5.9   Miscellaneous Energy Uses

Miscellaneous energy uses are defined as those that may be treated separately since they have little or no interaction with the conditioned thermal zones or the HVAC systems that serve them.

5.9.1 Water Heating    

Water heating systems shall always be modeled for both the proposed design and baseline building when the proposed building is expected to have a water heating load, even if no water heating is shown on the plans or specifications for the proposed design. In such instances, an electric resistance system shall be modeled for both the proposed design and baseline building, meeting the efficiency requirements of the baseline standard.

When the construction documents show a water heating system, the layout and configuration of the baseline building system shall be the same as the proposed design, e.g. the baseline building shall have the same number of water heaters and the same distribution system.

5.9.1.1 System Loads and Configuration

Water Heating System Name

Applicability

All water heating systems

Definition

A unique descriptor for each water heating system. A system consists of one or more water heaters, a distribution system, an estimate of hot water use, and a schedule for that use. Nonresidential buildings will typically have multiple systems, perhaps a separate electric water heater for each office break room, etc. Other building types such as hotels and hospitals may have a single system serving the entire building.

Units

Text, unique

Input Restrictions

Where applicable, this should match the tags that are used on the plans such that a plan reviewer can make a connection.

Standard Design

The naming convention for the baseline building system shall be similar to the proposed design.

Water Heating Peak Use

Applicability

All water heating systems, required

Definition

An indication of the peak hot water usage (e.g. service to sinks, showers, and kitchen appliances, etc.). When specified per occupant, this value is multiplied by design occupancy density values and modified by service water heating schedules to obtain hourly load values which are used in the simulation.

Peak consumption is commonly specified as gallons per hour per occupant, dwelling unit, hotel room, patient room, or floor area. If consumption is specified in gallons per hour, then additional inputs would be needed such as supply temperature, cold water inlet temperature, etc.

Software that specifies peak use as a thermal load in Btu/h. can apply ACM rules for the mains (cold water inlet) temperature and supply temperature to convert the prescribed peak use from gph/person to Btu/h-person. The thermal load does not include conversion efficiencies of water heating equipment.

Units

gph/person

Input Restrictions

Prescribed values from Appendix 5.4A.

Standard Design

Prescribed values from Appendix 5.4A

Water Heating Schedule

Applicability

All water heating systems, required

Definition

A fractional schedule reflecting the time pattern of water heating use. This input modifies the water heating peak use, described above.

Units

Data structure: schedule, fractional

Input Restrictions

The schedules from Appendix 5.4A shall be used.

Standard Design

The schedules from Appendix 5.4A shall be used.

Water Heating System Configuration

Applicability

All water heating systems, required

Definition

The configuration and layout of the water heating system, including the number of water heaters; the size, location, length and insulation of distribution pipes; recirculation systems and pumps; and any other details about the system that would affect the energy model.

Units

Data structure

Input Restrictions

None

Standard Design

The baseline building shall have one gas storage water heater, except for high-rise residential buildings, which shall follow the Standard Design rules in Appendix E of the 2013 Residential ACM 'Manual.

Water Mains Temperature Schedule

Applicability

All water heating systems, required

Definition

A monthly temperature schedule indicating the water mains temperature. This temperature and the setpoint temperature is used to convert the load into a water flow rate.

Units

Data structure: schedule, deg F

Input Restrictions

The schedules from Appendix 5.4A shall be used. The water mains temperature schedule shall be fixed for a given climate zone.

Standard Design

The schedules from Appendix 5.4A shall be used.  The water mains temperature schedule shall be fixed for a given climate zone.

 

5.9.1.2 Water Heaters

This section describes the building descriptors for water heaters. Typically, a building will have multiple water heating systems and each system can have multiple water heaters, so these building descriptors may need to be specified more than once.

Water Heater Name

Applicability

All water heaters

Definition

A unique descriptor for each water heater in the system. Some systems will have multiple pieces of equipment, for instance a series of water heaters plumbed in parallel or a boiler with a separate storage tank.

Units

Text, unique

Input Restrictions

Where applicable, this should match the tags that are used on the plans such that a plan reviewer can make a connection.

Standard Design

The naming convention for the baseline building system shall be similar to the proposed design.

Water Heater Type and Size

Applicability

All water heaters

Definition

This building descriptor includes information needed to determine the criteria from baseline standards. The choices are 'listed below.

      Electric water heaters (storage and instantaneous)

o   Small (≤ 12 kW)

o   Large (> 12 kW)

o   Heat pump

      Gas storage water heaters

o   Small (≤ 75,000 Btu/h)

o   Large (> 75,000 Btu/h)

      Gas instantaneous water heaters

o   Small (> 50,000 and < 200,000 Btu/h)

o   Large (≥ 200,000 Btu/h), <10 gal

o   Large (≥ 200,000 Btu/h), >= 10 gal

      Oil storage water heaters

o   Small (≤ 105,000 Btu/h)

o   Large (> 105,000 Btu/h)

      Oil instantaneous water heaters

o   Small (≤ 210,000 Btu/h)

o   Large (> 210,000 Btu/h), <10 gal

o   Large (> 210,000 Btu/h), >= 10 gal

      Gas hot water supply boiler

      Oil hot water supply boiler

Units

List (see above)

Input Restrictions

As designed

Standard Design

Gas storage water heater

Rated Capacity

Applicability

All water heaters

Definition

The heating capacity of a water heater at the rated conditions specified in DOE 10 CFR

Part 430 or ANSI Z21.10.

Units

Thousands of British Thermal Units per hour (MBH)

Input Restrictions

As designed. If the loads are not met, autosize.

Standard Design

Autosize

Storage Volume

Applicability

Gas-fired water heaters

Definition

The storage volume of a gas-fired water heater. This is used in the Standby loss calculations and baseline calculations of Energy Factor.

Units

gallons

Input Restrictions

As designed. If the loads are not met, autosize.

Standard Design

Autosize

Energy Factor

Applicability

Equipment covered by NAECA, which includes small storage and instantaneous water heaters

Definition

The energy factor (EF) is the ratio of the energy delivered by the water heater divided by the energy used, in the same units. EF is calculated according to the DOE 10 CFR Part 430 test procedure, which specifies a 24-hour pattern of draws, a storage temperature, inlet water temperature, and other test conditions. These conditions result in the energy delivered for the test period. Energy inputs are measured for the same test period and the EF ratio is calculated.

Units

Unitless ratio

Input Restrictions

Building descriptors for the proposed design should be consistent with equipment specified on the construction documents or observed in the candidate building.

Standard Design

The EF for the baseline building system shall be determined from the CEC Appliance Efficiency Regulations. The following baseline EF applies for water heaters:

Gas-fired storage type water heaters: 0.67 – 0.0019 x V

Oil-fired water heaters: 0.59 – 0.0019 x V

Electric storage water heaters: 0.97 – 0.00132 x V

Gas-fired instantaneous: 0.62 – 0.0019 x V

Electric instantaneous: 0.93 – 0.00132 x V

Heat pump water heaters: 0.97 – 0.00132 x V

Where V is the rated volume in gallons.

Thermal Efficiency

Applicability

Oil and gas fired water heaters not covered by NAECA

Definition

The full load efficiency of a water heater at rated conditions expressed as a dimensionless ratio of output over input. This is also referred to as recovery efficiency.

Units

Unitless ratio

Input Restrictions

Building descriptors for the proposed design should be consistent with equipment specified on the construction documents or observed in the candidate building.

For NAECA covered water heaters that have specified an Energy Factor but not a recovery efficiency, the default recovery efficiency is as follows:

Gas Water Heaters: ηth th = 0.78

Electric Water Heaters: ηth th = 0.97

Standard Design

Baseline efficiency is set from the Appliance Efficiency Regulations

 

Tank Standby Loss

Applicability

Water heaters not covered by NAECA

Definition

The tank standby loss for storage tanks, which includes the effect of recovery efficiency.

Units

Btu/h for the entire tank

Input Restrictions

Standby loss is calculated by the following:

STBY = 453.75 × S × VOL

where

S                 =The standby loss fraction listed in the Commission’s Appliance Database of Certified Water Heaters,

VOL             =The actual storage capacity of the water heater as listed in the Commission’s Appliance Database of Certified Water Heaters (gallons)

Standard Design

 

Tank Off-Cycle Loss Coefficient

Applicability

Water heaters

Definition

The tank standby loss coefficient (UA) for the water heater. For small water heater covered by NAECA, the loss coefficient is a derived parameter, a function of the Energy Factor and recovery efficiency

Units

Btu/h-deg F

Input Restrictions

For NAECA covered water heaters, the loss coefficient is calculated by the following:

 

where

EF         =The energy factor of the rated water heater (Unitless)

RE         =The recovery efficiency of the rated water heater.  If this data is not available the default shall be 0.78 for gas water heaters and 0.93 for electric water heaters.

Pon        =The input power to the water heater, in Btu/h

Standard Design

The baseline loss coefficient for NAECA water heaters shall be:

10 Btu/h-F for gas-fired water heaters

Off Cycle Parasitic Losses

Applicability

Water heater

Definition

The rate of parasitic losses, such as a pilot light or controls, when the water heater is not heating.

Units

Watts

Input Restrictions

As designed

Standard Design

0

Off Cycle Fuel Type

Applicability

Water heater

Definition

The type of fuel that serves energy using parasitic equipment, such as a pilot light or controls, when the water heater is not heating.

Units

List: Electricity, Gas, Oil, Propane

Input Restrictions

As designed

Standard Design

Not applicable

On Cycle Parasitic Losses

Applicability

Water heater

Definition

The rate of parasitic losses, such as a pilot light or controls, when the water heater is not heating. This may be different than off cycle losses if the flue energy is considered.

Units

Watts

Input Restrictions

As designed

Standard Design

0

On Cycle Fuel Type

Applicability

Water heater

Definition

The type of fuel that serves energy using parasitic equipment, such as a pilot light or controls, when the water heater is not heating.

Units

List: Electricity, Gas, Oil, Propane

Input Restrictions

As designed

Standard Design

Electricity

Water Heater Ambient Location

Applicability

Water heater

Definition

The location of the water heater for determining losses and energy interaction with the surroundings

Units

List: Schedule, Zone, Outdoors

Input Restrictions

As designed

Standard Design

Zone

Tank Standby Loss Fraction

Applicability

Title 24 Standards

Definition

The tank standby loss fraction for storage tanks.

Units

Unitless

Input Restrictions

Prescribed to the value listed in the Commission’s Appliance Database of Certified Water Heaters

Standard Design

Not applicable

 

The part-load curve procedure in Title 24 can be an alternate method of specifying the effects of standby and parasitic losses on performance.  The primary method is to specify a loss coefficient for the storage tank.

Fuel Water Heater Part Load Efficiency Curve

Applicability

Water Heating equipment for which a loss coefficient is not specified (alternate method)

Definition

A set of factors that adjust the full-load thermal efficiency for part load conditions. The factor is set as a curve.

Units

Percent (%)

Input Restrictions

The following prescribed  curve shall be used based on user inputs. The curve shall take the form of a quadratic equation as follows:

(58)

 

where

FHeatPLC     The fuel heating part load efficiency curve

Fuelpartload       The fuel consumption at part load conditions (Btu/h)

Fuel design       The fuel consumption at design conditions (Btu/h)

Qpartload          The water heater capacity at part load conditions (Btu/h)

Qrated The water heater capacity at design conditions (Btu/h)

For Title 24, the coefficients shall be determined by the following : 

a = STBY / INPUT

b = INPUT

* or Thermal Efficiency (TE)

PLRn = Part-load ratio for the nth hour and shall always be less than 1.  PLR n is
     calculated from the following equation:

* or Thermal Efficiency (TE)

INPUT = The input capacity of the water heater expressed in Btu/hr.

STBY = Hourly standby loss expressed in Btu/hr.  For large storage gas water heaters STBY is listed in the CEC’s appliance database.  The value includes pilot energy and standby losses.  For all other systems refer to equation N2-62.

SRL = the Standard Recovery Load, taken from Appendix 5.4A, in Btu/hr, adjusted for the number of occupants according to the occupancy schedules.

For Boilers, Instantaneous gas or other storage type water heaters, not in the scope of Covered Consumer Products as defined in the Title 10 or the Code of Federal Regulations, Part 430; STBY = 453.75 × S × VOL

where

S                 =The standby loss fraction listed in the Commission’s Appliance Database of Certified Water Heaters,

VOL             =The actual storage capacity of the water heater as listed in the Commission’s Appliance Database of Certified Water Heaters,

Required inputs and standard and proposed design assumptions depend on the type of water heater and whether or not it is a DOE covered consumer product.

Standard Design

Not applicable

 

5.9.1.3 Recirculation Systems

This section describes the building descriptors for hot water recirculation systems. The baseline building has a recirculation system when the proposed design does. This is one aspect of the water heating system configuration (see above).

Recirculating systems shall follow the rules set forth in Appendix E of the 2013 Residential ACM Manual.

5.9.1.4 Water Heating Auxiliaries

External Storage Tank Insulation

Applicability

All water heating systems that have an external storage tank

Definition

Some water heating systems have a storage tank that is separate from the water heater(s) that provides additional storage capacity. This building descriptor addresses the heat loss related to the external tank, which is an additional load that must be satisfied by the water heater(s).

Units

R-value (h-ft2-F/Btu)

Input Restrictions

As specified in manufacturer data and documented on the construction documents

Standard Design

Heat loss associated with the storage tank in the baseline building shall meet the requirements for an unfired storage tank in the baseline standards which is an insulation R-value of 12.5. The surface area and location of the storage tank shall be the same as the proposed design.

External Storage Tank Area

Applicability

All water heating systems that have an external storage tank

Definition

Some water heating systems have a storage tank that is separate from the water heater(s) that provides additional storage capacity. This documents the entire exterior surface area of the tank.

Units

ft2

Input Restrictions

As specified in manufacturer specifications

Standard Design

Not applicable

External Storage Tank Location

Applicability

All water heating systems that have an external storage tank

Definition

Location of the storage tank, used to determine the heat loss rate and energy exchange with the surroundings

Units

List: Schedule, Zone, Outdoors

Input Restrictions

As designed

Standard Design

Not applicable

 

Heat Recovery

Applicability

Water heating systems that are coupled to heat recovery equipment

Definition

Building equipment such as air conditioners, chillers, gas fired generators, etc. produce thermal energy that may be recovered and used to heat water. The heat producing characteristics are generally defined for the equipment that is producing the heat, not the equipment that is receiving the heat (water heaters in this case). The building descriptors will vary depending on the equipment. The models for heat producing equipment need to produce output on an hourly basis so that the schedule of heat production and heating needs can be aligned and evaluated in the water heating model.

Units

Data structure: depends on the equipment producing the heat

Input Restrictions

There are no restrictions, other than agreement with the construction documents.

Standard Design

Not applicable

Solar Thermal

Applicability

Water heating systems with a solar thermal system

Definition

A solar thermal water heating system consists of one or more collectors. Water is passed through these collectors and is heated under the right conditions. There are two general types of solar water heaters: integrated collector storage (ICS) systems and active systems. Active systems include pumps to circulate the water, storage tanks, piping, and controls. ICS systems generally have no pumps and piping is minimal.

Solar systems may be tested and rated as a complete system or the collectors may be separately tested and rated. SRCC OG-300 is the test procedure for whole systems and SRCC OG-100 is the test procedure for collectors. The building descriptors used to define the solar thermal system may vary with each software application and with the details of system design.

The solar fraction shall be estimated by the f-chart procedure for solar water heating systems.

Units

Unitless fraction

Input Restrictions

The solar fraction provided by the solar DHW system shall be between 0 and 1.

Standard Design

The baseline building has no solar auxiliary system.

Combined Space Heating and Water Heating

Applicability

Projects that use a boiler to provide both space heat and water heating

Definition

A system that provides both space heating and water heating from the same equipment, generally the space heating boiler. Such systems are restricted by the baseline standards, but may be modeled in the candidate building. The restrictions are due to the misalignment of the space heating load and the water heating load. The first is highly intermittent and weather dependent, while the latter is more constant and not generally related to the weather.

Units

Data structure

Input Restrictions

The proposed design may have a combined space and water heating system.

Standard Design

The baseline building shall be modeled with separate space heating and water heating systems

5.9.2 Exterior Lighting    

 

Outdoor lighting requirements are specified in Standards section 140.7. Outdoor lighting shall not be modeled in the proposed design or standard design, and no tradeoffs are available with other building end uses or systems. Outdoor lighting shall meet all prescriptive requirements in the Standards. Compliance software shall accept user input for outdoor lighting and verify that the proposed design outdoor lighting does not exceed the standard design outdoor lighting, and shall include verification of compliance on the appropriate compliance form(s).

5.9.3 Swimming Pools

Swimming pools must meet applicable mandatory requirements and are not required to be modeled for California Title 24 compliance or Reach.

5.9.4 Other Electricity Use    

This set of building descriptors should be used to include any miscellaneous electricity use that would add to the electric load of the building and would be on the building meter. These energy uses are assumed to be outside the building envelope and do not contribute heat gain to any thermal zone.

Miscellaneous Electric Power

Applicability

All buildings with miscellaneous electric equipment located on the building site

Definition

The power for miscellaneous equipment.

Units

Watts (W)

Input Restrictions

As designed.

Standard Design

Same as the proposed design

Miscellaneous Electric Schedule

Applicability

All buildings with miscellaneous electric equipment located on the building site

Definition

The schedule of operation for miscellaneous electric equipment. This is used to convert electric power to energy use.

Units

Data structure: schedule, fractional

Input Restrictions

The schedule specified for the building should match the operation patterns of the system.

Standard Design

Same as the proposed design

5.9.5 Other Gas Use    

This set of building descriptors should be used to include any miscellaneous gas use that would add to the load of the building and would be on the building meter. These energy uses are assumed to be outside the building envelope and do not contribute heat gain to any thermal zone.

Other Gas Power

Applicability

All buildings that have commercial gas equipment

Definition

Gas power is the peak power which is modified by the schedule (see below).

Units

Btu/h-ft²

Input Restrictions

As designed

Standard Design

Same as the proposed design

Other Gas Schedule

Applicability

All buildings that have commercial gas equipment

Definition

The schedule of operation for commercial gas equipment. This is used to convert gas power to energy use.

Units

Data structure: schedule, fractional

Input Restrictions

Continuous operation is prescribed.

Standard Design

Same as the proposed design