1.15 HVAC Equipment Models

Air conditioning systems shall be sized, installed, tested and modeled according to the provisions of this section.

1.15.1  Compression Air-Conditioner Model

The Compliance Software calculates the hourly cooling electricity consumption in kWh using Equation 219. In this equation, the energy for the air handler fan and the electric compressor or parasitic power for the outdoor unit of a gas absorption air conditioner are combined. The Compliance Software calculates the hourly cooling gas consumption in therms using Equation 219

Equation 219

Where:

ACkWh             =   Air conditioner kWh of electricity consumption for a particular hour of the simulation. This value is calculated for each hour, combined with the TDV multipliers, and summed for the year.

FanWh              =   Indoor fan electrical energy for a particular hour of the simulation, Wh.

CompWh         =   Electrical energy for all components except the indoor fan for a particular hour of the simulation, Wh.  This value includes consumption for the compressor plus outdoor condenser fan and  is calculated using Equation 221.

CSE calculates the energy for electrically driven cooling using the algorithms described in this section.

Primary model parameters. The following values characterize the AC unit and are constant for a given unit:

Cap95          =   AHRI rated total cooling capacity at 95 °F, Btuh

CFMper ton     =   Air flow rate per ton of cooling capacity, cfm/ton.

EFan            =   Fan operating electrical power, W/cfm.  Default = 0.365.

SEER          =   AHRI rated Seasonal Energy Efficiency Ratio, Btuh/W. EER shall be used in lieu of the SEER for equipment not required to be tested for a SEER rating.

EER             =   AHRI rated energy efficiency ratio at 95 °F, Btuh/W. If EER is not available, it is derived from SEER as follows:

If SEER

>=16

>=13 & <16

<13

EER

13

11.3 + 0.57 x (SEER-13)

10+0.84×(SEER– 11.5)

Fchg                  Refrigerant charge factor, default = 0.9. For systems with a verified charge indicator light (Reference Residential Appendix RA3.4) or verified refrigerant charge (Reference Residential Appendix RA3), the factor shall be 0.96.

Fsize             =   Compressor sizing factor, default = 0.95.  For systems sized according to the Maximum Cooling Capacity for compliance software Credit (see Section <TODO>), the factor shall be 1.0.

Derived model parameters. The following values are used in the formulas below and depend only on model parameters.

Tons            =   Nominal cooling capacity defined as Cap95 / 12000

QFanrat           =   Assumed fan heat included at AHRI test conditions, Btuh

Fan motor type

QFanrat

PSC

500 x Cap95 / 12000

BPM

283 x Cap95 / 12000

QFanop         =   Fan heat assumed during operation (i.e., during simulation), Btuh

Equation 220

Model inputs. The following values vary at each time step in the simulation and are used in the formulas below to determine AC unit performance under for that time step.

DBt              =   Dry bulb temperature of air at the condensing unit, °F (typically outdoor air temperature).

WBec            =   Coil entering air wet bulb temperature, °F (return air temperature adjusted for blow-through fan heat if any)

DBec                =  Coil entering air dry bulb temperature, °F (return air temperature adjusted for blow through fan heat if any)

Qneed          =   Cooling system sensible cooling output, Btuh.  Qneed is calculated across the unit and thus includes both the building load and distribution losses.

Compressor energy for a particular time step of the simulation shall be calculated using Equation 221.

Equation 221

Where:

Fanwh           =   Fan power for this time step, Wh.

CEt              =   Sensible energy efficiency at current conditions, Btuh/W.  This is calculated using Equation 222 below.

Equation 222

Where:

EERt            =   Energy efficiency ratio at current conditions, Btuh/W. EERt is calculated using Equation 226 below.

SHR             =   Sensible Heat Ratio (sensible capacity / total capacity), derived as follows:

SHR = minimum(1,        ASHR × DBec +

BSHR × WBec +

CSHR × DBt +

DSHR × CFMper ton +

ESHR × DBec × DBt +

FSHR × DBec × CFMper ton +

GSHR × WBec × DBt +

HSHR × WBec × CFMper ton +

ISHR × DBt × CFMper ton +

JSHR × WBec2 +

KSHR / CFMper ton +

LSHR)  

SHR coefficients:

ASHR

0.0242020

BSHR

-0.0592153

CSHR

0.0012651

DSHR

0.0016375

ESHR

0

FSHR

0

GSHR

0

HSHR

-0.0000165

ISHR

0

JSHR

0.0002021

KSHR

0

LSHR

1.5085285

 

CAPnf = Total cooling capacity across coil (that is, without fan heat) at current conditions, Btuh

Equation 223

Fcond_cap =           ACAP × DBec +

BCAP × WBec +

CCAP × DBt +

DCAP × CFMper ton +

ECAP × DBec × DBt +

FCAP × DBec × CFMper ton +

GCAP × WBec × DBt +

HCAP × WBec × CFMper ton +

ICAP × DBt × CFMper ton +

JCAP × WBec2 +

KCAP / CFMper ton +

LCAP  

 

Coefficients as follows:

SHR Condition

SHR < 1

SHR = 1

ACAP

0

0.009483100

BCAP

0.009645900

0

CCAP

0.002536900

-0.000600600

DCAP

0.000171500

-0.000148900

ECAP

0

-0.000032600

FCAP

0

0.000011900

GCAP

-0.000095900

0

HCAP

0.000008180

0

ICAP

-0.000007550

-0.000005050

JCAP

0.000105700

0

KCAP

-53.542300000

-52.561740000

LCAP

0.381567150

0.430751600

 

CAPsen         =   Sensible capacity including fan heat, Btuh

Equation 224

CAPlat          =   Latent capacity, Btuh

Equation 225

Note: The air leaving the AC unit is limited to 95% relative humidity.  If that limit is invoked, CAPlat is reduced and CAPsen is increase.

EERt is calculated as follows:

Equation 226

When

 

DBt ≤ 82 ºF

EERt = SEERnf

82 < DBt < 95 °F

EERt = SEERnf + ((DBt - 82)*(EERnf – SEERnf) / 13)

DBt ≥ 95 °F

EERt = EERnf

Where:

SEERnf           =   Seasonal energy efficiency ratio at current conditions without distribution fan consumption (“nf” = no fans). This is calculated using Equation 227.

EERnf           =   Energy efficiency ratio at current conditions without distribution fan consumption (“nf” = no fans) and adjusted for refrigerant charge and airflow. This is calculated using Equation 228.

Equation 227

Fcond_SEER = Fcond_cap /     (ASEER × DBec +

BSEER × WBec +

CSEER × DBt +

DSEER × CFMper ton +

ESEER × DBec × DBt +

FSEER × DBec × CFMper ton +

GSEER × WBec × DBt +

HSEER × WBec × CFMper ton +

ISEER × DBt × CFMper ton +

JSEER × WBec2 +

KSEER / CFMper ton +

LSEER)  

Coefficients as follows:

SHR Condition

SHR < 1

SHR = 1

ASEER

0

0.0046103

BSEER

-0.0202256

0

CSEER

0.0236703

0.0125598

DSEER

-0.0006638

-0.000512

ESEER

0

-0.0000357

FSEER

0

0.0000105

GSEER

-0.0001841

0

HSEER

0.0000214

0

ISEER

-0.00000812

0

JSEER

0.0002971

0

KSEER

-27.95672

0

LSEER

0.209951063

-0.316172311

 

Equation 228

Where:

Fcond_EER = (AEER × DBec +

BEER × WBec +

CEER × DBt +

DEER × CFMper ton +

EEER × DBec × DBt +

FEER × DBec × CFMper ton +

GEER × WBec × DBt +

HEER × WBec × CFMper ton +

IEER × DBt × CFMper ton +

JEER × WBec2 +

KEER / CFMper ton +

LEER)

Coefficients as follows:

SHR Condition

SHR < 1

SHR = 1

AEER

0

0.004610300

BEER

-0.020225600

0

CEER

0.023670300

0.012559800

DEER

-0.000663800

-0.000512000

EEER

0

-0.000035700

FEER

0

0.000010500

GEER

-0.000184100

0

HEER

0.000021400

0

IEER

-0.000008120

0

JEER

0.000297100

0

KEER

-27.956720000

0

LEER

0.015003100

-0.475306500

 

 

1.15.2  Air-Source Heat Pump Model (Heating mode)

The air source heat pump model is based on methods presented in AHRI Standard 210/240-2008.

Primary model parameters. The following values characterize the ASHP and are constant for a given unit:

Cap47          =   Rated heating capacity at outdoor dry-bulb temperature = 47 °F

COP47         =   Coefficient of performance at outdoor dry bulb = 47 °F (if available, see below)

Cap35          =   Heating capacity under frosting conditions at outdoor dry-bulb temperature = 35 °F (if available, see below)

COP35         =   Coefficient of performance at outdoor dry bulb = 35 °F (if available, see below)

Cap17          =   Rated heating capacity at outdoor dry-bulb temperature = 17 °F

COP17         =   Coefficient of performance at outdoor dry bulb = 17 °F (if available, see below)

HSPF           =   Rated Heating Seasonal Performance Factor, Btuh/Wh

COPbu         =   COP of backup heating, default = 1 (electric resistance heat)

Capbu          =   Available backup heating capacity, Btuh

 

Derived model parameters.

Inp47           =   Electrical input power at 47 °F = Cap47 / COP47, Btuh (not W)

Inp17           =   Electrical input power at 17 °F = Cap17 / COP17, Btuh (not W)

 

Estimation of unavailable model parameters.

 

 

Simulation

Full-load capacity and input power of the ASHP is determined each time step as a function of outdoor dry-bulb temperature T, as follows --

If (17 °F < T < 45 °F)

Else

 

Resistance heat.

Load in excess of Cap(T) is met with backup heating at COPbu.

 

1.15.3  Equipment Sizing

CSE determines the capacity of HVAC equipment via an auto-sizing capability.  Autosizing is conducted prior to the main annual simulation.  It is done by using the hourly simulator for a set of design days and increasing capacity as needed to maintain thermostat set points.  Each design day is repeated several times until the required capacity converges.  The set of design days includes one cold day with no solar gain and several hot days at with clear-sky solar at different times of the year.  This ensures that maximums of both heating and cooling loads will be found.  Equipment characteristics other than capacity are specified on a per-unit basis (e.g. “cfm per ton”), so a full description of the system can be derived from the primary capacity.

The sizing procedure uses the equipment models in an inverse mode.  For example, the sensible cooling load for a given set up conditions is back-converted to the required rated total capacity (Cap95) by using inverted forms of the model equations.  The general simulation calculation sequence is used, but the logic of the HVAC models is altered during the autosizing phase.

Note that for air-source heat pumps, only the backup heating capacity is autosized.  In addition, modeled duct sizes are not sized and must be specified.

The equipment sizes calculated by CSE are used for compliance analysis only and are not substitutes for load calculations used for selecting equipment or meeting other code requirements.