5.6   HVAC Zone Level Systems    

This group of building descriptors relate to HVAC systems at the zone level. There is not a one-to-one relationship between HVAC components in the proposed design and the Standard Design since the Standard Design system is determined from building type, size, and heating source. The applicability of each building descriptor for each of the 11 Standard Design systems is indicated in tables under the building descriptor Standard Design rules. Additions and Alterations should follow the same requirements stated for new construction Proposed Designs and new construction Standard Designs; unless otherwise noted in the descriptor.

5.6.1 Space Temperature Control

Space Thermostat Throttling Range

Applicability

All thermal zones

Definition

The number of degrees that the room temperature must change to cause the HVAC system to go from no heating or cooling (i.e., space temperatures floating) to full heating or cooling.

Units

Degrees Fahrenheit (°F)

Input Restrictions

The prescribed value is 2°F. (This is equivalent to a +/- 1F temperature tolerance around the heating and cooling setpoint.) No input is needed and the prescribed value may not be overridden.

Standard Design

Same as the proposed design

Space Temperature Schedule

Applicability

All thermal zones

Definition

An hourly space thermostat schedule

Units

Data structure: temperature schedule

Input Restrictions

Prescribed. The Schedule Group is specified for the given Space Type in Appendix 5.4A, and the schedule values are specified in Appendix 5.4B.

Standard Design

Schedules in the Standard Design shall be identical to the proposed design.

5.6.2 Terminal Device Data

Terminal Type

Applicability

All thermal zones

Definition

A terminal unit includes any device serving a zone (or group of zones collected in a thermal zone) that has the ability to reheat or recool in response to the zone thermostat. This includes:

      None (the case for single zone units)

      VAV box

      Series Fan-Powered VAV box

      Parallel Fan-Powered VAV box

      Induction-type VAV box

      Dual-duct mixing box (constant volume and VAV)

      Two and three duct mixing dampers (multi-zone systems)

      Reheat coil (constant volume systems)

      Perimeter induction units

Units

List (see above)

Input Restrictions

As designed

Standard Design

Table 14 specifies the HVAC terminal device for each of the Standard Design systems. See Section 5.1.2 for a summary of the HVAC mapping.

Table 14 – Standard Design HVAC Terminal Devices

Standard Design System

Terminal Type

System 1 – PTAC

None

System 2 – FPFC

None

System 3 – PSZ-AC

None

System 5 – Packaged VAV with Reheat

VAV Box

System 6 – VAV with Reheat

VAV Box

System 7 – SZVAV

None

System 9 – Heating and Ventilation

None

System 10 – CRAH

None

System 11 – CRAC

None

System 12 – LAB

None

System 13 – Kitchen

None

5.6.3 Terminal Heating    

This group of building descriptors applies to proposed design systems that have reheat coils at the zone level. The building descriptors are applicable for Standard Design systems 5 and 6.

Terminal Heat Type

Applicability

Systems that have reheat coils at the zone level

Definition

The heating source for the terminal unit. This includes:

      Electric resistance

      Gas furnace

      Oil furnace

      Hot water

      Steam

Units

List (see above)

Input Restrictions

As designed.

Standard Design

Table 15 shows the terminal heat type for each Standard Design system.

Table 15 – Baseline Building Terminal Heat Type

Baseline building System

Terminal Heat Type

System 1 – PTAC

None

System 2 – PTHP

None

System 3 – PSZ-AC

None

System 4 – PSZ-HP

None

System 5 – Packaged VAV with Reheat

Hot Water

System 6– VAV with Reheat

Hot Water

System 7 – SZVAV

None

System 8 – SZVAV HP

None

System 9 – Heating and Ventilation

None

System 10 – CRAH Unit

None

System 11 – CRAC Unit

None

System 12 – LAB

None

System 13 – Kitchen

None

 

Terminal Heat Capacity

Applicability

Systems that have reheat coils at the zone level

Definition

The heating capacity of the terminal heating source

Units

Btu/h

Input Restrictions

As designed. However, if the unmet load hours exceed 150, the energy analyst and design team may have to increase the size of the equipment so that the unmet load hours are less than 150. See Figure 10.

Standard Design

The software shall automatically size the terminal heating capacity to be 25% greater than the design loads. See Figure 2.

Reheat Delta T

Applicability

Systems that have reheat coils at the zone level

Definition

This is an alternate method to enter the terminal heat capacity. It can be calculated as follows:

(3) Treheat = Treheat - Tcool_supply
Treheat = Qcoil / (1.1*CFM)

 

where

∆Treheat                     heat rise across the terminal unit heating coil (°F)

Treheat heating air temperature at design (°F)

Tcool_supply        supply air temperature at the heating coil (°F)

Qcoil  heating coil load (Btu/h)

CFM airflow (cfm)

Units

Degrees Fahrenheit (°F)

Input Restrictions

As designed, but may need to be increased if zone unmet load hours are greater than 150.

Standard Design

Method not used for standard design. (The temperature difference shall be no more than 40F.) See Heat Capacity above.

5.6.4 Baseboard Heat

Baseboard Capacity

Applicability

All thermal zones

Definition

The total heating capacity of the baseboard unit(s)

Units

Btu/h

Input Restrictions

As designed

Standard Design

Not applicable to the standard design

Baseboard Heat Control

Applicability

All thermal zones

Definition

Defines the control scheme of base board heating as either:

      Controlled by a space thermostat

Units

List (see above)

Input Restrictions

Controlled by space thermostat is the only type allowed if baseboard heating is used.

Standard Design

Not applicable for the standard design

5.6.5 Zone Level Air Flow    

5.6.5.1 VAV Air Flow

This group of building descriptors applies to proposed design systems that vary the volume of air at the zone level. The building descriptors are applicable for standard design systems 5 and 6.

Design Airflow

Applicability

Systems that vary the volume of air at the zone level

Definition

The air delivery rate at design conditions

Units

cfm

Input Restrictions

As designed.

If the unmet load hours in the proposed design are greater than 150, the compliance simulation should not proceed and the user may have to modify the Design Airflow value manually.

Standard Design

For systems 5 and 6, the software shall automatically size the system airflow to meet both: (a) the standard design peak cooling load based on a supply-air-to-room-air temperature difference of 20°F for exterior zones or 15°F for interior zones, the required ventilation air from Table 120.1-A of the Standard, or makeup air; whichever is greater and (b) the standard design peak heating load based on 50% zone flow and 95F supply air temperature.

An exterior zone is defined as a type of thermal zone that has any exterior walls, and that has a non-zero amount of vertical fenestration (windows).  Any zone that does not meet the definition of an exterior zone is an interior zone.

For kitchen MAU systems, the design airflow is the greater of the airflow required to meet the design cooling loads and the total exhaust CFM.

Terminal Minimum Stop

Applicability

Systems that vary the volume of air at the zone level

Definition

The minimum airflow that will be delivered by a terminal unit before reheating occurs

Units

Unitless fraction of airflow (cfm) or specific airflow (cfm/ft²)

Input Restrictions

This input must be greater than or equal to the outside air ventilation rate.

Standard Design

For systems 5 and 6 set the minimum airflow to be the greater of 20% of the peak supply air volume to the zone or the minimum outside air ventilation rate.

For laboratories, the minimum airflow fraction shall be fixed at a value equivalent to 6 ACH.

Terminal Heating Control Type

Applicability

VAV boxes with reheat

Definition

The control strategy for the heating mode.

Single Maximum

In the single maximum control mode, the airflow is set to a minimum constant value in both the deadband and heating mode. This airflow can vary but is typically 30 to 50 percent of maximum. This control mode typically has a higher minimum airflow than the minimum used in the dual maximum below, resulting in more frequent reheat.

 

Single Maximum VAV Box Control

Courtesy: Taylor Engineering

Dual Maximum: raises the SAT as the first stage of heating, and increases the airflow to the zone as the second stage of heating. 

1. The first stage of heating consists of modulating the zone supply air temperature setpoint up to a maximum setpoint no larger than 95ºF while the airflow is maintained at the dead band flow rate.

2. The second stage of heating consists of modulating the airflow rate from the dead band flow rate up to the heating maximum flow rate (50% of design flow rate).

Figure 9 – Dual Maximum Control Sequence

 

Units

List:

Single Maximum

Dual Maximum

Input Restrictions

Fixed at Single Maximum if Control System Type is not DDC Control to the Zone Level

Standard Design

Dual Maximum

 

5.6.5.2 Fan Powered Boxes

Fan Powered Box Type

Applicability

thermal zones that have fan powered boxes

Definition

Defines the type of fan-powered induction box. This is either:

      Series; or

      Parallel

Units

List (see above)

Input Restrictions

As designed

Standard Design

Not applicable

Fan Power

Applicability

thermal zones that have fan powered boxes

Definition

The rated power input of the fan in a fan-powered box.

Units

W or W/cfm

Input Restrictions

As designed

Standard Design

Not applicable

Fan Powered Box Induced Air Zone

Applicability

thermal zones that have fan powered boxes

Definition

Zone from which a series or parallel fan-powered box draws its air

Units

List (of zones)

Input Restrictions

As designed

Standard Design

Not applicable

Parallel PIU Induction Ratio

Applicability

thermal zones that have fan powered boxes

Definition

The ratio of induction-side airflow of a fan-powered box at design heating conditions to the primary airflow

Units

Ratio

Input Restrictions

As designed

Standard Design

Not applicable

Parallel Fan Box Thermostat Setpoint

Applicability

thermal zones that have parallel fan powered boxes

Definition

The temperature difference above the heating setpoint at which the parallel fan is turned on

Units

Degrees Fahrenheit (°F)

Input Restrictions

2°F above the heating setpoint schedule

Standard Design

Not applicable

 

5.6.5.3 Zone Exhaust    

This group of building descriptors describes the rate of exhaust and the schedule or control for this exhaust. An exhaust system can serve one thermal zone or multiple thermal zones. Energy is summed for the exhaust system level, not the thermal zone level.

This section also contains unique inputs for kitchen exhaust systems that must meet requirements of section 140.9 of the Standards.

Kitchen Exhaust Hood Length

Applicability

Exhaust fans in spaces of type Kitchen

Definition

The exhaust hood length

Units

ft

Input Restrictions

As designed

Standard Design

Same as the proposed design

Kitchen Exhaust Hood Style

Applicability

Exhaust fans in spaces of type Kitchen

Definition

The hood style as defined in Table 140.9-A of the Standards

Units

List:  Wall-mounted canopy, Single Island, Double Island, Eyebrow, Backshelf/Passover

Input Restrictions

As designed

Standard Design

Same as the proposed design

Kitchen Exhaust Hood Cooking Duty

Applicability

Exhaust fans in spaces of type Kitchen

Definition

The hood cooking duty as defined in Table140.9-A of the Standards

Units

List: Light Duty, Medium Duty, Heavy Duty, Extra Heavy Duty

Input Restrictions

As designed

Standard Design

Same as the proposed design

 

Exhaust Fan Name

Applicability

All thermal zones

Definition

A reference to an exhaust fan system that serves the thermal zone

Units

Text or other unique reference to an exhaust fan system defined in the secondary systems section.

Input Restrictions

As designed

Standard Design

Same as the proposed design

Laboratory Exhaust Rate Type

Applicability

All laboratory zones

Definition

The type of load that dictates lab exhaust rate requirements

Units

List, either:

Hood dominated

Load dominated

Input Restrictions

As designed

Standard Design

Same as the proposed design

Exhaust Air Flow Rate

Applicability

All thermal zones

Definition

Rate of exhaust from a thermal zone

Units

cfm

Input Restrictions

As designed for non-process zones

For laboratory zones, the exhaust air flow rate is prescribed:

15 ACH for hood dominated spaces, or

6 ACH for load dominated spaces

 

Standard Design

Same as the proposed design but not above the maximum standard design flow rates 'listed in Appendix 5.4A. Exception for kitchen space types with over 5,000 cfm of exhaust: the baseline is a function of the Kitchen Exhaust Hood Length, Kitchen Exhaust Hood Style and Kitchen Exhaust Hood Cooking Duty, and is determined by Table 140.9-A.

Exhaust Minimum Air Flow Rate

Applicability

All laboratory zones

Definition

Rate of exhaust from a zone

Units

cfm

Input Restrictions

As designed for non-process zones

For laboratory zones, the exhaust air flow rate is the maximum of the hood scheduled exhaust air flow rate and the minimum ventilation rate

Standard Design

For laboratory systems, the exhaust minimum air flow rate is the maximum of the hood scheduled exhaust flow rate and 6 ACH, the minimum ventilation rate

Exhaust Fan Schedule

Applicability

All thermal zones

Definition

Schedule indicating the pattern of use for exhaust air from the thermal zone. This input should consider the position of fume hood sash opening. For toilets and other exhaust applications, the schedule may coincide with the operation of the exhaust fan system.

Units

Data structure: schedule, fraction

Input Restrictions

As designed for non-covered process spaces

For laboratory spaces, if the hoods are constant volume the schedule shall be fixed at 0.90 for all hours of the year (24/7).

For laboratory spaces, if the hoods are variable volume the schedule shall be prescribed at the values in Appendix 5.4B.

 

Standard Design

Same as the proposed design for non-covered process spaces

Exhaust schedules for kitchen exhaust hoods for flow less than 5,000 cfm and for flow greater than 5,000 cfm are prescribed and specified in Appendix 5.4B.

Laboratory hood exhaust schedules for CAV and VAV hoods are prescribed and specified in Appendix 5.4B.

 

5.6.5.4 Outdoor Air Ventilation    

Ventilation Source

Applicability

All thermal zones

Definition

The source of ventilation for an HVAC system. The choices are:

      Natural (by operable openings)

      Forced (by fan)

Units

List: natural or forced

Input Restrictions

For residential units and hotel/motel guest rooms, as designed. (For software that cannot model outside air ventilation with residential systems that do not have a ducted air source, the ventilation source shall be none.) For all other occupancies, as designed.

Standard Design

For residential units, set to same as proposed, for all other occupancies, set equal to the same value for the proposed design.

Design Ventilation Rate

Applicability

All thermal zones

Definition

The quantity of ventilation air that is provided to the space for the specified thermal zone at maximum occupancy

Units

cfm or cfm/occupant

Input Restrictions

As designed, but not lower than code minimum (default value).

The default value shall be the larger of 15 cfm times the design occupancy from Appendix 5.4A or the conditioned floor area times the applicable ventilation rate from Appendix 5.4A or Table 120.1-A of the Standards.

Standard Design

The standard design outside air ventilation rate shall be the larger of 15 cfm times the design occupancy from Appendix 5.4A, or the conditioned floor area of the space times the applicable ventilation rate in Appendix 5.4A or Table 120.1-A of the Standards.

Minimum Ventilation Rate

Applicability

All thermal zones, excluding unconditioned spaces

Definition

The minimum quantity of ventilation air that must be provided to the space when it is occupied

Units

cfm or cfm/ft²

Input Restrictions

As designed, but not lower than code minimum (default value).  The default value shall be the larger of 15 cfm times the design occupancy from Appendix 5.4A or the conditioned floor area times the applicable ventilation rate from Appendix 5.4A or Table 120.1-A of the Standards.

For labs the minimum ventilation rate shall not be less than 6 ACH at all times.

For spaces where demand control ventilation is installed, the minimum ventilation rate is specified by the greater of the rate in Table 120.1-A or 15 cfm times the scheduled occupancy for that hour;

For spaces where Occupant sensor ventilation controls are installed, the minimum ventilation rate shall be 25% of the area-based values in Table 120.1-A (e.g. 0.0375 cfm/ft2 for office) during hours when the occupancy schedule is 10% or less.

Standard Design

For spaces where demand control ventilation is required, the minimum ventilation rate is specified by the greater of the rate in Table 120.1-A or 15 cfm times the scheduled occupancy for that hour;

For systems serving laboratories, the airflow minimum for each lab space shall be 6 ACH.

For systems serving kitchens, the minimum outside air ventilation rate is the exhaust air ventilation rate minus available transfer air (available transfer shall be calculated from the building minimum outside airflow less any exhaust airflows other than kitchen exhausts) and minus 0.05 cfm/ft2 for exfiltration.

For all other spaces, the minimum ventilation rate is the same as the design ventilation rate in the standard design.

 

Ventilation Control Method

Applicability

All thermal zones

Definition

The method used to determine outside air ventilation needed for each hour in the simulation. This information is reported to the system serving the zone. The method of controlling outside air at the system level in response to this information is discussed under secondary systems. Options at the zone level are:

      Occupant sensors: When the space is occupied according to the prescribed occupancy schedule, the outside air requirement is equal to the design ventilation rate; otherwise, the outside air requirement is either 25% of the minimum ventilation rate or scheduled off (0).

      CO2 sensors in the space: The outside air is varied to maintain a maximum CO2 concentration in the space. This shall be approximated by multiplying the ventilation rate per occupant times the number of occupants for that hour. (When turnstile counts are used to automatically adjust ventilation levels based on occupancy, this method may also be used.)

      Fixed ventilation rate. Outside air is delivered to the zone at a constant rate and is equal to the design ventilation rate (see above).

Units

List (see above)

Input Restrictions

As designed. If the space includes a design occupant density greater than 25 persons per 1,000 ft2, and the system includes an airside economizer, the input is restricted to CO2 sensors in the space (a mandatory requirement).

Standard Design

For the federal tax credit Title 24 compliance, if the default occupancy from Appendix 5.4B is greater than 10025 persons per 1,000 ft² , set control method to CO2 sensors in the space, otherwise set to fixed ventilation rate.