All outdoor incandescent luminaires rated over 100 watts, determined in accordance with Section 130.0(c)2, shall be controlled by a motion sensor.

All outdoor luminaires rated for use with lamps greater than 150 lamp watts, determined in accordance with Section 130.0(c), shall comply with Backlight, Uplight, and Glare (collectively referred to as "BUG" in accordance with IES TM-15-11, Addendum A) requirements as follows:
1. There are no Backlight requirements in Section 130.2 of Part 6; and
2. Maximum zonal lumens for Uplight shall be in accordance with TABLE 130.2-A; and
3. Maximum zonal lumens for Glare shall be in accordance with TABLE 130.2-B.
EXCEPTION 1 to Section 130.2(b): Signs.
EXCEPTION 2 to Section 130.2(b): Lighting for building facades, public monuments, statues, and vertical surfaces of bridges.
EXCEPTION 3 to Section 130.2(b): Lighting not permitted by a health or life safety statute, ordinance, or regulation to be a cutoff luminaire.
EXCEPTION 4 to Section 130.2(b): Temporary outdoor lighting.
EXCEPTION 5 to Section 130.2(b): Replacement of existing pole mounted luminaires in hardscape areas meeting all of the following conditions:
A. Where the existing luminaire does not meet the luminaire BUG requirements in Section 130.2(b); and
B. Spacing between existing poles is greater than six times the mounting height of the existing luminaires; and
C. Where no additional poles are being added to the site; and
D. Where new wiring to the luminaires is not being installed; and
E. Provided that the connected lighting power wattage is not increased.
EXCEPTION 6 to Section 130.2(b): Luminaires that illuminate the public right of way on publicly maintained roadways, sidewalks, and bikeways.

Outdoor lighting controls shall be installed that meet the following requirements as applicable:
EXCEPTION 1 to Section 130.2(c): Outdoor lighting not permitted by a health or life safety statute, ordinance, or regulation to be turned OFF.
EXCEPTION 2 to Section 130.2(c): Lighting in tunnels required to be illuminated 24 hours per day and 365 days per year.
1. All installed outdoor lighting shall be controlled by a photocontrol or outdoor astronomical time-switch control that automatically turns OFF the outdoor lighting when daylight is available.
2. All installed outdoor lighting shall be circuited and independently controlled from other electrical loads by an automatic scheduling control.
3. All installed outdoor lighting, where the bottom of the luminaire is mounted 24 feet or less above the ground, shall be controlled with automatic lighting controls that meet all of the following requirements:
A.
Shall be motion sensors or other lighting control systems that automatically
controls lighting in accordance with Item B in response to the area being
vacated of occupants; and
B. Shall be capable of automatically reducing the lighting power of each luminaire by at least 40 percent but not exceeding 80 percent, or provide continuous dimming through a range that includes 40 percent through 80 percent, and
C. Shall employ auto-ON functionality when the area becomes occupied; and
D. No more than 1,500 watts of lighting power shall be controlled together.
EXCEPTION 1 to Section 130.2(c)3: Lighting for Outdoor Sales Frontage, Outdoor Sales Lots, and Outdoor Sales Canopies complying with Section 130.2(c)4.
EXCEPTION 2 to Section 130.2(c)3: Lighting for Building Facades, Ornamental Hardscape and Outdoor Dining complying with Section 130.2(c)5.
EXCEPTION 3to Section 130.2(c)3:, Outdoor lighting, where luminaire rated wattage is determined in accordance with Section 130.0(c), and which meet one of the following conditions:
A. Pole-mounted luminaires each with a maximum rated wattage of 75 watts; or
B. Non-pole mounted luminaires with a maximum rated wattage of 30 watts each; or
C. Linear lighting with a maximum wattage of 4 watts per linear foot of luminaire.
EXCEPTION 4 to Section 130.2(c)3: Applications listed as Exceptions to Section 140.7(a) shall not be required to meet the requirements of Section 130.2(c)3.
4. For Outdoor Sales Frontage, Outdoor Sales Lots, and Outdoor Sales Canopies lighting, an automatic lighting control shall be installed that meets the following requirements:
A. A part-night outdoor lighting control as defined in Section 100.1; or
B. Motion sensors capable of automatically reducing lighting power by at least 40 percent but not exceeding 80 percent, and which have auto-ON functionality.
5. For Building Facade, Ornamental Hardscape and Outdoor Dining lighting, an automatic lighting control shall be installed that meets one or more of the following requirements:
A. A part-night outdoor lighting control as defined in Section 100.1; or
B. Motion sensors capable of automatically reducing lighting power by at least 40 percent but not exceeding 80 percent, and which have auto-ON functionality; or
C. A centralized time-based zone lighting control capable of automatically reducing lighting power by at least 50 percent.
D. Outdoor wall mounted luminaires having a bilaterally symmetric distribution as described in the IES Handbook (typically referred to as "wall packs") where the bottom of the luminaire is mounted 24 feet or less above the ground shall comply with the applicable requirements in Section 130.2(c)3.
|
Secondary Solid Angle |
Maximum Zonal Lumens per Outdoor Lighting Zone | |||
|
OLZ 1 |
OLZ 2 |
OLZ 3 |
OLZ 4 | |
|
Uplight High (UH) 100 to 180 degrees |
10 |
50 |
500 |
1,000 |
|
Uplight Low (UL) 90 to <100 degrees |
10 |
50 |
500 |
1,000 |
|
Glare Rating for Asymmetrical Luminaire Types (Type 1, Type II, Type III, Type IV) | ||||
|
Secondary Solid Angle |
Maximum Zonal Lumens per Outdoor Lighting Zone | |||
|
OLZ 1 |
OLZ 2 |
OLZ 3 |
OLZ 4 | |
|
Forward Very High (FVH) 80 to 90 degrees |
100 |
225 |
500 |
750 |
|
Backlight Very High (BVH) 80 to 90 degrees |
100 |
225 |
500 |
750 |
|
Forward High (FH) 60 to <80 degrees |
1,800 |
5,000 |
7,500 |
12,000 |
|
Backlight High (BH) 60 to <80 degrees |
500 |
1,000 |
2,500 |
5,000 |
|
| ||||
|
Glare Rating for Quadrilateral Symmetrical Luminaire Types (Type V, Type V Square) | ||||
|
Secondary Solid Angle |
Maximum Zonal Lumens per Outdoor Lighting Zone | |||
|
OLZ 1 |
OLZ 2 |
OLZ 3 |
OLZ 4 | |
|
Forward Very High (FVH) 80 to 90 degrees |
100 |
225 |
500 |
750 |
|
Backlight Very High (BVH) 80 to 90 degrees |
100 |
225 |
500 |
750 |
|
Forward High (FH) 60 to <80 degrees |
1,800 |
5,000 |
7,500 |
12,000 |
|
Backlight High (BH) 60 to <80 degrees |
1,800 |
5,000 |
7,500 |
12,000 |