C1 System Loss Assumptions

In PVWatts, a single derating factor is used to cover a variety of system inefficiencies. The compliance software uses slightly different assumptions for this derating factor as described in the table below:

 

Loss Type

Value

Differences from PVWatts
default assumption

Soiling

0.02

 

Shading

 

0.0

Modeled explicitly

Snow

0.0

 

Mismatch

0.0

Mismatch from shading is characterized using SIF

Wiring

0.02

 

Connections

0.005

 

Light-induced degradation

0.015

 

Nameplate rating

0.01

 

Age

0.05

Estimated 0.5% degradation over 20 years based on these references: [1, 2, 3]

Availability

0.03

 

Total

0.14