Luminaires shall be labelled with its wattage as follows.
1. The maximum rated wattage or relamping rated wattage of a luminaire shall be listed on a permanent, preprinted, factory-installed label, as specified by UL 1574, 1598, 2108, or 8750, as applicable; and
2. Peel-off and peel-down labels that allow the maximum labeled wattage to be changed are prohibited, except for luminaires meeting all of the following requirements:
a. The luminaires can accommodate a range of lamp wattages without changing the luminaire housing, ballast, transformer or wiring.
b. They have a single lamp.
c. They have an integrated ballast or transformer.
d. Peel-down labels are layered such that the rated wattage reduces as successive layers are removed.
e. Qualifies as one of the following three types of luminaires:
i. High intensity discharge luminaires having an integral electronic ballast with a maximum relamping rated wattage of 150 watts.
ii. Low-voltage luminaires (does not apply to low voltage track systems) ≤ 24 volts with a maximum relamping rated wattage of 50 watts.
Compact fluorescent luminaires having an integral electronic ballast with a maximum relamping rated wattage of 42 watts.