Each electrical service shall have permanently installed user-accessible metering of total electrical energy use per TABLE 130.5-A
EXCEPTION to Section 130.5(a) Buildings for which the utility company provides a meter for occupant or user use that indicates instantaneous kW demand and kWh for a user-resettable period.
Electrical power distribution systems shall be designed to permit the disaggregated measurement of electrical load energy uses downstream from the service meter according to TABLE 130.5-B. Additive and subtractive methods may be used to determine aggregate and disaggregated energy use. This may be accomplished by any of the following methods:
1. Separate switchboards, motor control centers, or panelboards to which are connected only the required load or group of loads; or
2. Subpanels of the above to which are connected only the required load or group of loads and for which the subpanel load can be independently measured in aggregate; or
3. Branch circuits, taps or disconnects requiring overcurrent protection devices rated 60 amperes or greater.
EXCEPTION 1 to Section 130.5(b) Buildings for which a complete metering and measurement system is provided that at a minimum measures and reports the loads called for in TABLE 130.5-B.
EXCEPTION 2 to Section 130.5(b) Alterations where all of the following conditions exist are not required to comply with this section:
A. The following existing equipment remains in place:
i. Service distribution switchboards or panelboards; and
ii. Feeders; and
iii. Motor control centers or panelboards.
B. Existing equipment included in Item A (above) remains unaltered except for:
i. Changes to load circuit connections; or
ii. Changes to the quantity of outgoing overcurrent protection devices; or
iii. Changes to the ampacity of outgoing overcurrent protection devices.
1. Feeders. Feeder conductors shall be sized for a maximum voltage drop of 2 percent at design load.
2. Branch Circuits. Branch circuit conductors shall be sized for a maximum voltage drop of 3 percent at design load.
EXCEPTION to Section 130.5(c): Feeder conductors and branch circuits that are dedicated to emergency services.
In all buildings, both controlled and uncontrolled 120 volt receptacles shall be provided in each private office, open office area, reception lobby, conference room, kitchenette in office spaces, and copy room. Additionally, hotel/motel guest rooms shall comply with Item 5. Controlled receptacles shall meet the following requirements, as applicable:
1. Electric circuits serving controlled receptacles shall be equipped with automatic shut-OFF controls following the requirements prescribed in Section 130.1(c) (1 through 5); and
2. At least one controlled receptacle shall be installed within 6 feet from each uncontrolled receptacle or a splitwired duplex receptacle with one controlled and one uncontrolled receptacle shall be installed; and
3. Controlled receptacles shall have a permanent marking to differentiate them from uncontrolled receptacles; and
4. For open office areas, controlled circuits shall be provided and marked to support installation and configuration of office furniture with receptacles that comply with Section 130.5(d) and
5. For hotel and motel guest rooms at least one-half of the 120-volt receptacles in each guest room shall be controlled receptacles that comply with Section 130.5(d)1, 2, and 3. Electric circuits serving controlled receptacles shall have captive card key controls, occupancy sensing controls, or automatic controls such that, no longer than 30 minutes after the guest room has been vacated, power is switched off.
6. Plug-in strips and other plug-in devices that incorporate an occupant sensor shall not be used to comply with this requirement.
EXCEPTION 1 to Section 130.5(d): In open office areas, controlled circuit receptacles are not required if, at time of final permit, workstations are installed, and each workstation is equipped with an occupant sensing control that is permanently mounted in each workstation, and which controls a hardwired, nonresidential-rated power strip. Plug-in strips and other plug-in devices that incorporate an occupant sensor shall not be used for this exception.
EXCEPTION 2 to Section 130.5(d): Receptacles that are only for the following purposes:
i. Receptacles specifically for refrigerators and water dispensers in kitchenettes.
ii. Receptacles located a minimum of six feet above the floor that are specifically for clocks.
iii. Receptacles for network copiers, fax machines, A/V and data equipment other than personal computers in copy rooms.
iv. Receptacles on circuits rated more than 20 amperes.
Demand responsive controls and equipment shall be capable of receiving and automatically responding to at least one standards based messaging protocol which enables demand response after receiving a demand response signal.
1. An EMCS may be installed to comply with the requirements of one or more lighting controls if it meets the following minimum requirements:
A. Provides all applicable functionality for each specific lighting control or system for which it is installed in accordance with Section 110.9; and
B. Complies with all applicable Lighting Control Installation Requirements in accordance with Section 130.4 for each specific lighting control or system for which it is installed; and
C. Complies with all applicable application requirements for each specific lighting control or system for which it is installed, in accordance with Part 6.
2. An EMCS may be installed to comply with the requirements of a thermostat if it complies with all applicable application requirements for each thermostat in accordance with Part 6.
Meter Type |
Services rated 50 kVA or less |
Services rated more than 50kVA and less than or equal to 250 kVA |
Services rated more than 250 kVA and less than or equal to 1000kVA |
Services rated more than 1000kVA |
Instantaneous (at the time) kW demand |
Required |
Required |
Required |
Required |
Historical peak demand (kW) |
Not required |
Not required |
Required |
Required |
Resettable kWh |
Required |
Required |
Required |
Required |
kWh per rate period |
Not required |
Not required |
Not required |
Required |
Load Type |
Services rated 50 kVA or less |
Services rated more than 50kVA and less than or equal to 250 kVA |
Services rated more than 250 kVA and less than or equal to 1000kVA |
Services rated more than 1000kVA |
Lighting including exit and egress lighting and exterior lighting |
Not required |
All lighting in aggregate |
All lighting disaggregated by floor, type or area |
All lighting disaggregated by floor, type or area |
HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers, and circulation pumps associated with HVAC |
Not required |
All HVAC in aggregate |
All HVAC in aggregate and each HVAC load rated at least 50 kVA |
All HVAC in aggregate and each HVAC load rated at least 50kVA |
Domestic and service water system pumps and related systems and components |
Not required |
All loads in aggregate |
All loads in aggregate |
All loads in aggregate |
Plug load including appliances rated less than 25 kVA |
Not required |
All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf |
Elevators, escalators, moving walks, and transit systems |
Not required |
All loads in aggregate |
All loads in aggregate |
All loads in aggregate |
Other individual non-HVAC loads or appliances rated 25kVA or greater |
Not required |
All |
Each |
Each |
Industrial and commercial load centers 25 kVA or greater including theatrical lighting installations and commercial kitchens |
Not required |
All |
Each |
Each |
Renewable power source (net or total) |
Each group |
Each group |
Each group |
Each group |
Loads associated with renewable power source |
Not required |
All loads in aggregate |
All loads in aggregate |
All loads in aggregate |
Charging stations for electric vehicles |
All loads in aggregate |
All loads in aggregate |
All loads in aggregate |
All loads in aggregate |