 |
305 |
119.6 |
104 |
73 |
101 |
71 |
100 |
70 |
97 |
68 |
75 |
73 |
38 |
24 |
30 |
34 |
| |||||||||
|
Sepulveda |
9 |
34.2 |
818 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
32 |
28 |
33 |
36 |
664 | |||||||||
|
Shafter |
13 |
35.5 |
345 |
119.2 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
28 |
24 |
29 |
32 |
2185 | |||||||||
|
Shasta Dam |
11 |
40.7 |
1076 |
122.4 |
105 |
69 |
101 |
68 |
99 |
68 |
95 |
67 |
72 |
70 |
27 |
29 |
34 |
36 |
2943 | |||||||||
|
Shelter Cove |
1 |
40 |
110 |
124.1 |
80 |
61 |
73 |
60 |
72 |
59 |
68 |
57 |
63 |
61 |
15 |
34 |
39 |
41 |
| |||||||||
|
Sherman Oaks |
9 |
34.2 |
657 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
28 |
29 |
34 |
37 |
664 | |||||||||
|
Sierra City |
16 |
39.6 |
4230 |
120.1 |
96 |
62 |
93 |
61 |
92 |
61 |
89 |
59 |
66 |
64 |
43 |
12 |
19 |
24 |
| |||||||||
|
Sierra Madre |
9 |
34.2 |
1153 |
118.1 |
102 |
69 |
96 |
68 |
94 |
68 |
90 |
67 |
73 |
71 |
27 |
32 |
37 |
39 |
| |||||||||
|
Sierraville RS |
16 |
39.6 |
4975 |
120.4 |
94 |
60 |
91 |
59 |
90 |
59 |
86 |
57 |
64 |
62 |
44 |
-10 |
-4 |
0 |
6893 | |||||||||
|
Signal Hill |
6 |
33.5 |
100 |
118.2 |
99 |
70 |
90 |
69 |
88 |
68 |
84 |
66 |
72 |
70 |
19 |
35 |
39 |
42 |
| |||||||||
|
Simi Valley |
9 |
34.4 |
500 |
118.8 |
98 |
70 |
93 |
68 |
91 |
68 |
87 |
66 |
73 |
71 |
30 |
28 |
33 |
35 |
| |||||||||
|
Solana Beach |
7 |
33 |
15 |
117.3 |
87 |
68 |
83 |
67 |
81 |
67 |
77 |
65 |
70 |
68 |
10 |
35 |
39 |
41 |
| |||||||||
|
Soledad |
3 |
36.4 |
200 |
121.3 |
90 |
67 |
87 |
65 |
86 |
65 |
82 |
64 |
70 |
67 |
23 |
24 |
29 |
32 |
1020 | |||||||||
|
Sonoma |
2 |
38.3 |
70 |
122.5 |
101 |
70 |
96 |
69 |
94 |
69 |
90 |
67 |
72 |
70 |
40 |
22 |
28 |
31 |
2998 | |||||||||
|
Sonora RS |
12 |
38 |
1749 |
120.4 |
103 |
68 |
100 |
67 |
99 |
67 |
95 |
66 |
72 |
70 |
34 |
20 |
26 |
29 |
3537 | |||||||||
|
Soquel |
3 |
37 |
50 |
122 |
94 |
67 |
88 |
66 |
86 |
65 |
81 |
63 |
69 |
67 |
24 |
27 |
32 |
35 |
1097 | |||||||||
|
South El Monte |
9 |
34 |
270 |
118.1 |
101 |
72 |
97 |
70 |
95 |
70 |
91 |
68 |
74 |
72 |
28 |
31 |
36 |
38 |
| |||||||||
|
South Entr Yosemite |
16 |
37.5 |
5120 |
119.6 |
92 |
61 |
88 |
60 |
87 |
60 |
84 |
59 |
64 |
62 |
36 |
8 |
15 |
20 |
5789 | |||||||||
|
South Gate |
8 |
33.9 |
120 |
118.2 |
97 |
70 |
90 |
69 |
88 |
69 |
84 |
67 |
72 |
70 |
21 |
32 |
37 |
39 |
| |||||||||
|
South Laguna |
6 |
33.6 |
100 |
117.7 |
91 |
69 |
83 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
18 |
30 |
33 |
36 |
586 | |||||||||
|
South Lake Tahoe |
16 |
38.9 |
6200 |
120 |
85 |
56 |
82 |
55 |
79 |
55 |
71 |
54 |
60 |
58 |
33 |
-2 |
3 |
10 |
| |||||||||
|
South Oroville |
11 |
39.5 |
174 |
121.6 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
1385 | |||||||||
|
South Pasadena |
9 |
34 |
657 |
118.2 |
99 |
69 |
94 |
68 |
92 |
68 |
88 |
67 |
73 |
71 |
30 |
31 |
36 |
38 |
| |||||||||
|
South San Francisco |
3 |
37.7 |
10 |
122.4 |
87 |
67 |
81 |
64 |
78 |
64 |
72 |
62 |
68 |
65 |
20 |
32 |
36 |
38 |
| |||||||||
|
South San Gabriel |
9 |
34.1 |
450 |
118.1 |
99 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
73 |
30 |
35 |
37 |
431 | |||||||||
|
South Whittier |
9 |
33.9 |
300 |
118 |
100 |
70 |
92 |
69 |
90 |
69 |
84 |
68 |
73 |
71 |
30 |
31 |
36 |
38 |
| |||||||||
|
South Yuba City |
11 |
39.1 |
59 |
121.6 |
105 |
69 |
101 |
69 |
100 |
69 |
96 |
68 |
72 |
71 |
36 |
24 |
29 |
32 |
1160 | |||||||||
|
Spring Valley |
10 |
32.7 |
300 |
117 |
94 |
69 |
86 |
68 |
85 |
68 |
82 |
66 |
71 |
69 |
30 |
34 |
38 |
41 |
| |||||||||
|
Squaw Valley |
16 |
39.2 |
6235 |
120.2 |
88 |
57 |
85 |
56 |
84 |
56 |
80 |
54 |
61 |
59 |
40 |
-10 |
-4 |
0 |
| |||||||||
|
Squirrel Inn |
16 |
34.2 |
5680 |
117.2 |
86 |
61 |
82 |
60 |
81 |
60 |
77 |
58 |
65 |
63 |
23 |
12 |
18 |
22 |
5175 | |||||||||
|
Stanford |
4 |
37.5 |
23 |
122.1 |
93 |
66 |
85 |
64 |
83 |
64 |
77 |
62 |
68 |
66 |
25 |
26 |
31 |
34 |
1103 | |||||||||
|
Stanton |
8 |
33.6 |
45 |
118 |
98 |
69 |
91 |
68 |
89 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
36 |
38 |
| |||||||||
|
Stockton AP |
12 |
37.9 |
22 |
121.3 |
103 |
71 |
98 |
69 |
97 |
69 |
93 |
67 |
73 |
71 |
35 |
24 |
28 |
30 |
2806 | |||||||||
|
Stockton FS 4 |
12 |
38 |
12 |
121.3 |
101 |
70 |
96 |
68 |
95 |
68 |
91 |
67 |
72 |
70 |
37 |
24 |
28 |
30 |
2846 | |||||||||
|
Stony Gorge Res |
11 |
39.6 |
791 |
122.5 |
104 |
70 |
99 |
69 |
97 |
69 |
93 |
67 |
72 |
70 |
37 |
21 |
27 |
30 |
3149 | |||||||||
|
Strawberry Valley |
16 |
39.6 |
3808 |
121.1 |
96 |
63 |
93 |
62 |
92 |
62 |
88 |
60 |
66 |
64 |
32 |
14 |
21 |
25 |
5120 | |||||||||
|
Studio City |
9 |
34.3 |
620 |
118.4 |
102 |
70 |
97 |
69 |
95 |
69 |
91 |
67 |
73 |
71 |
31 |
28 |
33 |
36 |
664 | |||||||||
|
Suisun City |
12 |
38.2 |
72 |
122 |
103 |
71 |
98 |
69 |
96 |
68 |
91 |
66 |
73 |
70 |
35 |
24 |
29 |
32 |
1299 | |||||||||
|
Sun City |
10 |
33.7 |
1420 |
117.2 |
105 |
70 |
101 |
69 |
100 |
69 |
97 |
68 |
74 |
72 |
39 |
22 |
27 |
30 |
827 | |||||||||
|
Sunland |
16 |
34.3 |
1460 |
118.3 |
107 |
71 |
102 |
70 |
100 |
70 |
96 |
68 |
74 |
72 |
36 |
28 |
33 |
36 |
| |||||||||
|
Sunnyvale |
4 |
37.3 |
97 |
122 |
96 |
68 |
88 |
66 |
86 |
66 |
80 |
64 |
70 |
68 |
26 |
29 |
34 |
36 |
2511 | |||||||||
|
Susanville AP |
16 |
40.4 |
4148 |
120.6 |
98 |
62 |
95 |
61 |
94 |
61 |
90 |
59 |
66 |
64 |
38 |
-1 |
4 |
11 |
6233 | |||||||||
|
Taft |
13 |
35.1 |
987 |
119.5 |
106 |
71 |
102 |
70 |
101 |
70 |
98 |
68 |
74 |
72 |
34 |
26 |
31 |
35 |
934 | |||||||||
|
Tahoe City |
16 |
39.2 |
6230 |
120.1 |
84 |
56 |
81 |
55 |
80 |
55 |
76 |
53 |
60 |
58 |
36 |
2 |
7 |
14 |
8085 | |||||||||
|
Tahoe Valley AP |
16 |
38.9 |
6254 |
120.0 |
85 |
56 |
82 |
55 |
81 |
55 |
77 |
53 |
60 |
58 |
38 |
-5 |
2 |
6 |
| |||||||||
|
Tamalpais-Homestead Valley |
3 |
37.9 |
25 |
122.5 |
97 |
68 |
91 |
66 |
89 |
66 |
84 |
64 |
70 |
68 |
28 |
28 |
33 |
35 |
874 | |||||||||
|
Tarzana |
9 |
34.2 |
800 |
118.6 |
104 |
71 |
99 |
69 |
97 |
69 |
93 |
68 |
74 |
71 |
27 |
27 |
32 |
35 |
664 | |||||||||
|
Tehachapi |
16 |
35.1 |
3975 |
118.5 |
97 |
66 |
93 |
65 |
92 |
65 |
89 |
64 |
69 |
67 |
33 |
13 |
20 |
24 |
4494 | |||||||||
|
Tejon Rancho |
16 |
35 |
1425 |
118.8 |
107 |
71 |
103 |
70 |
102 |
70 |
99 |
68 |
74 |
72 |
27 |
24 |
29 |
32 |
2602 | |||||||||
|
Temecula |
10 |
33.5 |
1006 |
117.2 |
101 |
69 |
96 |
68 |
95 |
68 |
91 |
67 |
73 |
71 |
34 |
24 |
29 |
32 |
| |||||||||
|
Temple City |
9 |
34.1 |
403 |
118.1 |
101 |
70 |
95 |
69 |
93 |
69 |
89 |
68 |
73 |
71 |
27 |
30 |
35 |
37 |
| |||||||||
|
Termo |
16 |
40.9 |
5300 |
120.5 |
95 |
60 |
92 |
59 |
91 |
59 |
87 |
57 |
64 |
62 |
37 |
-17 |
-11 |
-4 |
| |||||||||
|
Thermal AP |
15 |
33.6 |
-112 |
116.1 |
114 |
74 |
110 |
74 |
109 |
74 |
106 |
74 |
80 |
79 |
29 |
26 |
31 |
35 |
1154 | |||||||||
|
Thermalito |
11 |
37.9 |
25 |
121.6 |
106 |
71 |
104 |
70 |
102 |
70 |
98 |
69 |
74 |
72 |
37 |
25 |
30 |
33 |
| |||||||||
|
Thousand Oaks |
9 |
34.2 |
810 |
118.8 |
98 |
69 |
93 |
68 |
92 |
68 |
88 |
67 |
72 |
70 |
30 |
27 |
32 |
35 |
| |||||||||
|
Three Rivers PH 1 |
13 |
36.5 |
1140 |
118.9 |
105 |
70 |
102 |
69 |
101 |
69 |
98 |
67 |
73 |
71 |
38 |
24 |
30 |
32 |
2642 | |||||||||
|
Tiburon |
3 |
37.9 |
90 |
122.5 |
85 |
66 |
80 |
65 |
78 |
65 |
73 |
63 |
67 |
65 |
12 |
30 |
34 |
36 |
| |||||||||
|
Tiger Creek PH |
16 |
38.5 |
2355 |
120.5 |
100 |
66 |
96 |
65 |
95 |
65 |
92 |
63 |
69 |
67 |
36 |
20 |
26 |
29 |
3795 | |||||||||
|
Torrance |
6 |
33.8 |
110 |
118.3 |
93 |
69 |
86 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
1859 | |||||||||
|
Tracy Carbona |
12 |
37.7 |
140 |
121.4 |
102 |
70 |
97 |
68 |
95 |
68 |
90 |
67 |
72 |
70 |
38 |
24 |
29 |
32 |
2704 | |||||||||
|
Tracy Pumps |
12 |
37.8 |
61 |
121.4 |
104 |
71 |
99 |
69 |
97 |
69 |
92 |
68 |
73 |
71 |
39 |
23 |
28 |
31 |
| |||||||||
|
Travis AFB |
12 |
38.3 |
72 |
121.9 |
103 |
71 |
98 |
69 |
96 |
68 |
91 |
66 |
73 |
70 |
35 |
24 |
29 |
32 |
2725 | |||||||||
|
Trinity Dam |
16 |
40.8 |
2500 |
122.8 |
99 |
65 |
94 |
64 |
92 |
64 |
88 |
62 |
68 |
66 |
37 |
17 |
24 |
28 |
| |||||||||
|
Trona |
14 |
35.8 |
1695 |
117.4 |
113 |
72 |
109 |
70 |
108 |
70 |
105 |
68 |
76 |
73 |
35 |
18 |
24 |
27 |
2415 | |||||||||
|
Truckee RS |
16 |
39.3 |
5995 |
120.2 |
90 |
58 |
87 |
57 |
86 |
57 |
82 |
55 |
62 |
60 |
40 |
-10 |
-4 |
0 |
8230 | |||||||||
|
Tujunga |
16 |
34.3 |
1820 |
118.3 |
103 |
70 |
99 |
69 |
98 |
69 |
94 |
67 |
73 |
71 |
36 |
20 |
26 |
29 |
| |||||||||
|
Tulare |
13 |
36.2 |
290 |
119.4 |
105 |
72 |
101 |
71 |
100 |
71 |
96 |
69 |
74 |
72 |
39 |
24 |
30 |
34 |
| |||||||||
|
Tulelake |
16 |
42 |
4035 |
121.5 |
92 |
60 |
88 |
59 |
87 |
59 |
83 |
57 |
63 |
61 |
41 |
-5 |
0 |
6 |
6854 | |||||||||
|
Turlock |
12 |
37.5 |
100 |
120.9 |
104 |
72 |
100 |
70 |
99 |
70 |
95 |
68 |
74 |
72 |
40 |
24 |
30 |
34 |
| |||||||||
|
Turntable Creek |
16 |
40.8 |
1067 |
120.9 |
105 |
69 |
101 |
68 |
99 |
68 |
95 |
66 |
72 |
70 |
28 |
24 |
29 |
32 |
| |||||||||
|
Tustin Foothills |
8 |
33.8 |
500 |
117.8 |
99 |
71 |
92 |
69 |
90 |
69 |
85 |
68 |
73 |
71 |
27 |
28 |
31 |
34 |
550 | |||||||||
|
Tustin Irvine Rch |
8 |
33.7 |
118 |
117.8 |
99 |
71 |
92 |
69 |
90 |
69 |
85 |
68 |
73 |
71 |
27 |
28 |
31 |
34 |
1856 | |||||||||
|
Twentynine Palms |
14 |
34.1 |
1975 |
116.1 |
110 |
71 |
107 |
70 |
106 |
70 |
103 |
69 |
76 |
74 |
31 |
21 |
26 |
29 |
1973 | |||||||||
|
Twin Lakes |
16 |
38.7 |
7829 |
119.1 |
73 |
49 |
64 |
47 |
62 |
47 |
57 |
46 |
53 |
50 |
30 |
-7 |
-2 |
4 |
9196 | |||||||||
|
Twitchell Dam |
5 |
35 |
582 |
120.3 |
99 |
70 |
93 |
68 |
92 |
68 |
88 |
66 |
71 |
69 |
26 |
26 |
31 |
34 |
| |||||||||
|
UCLA |
9 |
34.1 |
430 |
118.4 |
93 |
69 |
86 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
20 |
39 |
43 |
46 |
1509 | |||||||||
|
Ukiah |
2 |
39.2 |
623 |
123.2 |
100 |
70 |
97 |
69 |
96 |
69 |
92 |
68 |
72 |
71 |
42 |
22 |
28 |
31 |
2958 | |||||||||
|
Union City |
3 |
37.6 |
5 |
122.1 |
90 |
67 |
87 |
66 |
85 |
65 |
81 |
63 |
69 |
67 |
20 |
25 |
30 |
33 |
| |||||||||
|
Upland |
10 |
34.1 |
1605 |
117.7 |
102 |
69 |
98 |
68 |
96 |
68 |
92 |
66 |
73 |
71 |
31 |
29 |
34 |
36 |
2175 | |||||||||
|
Upper Lake RS |
2 |
39.2 |
1347 |
123 |
98 |
68 |
95 |
67 |
94 |
66 |
91 |
64 |
73 |
71 |
39 |
18 |
34 |
36 |
| |||||||||
|
Upper San Leandro |
3 |
37.8 |
394 |
122.1 |
93 |
67 |
87 |
66 |
85 |
65 |
80 |
63 |
69 |
67 |
22 |
28 |
33 |
35 |
| |||||||||
|
Vacaville |
12 |
38.4 |
105 |
122 |
103 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
40 |
23 |
28 |
31 |
2788 | |||||||||
|
Valinda |
9 |
34 |
340 |
117.9 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
68 |
74 |
72 |
28 |
31 |
36 |
38 |
| |||||||||
|
Valle Vista |
10 |
33.8 |
1655 |
116.9 |
109 |
70 |
104 |
69 |
103 |
69 |
101 |
67 |
74 |
72 |
40 |
20 |
25 |
28 |
| |||||||||
|
Vallejo |
3 |
38.1 |
85 |
122.3 |
93 |
67 |
90 |
66 |
88 |
66 |
84 |
64 |
70 |
68 |
23 |
28 |
33 |
36 |
| |||||||||
|
Valyermo RS |
14 |
34.5 |
3600 |
117.9 |
100 |
67 |
96 |
66 |
95 |
66 |
91 |
65 |
70 |
68 |
41 |
12 |
19 |
24 |
3870 | |||||||||
|
Van Nuys |
9 |
34.2 |
708 |
118.5 |
103 |
71 |
98 |
69 |
96 |
69 |
92 |
67 |
74 |
71 |
30 |
28 |
33 |
39 |
664 | |||||||||
|
Vandenburg AFB |
5 |
34.7 |
368 |
122.8 |
85 |
62 |
77 |
61 |
75 |
61 |
71 |
60 |
64 |
62 |
16 |
30 |
35 |
37 |
3451 | |||||||||
|
Ventura |
6 |
34.3 |
341 |
119.3 |
89 |
68 |
82 |
67 |
80 |
67 |
76 |
66 |
70 |
68 |
15 |
29 |
34 |
36 |
| |||||||||
|
Victorville Pumps |
14 |
34.5 |
2858 |
117.3 |
105 |
67 |
101 |
65 |
100 |
64 |
97 |
62 |
70 |
68 |
39 |
14 |
24 |
27 |
3191 | |||||||||
|
View Park |
6, 8 |
34 |
300 |
118.3 |
95 |
69 |
88 |
68 |
85 |
68 |
78 |
66 |
71 |
69 |
18 |
36 |
40 |
43 |
| |||||||||
|
Villa Park |
8 |
33.8 |
300 |
117.8 |
99 |
70 |
92 |
68 |
90 |
68 |
85 |
67 |
72 |
70 |
27 |
33 |
37 |
40 |
550 | |||||||||
|
Vincent |
9 |
34.5 |
3135 |
118.1 |
105 |
67 |
101 |
65 |
100 |
65 |
96 |
64 |
71 |
69 |
33 |
10 |
18 |
22 |
1455 | |||||||||
|
Visalia |
13 |
36.3 |
325 |
119.3 |
103 |
71 |
100 |
70 |
99 |
70 |
96 |
69 |
73 |
72 |
38 |
25 |
30 |
33 |
2459 | |||||||||
|
Vista |
10 |
33.2 |
510 |
117.2 |
96 |
69 |
90 |
68 |
89 |
68 |
85 |
67 |
72 |
70 |
16 |
30 |
35 |
37 |
| |||||||||
|
Volta PH |
12 |
40.5 |
2220 |
120.9 |
101 |
66 |
98 |
65 |
97 |
65 |
93 |
63 |
69 |
67 |
33 |
21 |
27 |
30 |
| |||||||||
|
Walnut |
9 |
34 |
550 |
117.9 |
101 |
70 |
97 |
69 |
96 |
69 |
92 |
69 |
74 |
72 |
30 |
28 |
33 |
35 |
| |||||||||
|
Walnut Creek |
12 |
37.9 |
245 |
122.1 |
100 |
69 |
94 |
67 |
92 |
67 |
87 |
66 |
71 |
69 |
32 |
23 |
29 |
31 |
| |||||||||
|
Walnut Grove |
12 |
38.2 |
23 |
121.5 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
68 |
72 |
71 |
37 |
24 |
30 |
32 |
| |||||||||
|
Walnut Park |
8 |
33.9 |
45 |
118.2 |
92 |
69 |
84 |
68 |
82 |
68 |
78 |
66 |
71 |
69 |
12 |
37 |
42 |
44 |
450 | |||||||||
|
Warner Springs |
14 |
33.3 |
3180 |
116.6 |
100 |
67 |
95 |
66 |
94 |
66 |
91 |
65 |
71 |
69 |
40 |
15 |
22 |
26 |
3591 | |||||||||
|
Wasco |
13 |
35.6 |
333 |
119.3 |
105 |
71 |
101 |
70 |
100 |
70 |
97 |
68 |
74 |
72 |
36 |
23 |
28 |
31 |
2466 | |||||||||
|
Watsonville |
3 |
36.9 |
95 |
121.8 |
86 |
66 |
82 |
64 |
81 |
63 |
79 |
61 |
68 |
65 |
22 |
28 |
33 |
35 |
3418 | |||||||||
|
Weaverville RS |
16 |
40.7 |
2050 |
122.9 |
100 |
67 |
95 |
66 |
93 |
65 |
89 |
63 |
69 |
67 |
46 |
10 |
17 |
22 |
4992 | |||||||||
|
Weed FD |
16 |
41.4 |
3590 |
122.4 |
92 |
63 |
89 |
62 |
88 |
61 |
84 |
59 |
65 |
63 |
35 |
4 |
12 |
17 |
| |||||||||
|
West Athens |
8 |
33.9 |
25 |
118.3 |
92 |
69 |
85 |
68 |
84 |
68 |
80 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
450 | |||||||||
|
West Carson |
6 |
33.8 |
100 |
118.3 |
92 |
69 |
87 |
68 |
85 |
68 |
81 |
66 |
71 |
69 |
18 |
32 |
37 |
39 |
| |||||||||
|
West Compton |
8 |
33.9 |
71 |
118.3 |
97 |
69 |
90 |
68 |
88 |
68 |
83 |
67 |
72 |
70 |
21 |
33 |
37 |
39 |
450 | |||||||||
|
West Covina |
9 |
34 |
365 |
117.9 |
102 |
70 |
98 |
69 |
96 |
69 |
92 |
68 |
74 |
72 |
34 |
29 |
34 |
36 |
| |||||||||
|
West Hollywood |
9 |
34 |
290 |
118.4 |
95 |
70 |
89 |
69 |
87 |
69 |
82 |
67 |
72 |
70 |
20 |
38 |
42 |
45 |
| |||||||||
|
West Pittsburg |
12 |
38 |
12 |
121.9 |
102 |
70 |
97 |
68 |
95 |
68 |
90 |
67 |
72 |
70 |
34 |
26 |
32 |
35 |
| |||||||||
|
West Puente Valley |
9 |
34 |
500 |
117.9 |
101 |
71 |
97 |
70 |
95 |
70 |
91 |
68 |
73 |
71 |
26 |
31 |
36 |
39 |
| |||||||||
|
West Sacramento |
12 |
38.6 |
19 |
121.5 |
104 |
72 |
100 |
70 |
98 |
70 |
94 |
68 |
74 |
71 |
35 |
26 |
31 |
33 |
1290 | |||||||||
|
West Whittier-Los Nietos |
9 |
34 |
320 |
118.1 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
35 |
38 |
| |||||||||
|
Westlake Village |
9 |
34.2 |
750 |
118.8 |
103 |
71 |
99 |
70 |
98 |
70 |
94 |
69 |
73 |
71 |
26 |
26 |
30 |
33 |
| |||||||||
|
Westminster |
6 |
33.8 |
38 |
118 |
95 |
70 |
88 |
68 |
86 |
68 |
81 |
67 |
72 |
70 |
23 |
33 |
38 |
41 |
| |||||||||
|
Westmont |
8 |
33.9 |
110 |
118.3 |
96 |
70 |
89 |
69 |
87 |
69 |
83 |
67 |
72 |
70 |
20 |
36 |
41 |
44 |
400 | |||||||||
|
Whiskeytown Res |
11 |
40.6 |
1295 |
122.6 |
105 |
69 |
101 |
68 |
100 |
68 |
96 |
67 |
72 |
70 |
31 |
25 |
30 |
33 |
| |||||||||
|
White Mtn 1 |
16 |
37.5 |
10150 |
119.3 |
73 |
49 |
69 |
47 |
68 |
47 |
65 |
45 |
53 |
50 |
37 |
-15 |
-9 |
-6 |
| |||||||||
|
White Mtn 2 |
16 |
37.6 |
12470 |
119.3 |
61 |
42 |
58 |
41 |
57 |
41 |
54 |
40 |
46 |
43 |
38 |
-20 |
-15 |
-12 |
| |||||||||
|
Whittier |
9 |
34 |
320 |
118 |
99 |
69 |
90 |
68 |
88 |
68 |
84 |
67 |
72 |
70 |
24 |
31 |
35 |
38 |
| |||||||||
|
Wildomar |
10 |
33.6 |
1255 |
117.3 |
103 |
70 |
99 |
69 |
98 |
69 |
94 |
68 |
74 |
72 |
36 |
23 |
28 |
30 |
827 | |||||||||
|
Wildrose RS |
16 |
36.3 |
4100 |
|
100 |
64 |
97 |
63 |
96 |
63 |
93 |
61 |
68 |
66 |
33 |
13 |
20 |
24 |
| |||||||||
|
Williams |
11 |
39.2 |
85 |
122.2 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
36 |
24 |
29 |
32 |
| |||||||||
|
Willits |
2 |
39.4 |
1350 |
123.3 |
95 |
66 |
89 |
65 |
87 |
64 |
82 |
62 |
68 |
66 |
38 |
18 |
24 |
27 |
| |||||||||
|
Willow Brook |
8 |
33.9 |
60 |
118.2 |
97 |
70 |
90 |
69 |
88 |
69 |
83 |
67 |
72 |
70 |
21 |
35 |
39 |
42 |
| |||||||||
|
Willow Creek |
2 |
41 |
461 |
123 |
104 |
70 |
98 |
68 |
96 |
68 |
92 |
66 |
71 |
69 |
35 |
22 |
28 |
31 |
| |||||||||
|
Willows |
11 |
39.5 |
140 |
122.2 |
104 |
71 |
100 |
70 |
98 |
70 |
94 |
68 |
73 |
71 |
36 |
22 |
28 |
31 |
2836 | |||||||||
|
Windsor |
2 |
38.5 |
130 |
122.8 |
99 |
69 |
96 |
68 |
95 |
68 |
92 |
66 |
71 |
69 |
35 |
24 |
27 |
29 |
1249 | |||||||||
|
Winters |
12 |
38.5 |
135 |
122 |
104 |
71 |
99 |
70 |
97 |
70 |
93 |
68 |
73 |
71 |
38 |
24 |
29 |
32 |
2593 | |||||||||
|
Winton |
12 |
37.4 |
168 |
120.6 |
103 |
71 |
100 |
69 |
99 |
69 |
95 |
67 |
73 |
71 |
36 |
21 |
27 |
30 |
1244 | |||||||||
|
Woodcrest |
10 |
33.9 |
1500 |
117.4 |
104 |
70 |
100 |
69 |
99 |
68 |
95 |
65 |
74 |
72 |
37 |
27 |
32 |
35 |
611 | |||||||||
|
Woodfords |
16 |
38.8 |
5671 |
119.8 |
92 |
59 |
89 |
58 |
88 |
58 |
84 |
56 |
63 |
61 |
32 |
0 |
5 |
12 |
6047 | |||||||||
|
Woodlake |
13 |
36.3 |
500 |
119.1 |
103 |
71 |
100 |
70 |
99 |
70 |
96 |
69 |
73 |
72 |
38 |
25 |
30 |
33 |
1130 | |||||||||
|
Woodland |
12 |
38.7 |
69 |
121.8 |
106 |
72 |
101 |
71 |
100 |
71 |
96 |
69 |
74 |
72 |
40 |
25 |
30 |
33 |
2708 | |||||||||
|
Woodland Hills |
9 |
34.2 |
944 |
118.6 |
104 |
71 |
99 |
70 |
97 |
70 |
93 |
68 |
74 |
72 |
32 |
26 |
31 |
34 |
664 | |||||||||
|
Woodside |
3 |
37.5 |
75 |
122.3 |
92 |
67 |
84 |
66 |
82 |
65 |
76 |
63 |
69 |
67 |
24 |
22 |
28 |
31 |
| |||||||||
|
Yorba Linda |
8 |
33.9 |
350 |
117.8 |
102 |
70 |
94 |
69 |
92 |
69 |
88 |
68 |
73 |
71 |
31 |
30 |
35 |
37 |
1643 | |||||||||
|
Yosemite Park Hq |
16 |
37.7 |
3970 |
119.6 |
97 |
63 |
94 |
62 |
93 |
62 |
90 |
60 |
67 |
65 |
38 |
11 |
18 |
23 |
4785 | |||||||||
|
Yreka |
16 |
41.7 |
2625 |
122.6 |
99 |
66 |
95 |
65 |
94 |
65 |
90 |
64 |
69 |
67 |
39 |
8 |
15 |
20 |
5395 | |||||||||
|
Yuba City |
11 |
39.1 |
70 |
121.6 |
105 |
69 |
101 |
69 |
100 |
69 |
96 |
68 |
72 |
71 |
36 |
24 |
29 |
32 |
| |||||||||
|
Yucaipa |
10 |
34 |
2600 |
117 |
106 |
68 |
102 |
67 |
101 |
67 |
98 |
65 |
73 |
71 |
35 |
27 |
32 |
35 |
| |||||||||
|
Yucca Valley |
14 |
34.2 |
2600 |
116.4 |
108 |
71 |
105 |
70 |
104 |
70 |
101 |
69 |
75 |
73 |
32 |
19 |
24 |
27 |
862 | |||||||||