5.4 Space Uses

Each thermal zone discussed above may be subdivided into spaces. This section presents the building descriptors that relate to the space uses. Space uses and the defaults associated with them are listed in Appendix 5.4A. Every thermal zone shall have at least one space, as defined in this section. Daylit spaces should generally be separately defined by space type and/or orientation.

5.4.1    General Information

Space Function Type

Applicability

All projects

Definition

The space function type that defines occupancy, internal load, and other characteristics, as indicated in Appendix 5.4A.

If lighting compliance is not performed, use either approach but actual LPDs cannot be entered for the spaces; the LPDs of the building match the standard design.

The allowed space function types in area category are available from Appendix 5.4A. The building or space type determines the following standard design inputs:

            Number of occupants (occupant density)

            Equipment power density

            Lighting power density

            Hot water load

            Schedules (from Appendix 5.4B)

Units

List

Input Restrictions

Only selections shown in Appendix 5.4A may be used.

For unconditioned spaces, the user must enter “unconditioned” as the occupancy and ventilation; internal loads and uses are set to zero. Compliance software shall require the user to identify if lighting compliance is performed (lighting plans are included or have already been submitted).

Standard Design

Same as proposed

Existing Buildings

Same as proposed

 

Ventilation Space Function

Applicability

All projects

Definition

A unique identifier for ventilation requirements. A given space type may have different ventilation functions available, which define the design ventilation rate and minimum ventilation rates for the space, and any exhaust air requirements.

Units

List (from Reference Manual Appendix 5.4A)

Input Restrictions

As designed (selection from list)

Standard Design

Same as the proposed

Existing Buildings

Same as proposed

 

Floor Area

Applicability

All projects

Definition

The floor area of the space

The area of the spaces that make up a thermal zone shall sum to the floor area of the thermal zone.

Units

Square feet (ft²)

Input Restrictions

Area shall be measured to the outside of exterior walls and to the center line of partitions

Standard Design

Area shall be identical to the proposed design

Existing Buildings

Same as proposed

5.4.2    Infiltration

Infiltration Method

Applicability

All projects

Definition

Energy simulation programs have a variety of methods for modeling uncontrolled air leakage or infiltration. Some procedures use the effective leakage area which is generally applicable for small residential scale buildings. The component leakage method requires the user to specify the average leakage through the building envelope per unit area (ft²). Other methods require the specification of a maximum rate, which is modified by a schedule.

Units

List effective leakage area, component leakage, or air changes per hour

Input Restrictions

The component leakage area is prescribed; a fixed infiltration rate shall be specified and calculated as a leakage per area of exterior envelope, including the gross area of exterior walls and fenestration but excluding roofs and exposed floors.

Standard Design

The infiltration method used for the standard design shall be the same as the proposed design.

 

Infiltration Data

Applicability

All projects

Definition

Information needed to characterize the infiltration rate in buildings.

The required information will depend on the infiltration method selected above. For the effective leakage area method, typical inputs are leakage per exterior wall area in ft² or other suitable units and information to indicate the height of the building and how shielded the site is from wind pressures. Only zones with exterior wall area are assumed to be subject to infiltration.

Units

A data structure is required to define the effective leakage area model.

Infiltration shall be calculated each hour using the following equation:

Where:

Infiltration =

zone infiltration airflow (m³/s-m²)

Idesign =

design zone infiltration airflow (m³/s-m²)

Fschedule =

fractional adjustment from a prescribed schedule, based on HVAC availability schedules in Appendix 5.4B(unitless)

tzone =

zone air temperature (°C)

todb =

outdoor dry bulb temperature (°C)

ws =

the wind speed (m/s)

A =

overall coefficient (unitless)

B =

temperature coefficient (1/°C)

C =

wind speed coefficient (s/m)

D =

wind speed squared coefficient (s²/m²)

Input Restrictions

For the proposed design, Idesign shall have a fixed value of 0.0448 cfm/ft2 (0.000228 m³/s-m²) times the gross wall area exposed to ambient outdoor air. A, B and D shall be fixed at zero. C shall be fixed at 0.10016 hr/mile (0.224 s/m).

For nonresidential spaces with operable windows that do not have mechanical system interlocks, the CBECC software shall automatically increase infiltration to the space by 0.15 cfm/ft2 whenever the outside air temperature is between 50°F and 90°F and when the HVAC system is operating.  High-rise dwelling units are exempt from mechanical system interlocks.

Standard Design

The standard design shall use the equation listed above, with coefficients A, B, and D set to 0. C shall be set to 0.10016 hr/mile (0.224 s/m) Idesign shall be 0.0448 cfm/ft2.

 

Infiltration Schedule

Applicability

When an infiltration method is used that requires the specification of a schedule

Definition

With the ACH method and other methods (see above), it may be necessary to specify a schedule that modifies the infiltration rate for each hour or time step of the simulation. Typically the schedule is either on or off but can also be fractional.

Units

Data structure: schedule, fractional

Input Restrictions

The infiltration schedule shall be prescribed based on the HVAC system operating schedules from Appendix 5.4B. The infiltration schedule shall be set equal to 1 when the HVAC system is scheduled off and 0.25 when the HVAC system is scheduled on. This is based on the assumption that when the HVAC system is on it brings the pressure of the interior space above the pressure of the exterior, decreasing the infiltration of outside air. When the HVAC system is off, interior pressure drops below exterior pressure and infiltration increases.

The implementation of the prescriptive requirement for interlocks for operable windows will model mixed mode ventilation as an increased infiltration rate when outside air conditions allow for nonresidential buildings only, excluding healthcare and high-rise residential buildings and spaces.

Standard Design

The infiltration schedule for the standard design shall be set equal to 1 when the HVAC system is scheduled off and 0.25 when the HVAC system is scheduled on.

 

5.4.3    Occupants

For space level information on occupancy, lighting, and plug load schedules, as well as occupant density, allowed lighting power density. Appendix 5.4A provides a table of allowed space types.

 

Fixed Seating in Space

Applicability

All projects that have a space with fixed seating (such as a theater or auditorium)

Definition

This is a flag that indicates that the space has fixed seating. If checked, this flag allows the user to override the default occupancy with values that comply with the California Building Code.

Units

Boolean

Input Restrictions

As designed

May not be used with high-rise residential, hotel/motel, unoccupied, and unleased tenant area spaces. The default is false.

Standard Design

Same as proposed

Existing Buildings

The number of occupants must be identical for both the proposed and standard design cases.

 

Dwelling Units per Space

Applicability

High-rise residential projects

Definition

The number of residential living units within a single compliance model space

Units

positive integer

Input Restrictions

As designed

Standard Design

1

Existing Buildings

1

 

Number of Bedrooms

Applicability

High-rise residential projects

Definition

The number of bedrooms per dwelling unit

Units

Integer

Input Restrictions

As designed but constrained to a minimum of 0 (studio) and a maximum of 5

Standard Design

Same as proposed

Existing Buildings

Same as proposed

 

Number of Occupants

Applicability

High-rise residential projects

Definition

The number of people in a space.

The number of people is modified by an hourly schedule (see below), which approaches but does not exceed 1.0. Therefore, the number of people specified by the building descriptor is similar to design conditions as opposed to average occupancy.

Units

The number of people may be specified in an absolute number, ft²/person, or people/1000 ft².

Input Restrictions

The number of occupants is prescribed, and the values are given by Space Type in Appendix 5.4A, For high-rise residential spaces, the number of occupants is defined as: Max (number of bedrooms +1, 2).

Standard Design

The number of occupants must be identical for both the proposed and standard design cases.

Standard Design:

Existing Buildings

The number of occupants must be identical for both the proposed and standard design cases.

 

Occupant Heat Rate

Applicability

All projects

Definition

The sensible and latent heat produced by each occupant in an hour.

This depends on the activity level of the occupants and other factors. Heat produced by occupants must be removed by the air conditioning system as well as the outside air ventilation rate and can have a significant impact on energy consumption.

Units

Btu/h specified separately for sensible and latent gains

Input Restrictions

The occupant heat rate is prescribed.

Standard Design

The occupant heat rate for the standard design shall be the same as the proposed design.

Standard Design:

Existing Buildings

Same as proposed

 

Occupancy Schedule

Applicability

All projects

Definition

The occupancy schedule modifies the number of occupants to account for expected operational patterns in the building. The schedule adjusts the heat contribution from occupants to the space on an hourly basis to reflect time-dependent usage patterns. The occupancy schedule can also affect other factors such as outside air ventilation, depending on the control mechanisms specified.

Units

Data structure: schedule, fractional

Input Restrictions

The occupant schedule is prescribed for California compliance. For California compliance, an appropriate schedule from Appendix 5.4B shall be used.

Standard Design

Occupancy schedules are identical for proposed and standard design buildings.

Standard Design:

Existing Buildings

Same as proposed

 

5.4.4    Interior Lighting

The building descriptors in this section are provided for each lighting system. Typically a space will have only one lighting system but, in some cases, it could have two or more. Examples include a general and task lighting system in offices, or hotel multi-purpose rooms that have lighting systems for different functions. It may also be desirable to define different lighting systems for areas that are daylit and those that are not.

 

Lighting Classification Method

Applicability

Each space in the building

Definition

Indoor lighting power can be specified using the area category method or the tailored method.

Area category method can be used for all areas of the building with space types listed in Appendix 5.4A. This method can be used by itself or with the tailored lighting method.

Tailored lighting method can be used for spaces with primary function listed in Table 140.6-D of the standards. The tailored lighting method is intended to accommodate special lighting applications. The tailored lighting method can be used by itself for all areas of the building or with the area category method. For a given area only one classification type can be used.

Units

List

Input Restrictions

Only area category or tailored lighting are allowed

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

Table 6: Lighting Specification

Options: Lighting Classification Method

Area category method

Tailored lighting Method

Allowed combinations with other lighting classification methods

May be combined with tailored method in same building, but not in same space.

May be combined with area category method, in same building, but not in same space.

Allowed Regulated lighting power types

General lighting power

Additional lighting power

General lighting power

Wall display lighting power

Floor display and task lighting power

Ornamental/special effect lighting power

Very valuable display case lighting power

Allowed Trade-offs

General lighting between conditioned spaces using area category method

General lighting between conditioned spaces using area category and tailored method

General lighting between conditioned spaces using tailored method

General lighting between conditioned spaces using tailored and area category method

Exception: With the area category method, additional lighting power can be used only if the tailored lighting method is not used in any area of the building.

 

Regulated Interior Lighting Power Density

Applicability

All projects when lighting compliance is performed

Definition

Total connected lighting power density for all regulated interior lighting power

This includes the loads for lamps and ballasts. The total regulated interior lighting power density is the sum of general lighting power and applicable custom lighting power per floor area in a space. Calculation of lighting power for conditioned spaces is done separately from unconditioned spaces.

Lighting in unconditioned spaces can be modeled, but total lighting power in unconditioned spaces is not enforced in the compliance software. Lighting in unconditioned spaces must follow prescriptive compliance, and must be documented on appropriate compliance forms. No tradeoffs are allowed between lighting in conditioned spaces and lighting in unconditioned spaces.

Units

W/ft2

Input Restrictions

Proposed value is:

a) For the area category method: the sum of the proposed general lighting power and the proposed general lighting exceptional power within a conditioned space or a user input value if no interior lighting systems are modeled.

b)  For the tailored lighting method: the sum of the proposed general lighting power and the proposed custom lighting power within a conditioned space or a user input value if no interior lighting systems are modeled.

When lighting compliance is not performed, the lighting power may not be entered and is set equal to the lighting level of the standard design, which is set to the levels for the selected occupancy from Appendix 5.4A.

Standard Design

For spaces without special task lighting, wall display lighting or similar requirements, this input will be the same as the general lighting power density. See the general lighting power building descriptor for details.

With the area category and tailored method regulated interior lighting power for each space will be the sum of general lighting power and allowed custom lighting power.

Standard Design:

Existing Buildings

For alterations where less than 40 luminaires have been modified the standard design is the existing lighting condition before the alteration. If 40 or more luminaires have been modified, the prescriptive requirements for new construction apply.

 

General Lighting Power

Applicability

All spaces or projects

Definition

General lighting power is the power used by installed electric lighting that provides a uniform level of illumination throughout an area, exclusive of any provision for special visual tasks or decorative effect, and also known as ambient lighting.

Units

Watts

Input Restrictions

As designed

For spaces without special task lighting, wall display lighting or similar requirements, this input will be the same as the regulated lighting power.

Trade-offs in general lighting power are allowed between spaces all using the area category method, between spaces all using the tailored lighting method and between spaces that use area category and tailored methods. See Table 6: Lighting Specification for details.

Standard Design

With the area category method, general lighting power is the product of the lighting power densities for the space type from Appendix 5.4A and the floor areas for the corresponding conditioned spaces.

With the tailored lighting method, general lighting power is the product of the lighting power density for the primary function type in Table 140.6-D of the standards and the floor area of the space. The lighting power density is given as a function of room cavity ratio (RCR) and interior illumination level in Table 140.6-G. No interpolation is allowed for this table.

The general lighting power in the tailored method is calculated by the following steps:

Step 1. Determine illumination level from Table 140.6-D by matching the primary function area in Table 140.6-D with the space type in Appendix 5.4A.

Step 2. Calculate the room cavity ratio (RCR) by using the applicable equation in Table 140.6-F.

            Rectangular Rooms:  RCR = 5 x H x (L+W) / (L x W)

            Irregular Rooms:  RCR = 2.5 x H x P / A

Where: L = length of room; W = width of room; H = vertical distance from the work plane to the centerline of the lighting fixture; P = perimeter of room, and A = area of room

Step 3. Determine the general lighting in the space(s) using the tailored method by a look-up in Table 140.6-G, where the general lighting LPD is a function of illuminance level and RCR. No interpolation is allowed for this table. A space between two illuminance levels (for example, 150 lux) uses the applicable LPD from the next lower illuminance level (100 lux).

The standard design uses the irregular room RCR equation for both simplified and detailed geometry models.

The standard design lighting power is modified by a factor of 1/1.20 (0.833) if the simplified geometry approach is used and if the visible transmittance of any fenestration in the space does not meet the prescriptive requirements established in Section 140.3 of the standards.

Standard Design:

Existing Buildings

When the lighting status is “existing” (and unaltered) for the space, the standard design is the same as the existing, proposed design.

When the lighting status is “altered” for the space, and at least 10 percent of existing luminaires have been altered:

a)   If the lighting status is “existing”, then the standard design LPD is the same as the proposed design.

b)   If the lighting status is “new”, then the standard design LPD is same as new construction.

c)   If the lighting status is “altered”, then the standard design LPD is the same as new construction.

 

General Lighting Exceptional Power

Applicability

Spaces that use the area category method; note that some exceptional allowances are only applicable to certain space types. See Table 140.6-C of the standards.

Definition

The standards provide an additional lighting power allowance for special cases. Each of these lighting system cases is treated separately as “use-it-or-lose-it” lighting--the user receives no credit (standard design matches proposed) but there is a maximum power allowance for each item). There are eight lighting power allowances, as defined in the standards Table 140.6-C footnotes.

Units

Data structure. This input has eight data elements:

1.   Specialized task work, laboratory (W/ft2)

2.   Specialized task work, other approved areas (W/ft2)

3.   Ornamental lighting (W/ft2)

4.   Precision commercial and industrial work (W/ft2)

5.   White board or chalk board lighting (W/linear foot)

6.   Accent, display and feature lighting (W/ft2)

7.   Decorative Lighting (W/ft2)        

8.   Videoconferencing studio lighting (W/ft2)

Input Restrictions

As designed

Standard Design

The standard design general lighting exceptional power (GLEP) is given by the following equation:

Where:

GLEPstd

The GLEP of the standard design

GLEPprop,i

The proposed GLEP of the footnote allowance i in the data structure above, or in the footnotes to Table 140.6-C of the standards

GLEAi

The general lighting exceptional allowance (GLEA) , which is the maximum allowed added lighting power in the rightmost column in Table 140.6-C of the standards; these allowances are, for GLEA1 through GLEA8, 0.2 W/ft2, 0.5 W/ft2, 0.5 W/ft2, 1.0 W/ft2, 5.5 W/linear foot, 0.3 W/ft2, 0.2 W/ft2 and 1.5 W/ft2, respectively

GLETAi

The general lighting exceptional task area  (GLETA) for the ith exception, where the exception number corresponds to the area category exception number in the footnotes to Table 140.6-C of the standards

Standard Design:

Existing Buildings

Not applicable

 

General Lighting Exceptional Task Area

Applicability

Spaces that use area category method

Definition

The area associated with each of the exceptional lighting allowances in the GLEP building descriptor

Units

ft2

Input Restrictions

As designed but cannot exceed the floor area of the space

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

White Board Length

Applicability

Spaces that use area category method and take GLEP allowance #5

Definition

The linear length of the white board or chalk board in feet

Units

Ft

Input Restrictions

As designed

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

Custom Lighting Power

Applicability

All spaces or projects that use the tailored lighting method

Definition

Custom lighting power covers lighting sources that are not included as general lighting, including task lighting, display lighting, and other specialized lighting designated in the footnotes to Table 140.6-C and lighting systems in Table 140.6-D of the standards. This lighting must be entered separately from the general lighting because it is not subject to tradeoffs.

Software shall allow the user to input a custom lighting input for the allowed lighting system. If area category method is used, custom lighting power cannot be used if the tailored method is used for any area of the building. See Table 6: Lighting Specification for details.

Units

Watts

Input Restrictions

As designed

Standard Design

Same as proposed but subject to the maximum limits specified in the footnotes to Table 140.6-C and Table 140.6-D of the standards. For spaces using the tailored method, the maximum allowed custom power is defined by the following procedure:

The standard design custom lighting power is calculated by the sum of the following four terms:

1)  The product of the standard design wall display power and the standard design wall display length;

2)  The product of the standard design floor and task lighting power and the standard design floor and task lighting area;

3)  The product of the standard design ornamental and special effect lighting power, and the standard design ornamental and special effect lighting area; and

4)  The product of the standard design very valuable display case power and the standard design very valuable display case area.

Standard Design:

Existing Buildings

For alterations where less than 10 percent of existing luminaires have been modified, the standard design is the existing lighting condition before the alteration. If 10 percent or more luminaires have been altered, the custom lighting power for the standard design is the same as proposed, but subject to the limits specified in the footnotes to Table 140.6-C of the standards.

 

Wall Display Power

Applicability

All spaces that use the tailored method

Definition

The lighting power allowed for wall display, as specified in standards Table 140.6-D, column 3

Units

W/ft

Input Restrictions

As designed

Standard Design

The standard design lighting power is the lesser of the proposed design wall display power or the limit specified in Table 140.6-D for the applicable space type.

Standard Design:

Existing Buildings

Same as proposed

 

Wall Display Length

Applicability

All spaces that use the tailored method

Definition

The horizontal length of the wall display lighting area using the tailored method for the space

Units

ft

Input Restrictions

As designed but this value cannot exceed the floor area of the space

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

Floor and Task Lighting Power

Applicability

All spaces that use the tailored method

Definition

The lighting power allowed for floor display and task lighting, as specified in Table 140.6-D, column 4, of the standards

Units

W/ft2

Input Restrictions

As designed

Standard Design

The standard design floor and task lighting power is the lesser of the proposed design floor and task lighting power or the limit specified in Table 140.6-D, column 4, for the applicable space type.

Standard Design:

Existing Buildings

Same as proposed

 

Floor and Task Lighting Area

Applicability

All spaces that use the tailored method

Definition

The lighting area that is served by the floor and task lighting defined using the tailored method for the space

Units

ft2

Input Restrictions

As designed but this value cannot exceed the floor area of the space

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

Ornamental and Special Effect Lighting Power

Applicability

All spaces that use the tailored method

Definition

The lighting power allowed for ornamental and special effect lighting, as specified in Table 140.6-D, column 5, of the standards

Units

W/ft2

Input Restrictions

As designed

Standard Design

The standard design ornamental and special effect lighting power is the lesser of the proposed design ornamental and special effect lighting power or the limit specified in Table 140.6-D, column 5, for the applicable space type.

Standard Design:

Existing Buildings

Same as proposed

 

Ornamental and Special Effect Lighting Area

Applicability

All spaces that use the tailored method

Definition

The lighting area that is served by the ornamental and special effect lighting defined using the tailored method for the space

Units

ft2

Input Restrictions

As designed but this value cannot exceed the floor area of the space

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

Very Valuable Display Case Lighting Power

Applicability

All spaces that use the tailored method

Definition

The lighting power allowed for very valuable display case lighting, as specified in standards section 140.6(c)3L

Units

W/ft2

Input Restrictions

As designed

Standard Design

The standard design very valuable display case lighting power is the lesser of:

a)   The product of the area of the primary function and 0.8 W/ft2;

b)   The product of the area of the display case and 12 W/ft2; or

c)   The proposed very valuable display lighting power.

Standard Design:

Existing Buildings

Same as proposed

 

Very Valuable Display Case Lighting Area

Applicability

All spaces that use the tailored method

Definition

The area of the very valuable display case(s) in plan view

Units

ft2

Input Restrictions

As designed but this value cannot exceed the floor area of the space

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as proposed

 

Non-Regulated Interior Lighting Power

Applicability

All projects

Definition

For California, §140.6(a)3 of the energy efficiency standards identifies non-regulated (exempted) lighting.

Units

W/ft2 or Watts

Input Restrictions

As designed

The non-regulated lighting power should be cross-referenced to the type of exception and to the construction documents. The default for non-regulated lighting power is zero.

Standard Design

The non-regulated interior lighting in the standard design shall be the same as the proposed design.

Standard Design:

Existing Buildings

Same as proposed

 

Lighting Schedules

Applicability

All projects

Definition

Schedule of operation for interior lighting power used to adjust the energy use of lighting systems on an hourly basis to reflect time-dependent patterns of lighting usage

Units

Data structure: schedule, fractional

Input Restrictions

The lighting schedule is prescribed for California compliance. An appropriate schedule from Appendix 5.4B shall be used.

Standard Design

The non-regulated interior lighting in the standard design shall be the same as the proposed design.

Standard Design:

Existing Buildings

Same as proposed

 

Tailored Lighting General Illumination Height

Applicability

Spaces that have special tailored lighting power allowances

Definition

The illumination height is the vertical distance from the work plane to the centerline of the luminaire. This distance is used in the room cavity ratio (RCR) calculation which determines the allowed general lighting power density for a tailored lighting space.

Units

Ft

Input Restrictions

As designed

Standard Design

Same as proposed

The illumination height, H, is used to calculate the RCR and therefore the standard design general lighting power. See general lighting power for details.

Standard Design:

Existing Buildings

Same as proposed

 

Floor/Wall Display Mounting Height Above Floor

Applicability

Spaces that have wall display or floor display lighting and tailored lighting power allowances

Definition

The mounting height of wall display or floor display lighting above the floor

Units

List one of four choices:

1)   <10’-7”

2)   10’-7” – 14’-0”

3)   >14’-0” – 18’-0”

4)   > 18’-0”

Input Restrictions

As designed

Standard Design

As designed

The entered value maps to Table 140.6-E of the standards, that provides an adjustment multiplier for the tailored lighting wall power allowance in Table 140.6-D. The multiplier is 1.15 if the mounting height is 12 ft to 16 ft, and 1.30 if greater than 16 ft. The compliance software uses this adjustment multiplier to set the standard design lighting power.

Standard Design:

Existing Buildings

Same as proposed

 

Fixture Type

Applicability

All interior light fixtures

Definition

The type of lighting fixture, which is used to determine light heat gain distribution

Units

List: one of three choices:

1)   Recessed with lens

2)   Recessed/downlight

3)   Not in ceiling

Input Restrictions

As designed

Standard Design

Recessed/downlight

Standard Design:

Existing Buildings

Recessed/downlight

 

Luminaire Type

Applicability

All interior light fixtures

Definition

The type of lighting luminaire used to determine the light heat gain distribution

The dominant luminaire type determines the daylight dimming characteristics, when there is more than one type of luminaire in the space.

Units

List one of three choices:

a)   Linear fluorescent

b)   Compact fluorescent lamp

c)   Incandescent

d)   Light emitting diode

e)   Metal halide

f)    Mercury vapor

g)   High pressure sodium

Input Restrictions

As designed

Standard Design

Linear fluorescent

Standard Design:

Existing Buildings

Linear fluorescent

 

Light Heat Gain Distribution

Applicability

All projects

Definition

The distribution of the heat generated by the lighting system that is directed to the space, the plenum, the HVAC return air, or to other locations

This input is a function of the luminaire type and location. Luminaires recessed into a return air plenum contribute more of their heat to the plenum or the return air stream if the plenum is used for return air; while pendant mounted fixtures hanging in the space contribute more of their heat to the space. Common luminaire type/space configurations are listed in Table 3, Chapter 18, 2009 ASHRAE Handbook of Fundamentals, summarized in Table 7. Typically the data will be linked to list of common luminaire configurations similar to Table 7 so that the user chooses a luminaire type category and heat gain is automatically distributed to the appropriate locations.

Units

List (of luminaire types) or data structure consisting of a series of decimal fractions that assign heat gain to various locations

Input Restrictions

Heat gain distribution is fixed to Table 7 values based on the luminaire, fixture, and distribution type.

Where lighting fixtures having different heat venting characteristics are used within a single space, the wattage weighted average heat-to-return-air fraction shall be used.

Standard Design

The standard design shall use the values in Table 7 for recessed fluorescent luminaires without lens.

Standard Design:

Existing Buildings

Same as new construction

Table 7: Light Heat Gain Parameters for Typical Operating Conditions
Based on Table 3, Chapter 18, 2009 ASHRAE Handbook – Fundamentals

Fixture Type

Luminaire Type

Return Type

Space Fraction

Radiative Fraction

Recessed with Lens

Linear Fluorescent

Ducted/Direct

1.00

0.67

Plenum

 

0.45

0.67

Recessed/Downlight

Linear Fluorescent

Ducted/Direct

1.00

0.58

Plenum

0.69

0.58

CFL

Ducted/Direct

1.00

0.97

Plenum

0.20

0.97

Incandescent

Ducted/Direct

1.00

0.97

Plenum

0.75

0.97

LED

Ducted/Direct

1.00

0.97

Plenum

0.20

0.97

Metal Halide

Ducted/Direct

1.00

0.97

Plenum

0.75

0.97

Non In Ceiling

Linear Fluorescent

Ducted/Direct

1.00

0.54

Plenum

1.00

0.54

CFL

Ducted/Direct

1.00

0.54

Plenum

1.00

0.54

Incandescent

Ducted/Direct

1.00

0.54

Plenum

1.00

0.54

LED

Ducted/Direct

1.00

0.54

Plenum

1.00

0.54

Metal Halide

Ducted/Direct

1.00

0.54

Plenum

1.00

0.54

Mercury Vapor

Ducted/Direct

1.00

0.54

 

Plenum

1.00

0.54

High Pressure Sodium

Ducted/Direct

1.00

0.54

 

Plenum

1.00

0.54

In this table, the Space Fraction is the fraction of the lighting heat gain that goes to the space; the radiative fraction is the fraction of the heat gain to the space that is due to radiation, with the remaining heat gain to the space due to convection.

 

Lighting Power Adjustment Factors (PAF)

Applicability

All projects

Definition

Automatic controls that are not already required by the Energy Standards and which reduce lighting power more or less uniformly over the day can be modeled as power adjustment factors. Power adjustment factors represent the percent reduction in lighting power that will approximate the effect of the control. Models account for such controls by multiplying the controlled watts by (1–PAF).

Eligible California power adjustment factors are defined in Table 140.6-A. Reduction in lighting power using the PAF method can be used only for nonresidential controlled general lights. Only one PAF can be used for a qualifying lighting system unless multiple adjustment factors are allowed in Table 140.6-A of the standards. Controls for which PAFs are eligible are listed in Table 140.6-A of the standards and include:

a)   Occupancy Sensing Controls for qualifying enclosed spaces and open offices.

b)   Demand Response Controls – Demand responsive lighting control that reduces lighting power consumption in response to a demand response signal for qualifying building types.

c)   Institutional tuning – lighting tuned to not use more than 85 percent of rated power, per section 140.6 of the standards.

d)   Daylight dimming plus off controls – daylight dimming controls that automatically shut off luminaires when natural lighting provides an illuminance level of at least 150 percent of the space requirement,.

e)   Horizontal slats – interior or exterior horizontal slats on fenestration adjacent to daylit areas

f)    Light shelves – interior or exterior light shelves adjacent to daylit areas

Clerestories are modeled as Power Adjustment Factors, and are not modeled directly by compliance software. Compliance software shall have a means of disregarding daylight through clerestory windows when using the PAF.  If handled with a PAF, daylight controls in zones with clerestory windows should be disabled.

Units

List: eligible control types (see above) linked to PAFs

Input Restrictions

PAF shall be fixed for a given control and area type

Standard Design

PAF is zero

Standard Design:

Existing Buildings

PAF is zero

 

5.4.5    Daylighting Control

This group of building descriptors is applicable for spaces that have daylighting controls or daylighting control requirements.

California prescribes a modified version of the split flux daylighting methods to be used for compliance. This is an internal daylighting method because the calculations are automatically performed by the simulation engine. For top-lighted or sidelit daylit areas, California compliance prescribes an internal daylighting model consistent with the split flux algorithms used in many simulation programs. With this method the simulation model has the capability to model the daylighting contribution for each hour of the simulation and make an adjustment to the lighting power for each hour, taking into account factors such as daylighting availability, geometry of the space, daylighting aperture, control type, and the lighting system. The assumption is that the geometry of the space, the reflectance of surfaces, the size and configuration of the daylight apertures, and the light transmission of the glazing are taken from other building descriptors.

For daylight control using a simplified geometry approach, daylight control for both the primary daylit zone (mandatory) and secondary daylit zone (prescriptive) must be indicated on the compliance forms. If the simplified geometry approach is used and the visible transmittance of fenestration does not meet prescriptive requirements, the standard design lighting power is reduced by 20 percent as a penalty. See Interior Lighting.

 

Daylight Control Requirements

Applicability

All spaces with exterior fenestration

Definition

The extent of daylighting controls in skylit and sidelit areas of the space

Units

List

Input Restrictions

When the installed general lighting power in the primary daylit zone exceeds 120W, daylighting controls are required, per the Title 24 mandatory requirements.

Standard Design

For nonresidential spaces, when the installed general lighting power in the skylit or primary sidelit daylit zone exceeds 120W, daylighting controls are required in the primary daylit zone, per the Title 24 mandatory requirements.

For parking garages, when the installed general lighting power in the primary sidelit or secondary sidelit daylit zone exceeds 120W, daylighting controls are required, per the Title 24 mandatory requirements. Luminaires located in daylit transition zones or dedicated ramps are exempt from this requirement.

For nonresidential spaces, daylighting controls are specified when the installed general lighting power in the skylit, primary sidelit, or secondary sidelit daylit zone(s) exceeds 120W.

For parking garages, when the installed general lighting power in the primary sidelit or secondary sidelit daylit zone exceeds 120W, daylighting controls are required. Luminaires located in daylit transition zones or dedicated ramps are exempt from this requirement.

Standard Design:

Existing Buildings

When lighting systems in an existing altered building are not modified as part of the alteration, daylighting controls are the same as the proposed design.

When an alteration increases the area of a lighted space, increases lighting power in a space, or when luminaires are modified in a space where proposed design lighting power density is greater than 85 percent of the standard design LPD, daylighting control requirements are the same as for new construction.

 

Skylit, Primary, and Secondary Daylit Area

Applicability

All daylit spaces

Definition

The floor area that is daylit.

The skylit area is the portion of the floor area that gets daylighting from a skylight. Two types of sidelit daylit areas are recognized. The primary daylit area is the portion that is closest to the daylighting source and receives the most illumination. The secondary daylit area is an area farther from the daylighting source, which still receives useful daylight.

The primary daylit area for side lighting is a band near the window with a depth equal to the distance from the floor to the top of the window and width equal to window width plus 0.5 times window head height wide on each side of the window opening. The secondary daylit area for side lighting is a band beyond the primary daylit area that extends a distance double the distance from the floor to the top of the window and width equal to window width plus 0.5 times window head height wide on each side of the window opening. Area beyond a permanent obstruction taller than 6 feet should not be included in the primary and secondary daylight area calculation.

The skylit area is a band around the skylight well that has a depth equal to 70 percent of the ceiling height from the edge of the skylight well. The geometry of the skylit daylit area will be the same as the geometry of the skylight. Area beyond a permanent obstruction taller than 50 percent of the height of the skylight from the floor should not be included in the skylit area calculation.

Double counting due to overlaps is not permitted. If there is an overlap between secondary and primary or skylit areas, the effective daylit area used for determining reference position shall be the area minus the overlap.

Units

ft2

Input Restrictions

The daylit areas in a space are derived using other modeling inputs like dimensions of the fenestration and ceiling height of the space.

Standard Design

The daylit areas in the standard design are derived from other modeling inputs, including the dimensions of the fenestration and ceiling height of the space. Daylit area calculation in the standard design is done after window to wall ratio and skylight to roof ratio rules in Section 5.5.7 of this manual are applied.

Standard Design:

Existing Buildings

Same as new construction when skylights are added/replaced and general lighting altered

 

Installed General Lighting Power in the Primary and Skylit Daylit Zone

Applicability

All spaces

Definition

The installed lighting power of general lighting in the primary and skylit daylit zone.

The primary and skylit daylit zone shall be defined on the plans, and be consistent with the definition of the primary and skylit daylit zone in the standards. Note that a separate building descriptor, fraction of controlled lighting, defines the fraction of the lighting power in the space that is controlled by daylighting.

Units

Watts

Input Restrictions

As designed

Standard Design

The installed lighting power for the standard design is the product of the primary daylit area and the LPD for general lighting in the space.

Standard Design:

Existing Buildings

Same as new construction when skylights are added/replaced and general lights are altered

 

Installed General Lighting Power in the Secondary Daylit Zone

Applicability

All spaces

Definition

The installed lighting power of general lighting in the secondary daylit zone.

The secondary daylit zone shall be defined on the plans and be consistent with the definition of the secondary daylit zone in the standards. Note that a separate building descriptor, fraction of controlled lighting, defines the fraction of the lighting power in the space that is controlled by daylighting.

Units

W

Input Restrictions

As designed

Standard Design

The installed lighting power for the standard design is the product of the secondary daylit area and the LPD for general lighting in the space.

Standard Design:

Existing Buildings

Same as new construction when skylights are added/replaced and general lights are altered

 

Reference Position for Illuminance Calculations

Applicability

All spaces or thermal zones, depending on which object is the primary container for daylighting controls

Definition

The position of the two daylight reference points within the daylit space.

Lighting controls are simulated so that the illuminance at the reference position is always maintained at or above the illuminance setpoint. For step switching controls, the combined daylight illuminance plus uncontrolled electric light illuminance at the reference position must be greater than the setpoint illuminance before the controlled lighting can be dimmed or tuned off for stepped controls. Similarly, dimming controls will be dimmed so that the combination of the daylight illuminance plus the controlled lighting illuminance is equal to the setpoint illuminance.

Preliminary reference points for primary and secondary daylit areas are located at the farthest end of the daylit area aligned with the center of  each window. For skylit area, the preliminary reference point is located at the center of the edge of the skylit area closest to the centroid of the space. In each case, the Z – coordinate of the reference position (elevation) shall be located 2.5 feet above the floor.

Up to two final reference positions can be selected from among the preliminary reference positions identified in for each space.

Units

Data structure

Input Restrictions

The user does not specify the reference position locations; reference positions are automatically calculated by the compliance software based on the procedure outlined below. Preliminary reference positions are each assigned a relative daylight potential (RDP) which estimates the available illuminance at each position, and the final reference position selection is made based on the RDP.

RDP: An estimate of daylight potential at a specific reference position. This is NOT used directly in the energy simulation, but it used to determine precedence for selecting the final reference points. The relative daylight potential is calculated as a function of effective aperture, azimuth, illuminance setpoint and the type (skylit, primary sidelit, or secondary sidelit) of the associated daylit zone. RDP is defined as:

 

Where C1, C2 and C3 are selected from the following table.

 

Skylit Daylit Zones

Primary Sidelit Daylit Zones

Secondary Sidelit Daylit Zones

Illuminance Setpoint

C1

C2

C3

C1

C2

C3

C1

C2

C3

200 lux

3927

0

3051

1805

-0.40

3506

7044

-3.32

1167

≤ 1000 lux

12046

0

-421

6897

-7.22

475

1512

-2.88

-22

> 1000 lux

5900

0

-516

884

-5.85

823

212

-0.93

57

Illuminance Setpoint: This is defined by the user, and is entered by the user, subject to the limits specified in Appendix 5.4A, determined from the space type.

Source Orientation (SO):  The angle of the outward facing normal of the daylight source’s parent surface projected onto a horizontal plane, expressed as degrees from south. This is not a user input but is calculated from the geometry of the parent surface. For skylights, the source orientation is not applicable. For vertical fenestration, it is defined:

 

Where: Azimuth is defined as the azimuth of the parent object containing the fenestration associated with the preliminary reference point.

Effective Aperture (EA): For this calculation, effective aperture represents the effectiveness of all sources which illuminate a specific reference position in contributing to the daylight available to the associated daylit zone. In cases where daylit zones from multiple fenestration objects intersect, the effective aperture of an individual daylit zone is adjusted to account for those intersections according to the following rules:

      For skylit and primary sidelit daylit zones, intersections with other skylit or primary sidelit daylit zones are considered.

      For secondary sidelit daylit zones, intersections with any toplit or sidelit (primary or secondary) daylit zones are considered.

Effective aperture is defined as follows:

Where:

EAdz

Is the combined effective aperture of all daylight sources illuminating a specific daylit zone.

VTfdz

Is the user specified visible transmittance of the fenestration object directly associated with the daylit zone.

Afdz

Is the area of the fenestration object directly associated with the daylit zone.

VTi

Is the user specified visible transmittance of the fenestration object associated with each intersecting daylit zone.

Ai

Is the area of the fenestration object directly associated with each intersecting daylit zone.

Fi

Is the fraction of intersecting area between the daylit zone in question and each intersecting daylit zone:

Adzi

Is the area of each intersecting daylit zone (including area that might fall outside a space or exterior boundary).

Adz

Is the area of the daylit zone (including area that might fall outside a space or exterior boundary).

First Reference Position: Select the preliminary reference point with the highest relative daylight potential (RDP) from among all preliminary reference points located within either top or primary sidelit daylit zones. If multiple reference points have identical RDPs, select the reference point geometrically closest to the centroid of the space.

Second Reference Position: Select the preliminary reference point with the highest RDP from amongst all remaining preliminary reference points located within either top or primary sidelit daylit zones. If multiple reference points have identical RDPs, select the reference point geometrically closest to the centroid of the space.

Standard Design

Reference positions for the standard design shall be selected using the same procedure as those selected for the proposed design.

Standard Design:

Existing Buildings

Additions or alternations of lighting in spaces trigger the daylighting control requirements whenever the total installed lighting in the daylit zone is 120 W or greater, and the reference positions shall be determined in the same manner as with new construction. This only applies when alterations or additions to the lighting in an existing building trigger daylighting control requirements.

 

Illumination Adjustment Factor

Applicability

All Daylighted Spaces

Definition

Recent studies have shown that the split flux interreflection component model used in many simulation programs overestimates the energy savings due to daylighting, particularly deep in the space. A set of two adjustment factors is provided, one for the primary daylit zone and one for the secondary daylit zone.

For simulation purposes, the input daylight illuminance setpoint will be modified by the illuminance adjustment factor as follows:

Units

Unitless

Input Restrictions

Prescribed values for space type in Appendix 5.4A

Standard Design

The standard design illumination adjustment factors shall match the proposed

Standard Design:

Existing Buildings

Same as new construction when skylights are added/replaced and general light is altered.

 

Fraction of Controlled Lighting

Applicability

Daylighted Spaces

Definition

The fraction of the general lighting power in the primary and skylit daylit zone, or secondary sidelit daylit zone that is controlled by daylighting controls.

Units

Numeric: fraction for primary and skylit daylit zone, and fraction for secondary zone

Input Restrictions

As designed for secondary daylit areas. If the proposed design has no daylight controls in the secondary daylit area the value is set to 0 for the general lights in the secondary daylit area. Primary and skylit daylit area fraction of controlled general lighting shall be as designed when the daylight control requirements building descriptor indicates that they are not required, and shall be 1 when controls are required.

Standard Design

When daylight controls are required according to the daylight control requirements building descriptor in either the primary daylit and skylit zone, or the secondary daylit zone, or both, the fraction of controlled lighting shall be 1.

Standard Design:

Existing Buildings

Same as for new construction when skylights are added/replaced, and general light is altered.

 

Daylighting Control Type

Applicability

Daylighted Spaces

Definition

The type of control that is used to control the electric lighting in response to daylight available at the reference point.

Options:

      Stepped switching controls vary the electric input power and lighting output power in discrete equally spaced steps. At each step, the fraction of light output is equal to the fraction of rated power.

      Continuous dimming controls have a fraction to rated power to fraction of rated output that is a linear interpolation of the minimum power fraction at the minimum diming light fraction to rated power (power fraction = 1.0) at full light output. See Figure 8: Example Continuous Dimming Control

Continuous dimming + off controls are the same as continuous dimming controls except that these controls can turn all the way off when none of the controlled light output is needed. See the example control chart below.

 

Figure 8: Example Continuous Dimming Control

Source: NORESCO for California Energy Commission

Units

List (see above)

Input Restrictions

As designed

Standard Design

Standard design uses continuous daylighting control.

Standard Design:

Existing Buildings

Same as for new construction when skylights are added/replaced, and general light is altered.

 

Minimum Dimming Power Fraction

Applicability

Daylit spaces

Definition

The minimum power fraction when controlled lighting is fully dimmed. Minimum power fraction = minimum power / full rated power.

Units

Numeric: fraction

Input Restrictions

As designed, specified from luminaire type (not a user input)

Standard Design

Standard design uses continuous dimming control with a minimum dimming power fraction from Table 8: Standard Design Power/Light Output Fraction. Where the controlled luminaire type, input by the user, determines the minimum dimming power fraction.

Standard Design: Existing Buildings

Same as for new construction when skylights are added/replaced, and general light is altered.

 

Minimum Dimming Light Fraction

Applicability

Daylighting and dimming controls

Definition

The minimum light output when controlled lighting is fully dimmed. Minimum light fraction = minimum light output / rated light output.

Units

Numeric: fraction

Input Restrictions

As designed

Standard Design

Standard design uses continuous dimming control with a minimum dimming light fraction from Table 8: Standard Design Power/Light Output Fraction. Where the controlled luminaire type, input by the user, determines the minimum dimming power fraction.

Standard Design:

Existing Buildings

Same as for new construction when skylights are added/replaced, and general light is altered.

 

Table 8: Standard Design Power/Light Output Fraction

Light Source

Power Fraction

Light Output Fraction

LED

0.1

0.1

Linear Fluorescent

0.2

0.2

Mercury Vapor

0.3

0.2

Metal Halide

0.45

0.2

High Pressure Sodium

0.4

0.2

CFL

0.4

0.2

Incandescent

0.5

0.2

 

5.4.6    Receptacle Loads

Receptacle loads contribute to heat gains in spaces and directly use energy.

Receptacle Power

Applicability

All building projects

Definition

Receptacle power is power for typical general service loads in the building. Receptacle power includes equipment loads normally served through electrical receptacles, such as office equipment and printers, but does not include either task lighting or equipment used for HVAC purposes. Receptacle power values are slightly higher than the largest hourly receptacle load that is actually modeled because the receptacle power values are modified by the receptacle schedule, which approaches but does not exceed 1.0.

Units

Total power (W) or the space power density (W/ft²)

Compliance software shall also use the following prescribed values to specify the latent heat gain fraction and the radiative/convective heat gain split.

For software that specifies the fraction of the heat gain that is lost from the space, this fraction shall be prescribed at 0.

Heat Gain Fractions:

 

Radiative

Latent

Convective

Receptacle Power

0.20

0.00

0.80

Gas Equipment Power

0.15

0.00

0.00

 

Input Restrictions

Prescribed to values from Appendix 5.4A

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as for new construction

 

Receptacle Schedule

Applicability

All projects

Definition

Schedule for receptacle power loads used to adjust the intensity on an hourly basis to reflect time-dependent patterns of usage.

Units

Data structure: schedule, fraction

Input Restrictions

Prescribed to schedule in Appendix 5.4A

Standard Design

Same as proposed

Standard Design:

Existing Buildings

Same as for new construction

 

5.4.7    Commercial Refrigeration Equipment

Commercial refrigeration equipment includes the following:

      Walk-in refrigerators

      Walk-in freezers

      Refrigerated casework

Refrigeration equipment is modeled as neutral plug loads, with standard design power matching the proposed design.

 

Refrigeration Modeling Method

Applicability

All buildings that have commercial refrigeration for cold storage or display

Definition

The method used to estimate refrigeration energy and to model the thermal interaction with the space where casework is located. Two methods are included in this manual:

      Title 24 defaults. With this method, the power density values provided in Appendix 5.4A are used; schedules are assumed to be continuous operation.

 

Units

List (see above)

Input Restrictions

The Title 24 defaults shall be used.

Standard Design

Title 24 defaults

Standard Design:

Existing Buildings

Same as for new construction

 

Refrigeration Power

Applicability

All buildings that have commercial refrigeration for cold storage or display

Definition

Commercial refrigeration power is the average power for all commercial refrigeration equipment, assuming constant year-round operation. Equipment includes walk-in refrigerators and freezers, open refrigerated casework, and closed refrigerated casework. It does not include residential type refrigerators used in kitchenettes or refrigerated vending machines. These are covered under receptacle power.

Units

W/ft2

Input Restrictions

With the Title 24 defaults method, the values in Appendix 5.4A are prescribed. These values are multiplied times the floor area of the rated building to estimate the refrigeration power.

Standard Design

Refrigeration power is the same as the proposed design when the Title 24 defaults are used.

Standard Design:

Existing Buildings

Same as for new construction

 

5.4.8    Elevators, Escalators and Moving Walkways

Elevators, escalators and moving walkways account for 3 percent to 5 percent of electric energy use in buildings. Buildings up to about five to seven stories typically use hydraulic elevators because of their lower initial cost. Mid-rise buildings commonly use traction elevators with geared motors, while high-rise buildings typically use gearless systems where the motor directly drives the sheave. The energy-using components include the motors and controls as well as the lighting and ventilation systems for the cabs.

Elevators, escalators, and moving walkways are modeled as a plug loads, with the standard design power matching the proposed design.

 

Elevator/Escalator Power

Applicability

All buildings that have commercial elevators, escalators, or moving walkways

Definition

The power for elevators, escalators and moving walkways are modeled as plug loads.

Units

W/unit

Input Restrictions

The power values are prescribed for the proposed design.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Elevator/Escalator Schedule

Applicability

All buildings that have commercial elevators, escalators, or moving walkways

Definition

The schedule of operation for elevators, escalators, and moving walkways. This is used to convert elevator/escalator power to energy use.

Units

Data structure: schedule, state

Input Restrictions

The operating schedule is prescribed and indicated in Appendix 5.4B.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

5.4.9    Process, Gas

Commercial gas equipment includes the following:

      Ovens

      Fryers

      Grills

      Other equipment

 

The majority of gas equipment is located in the space and may contribute both sensible and latent heat. Gas equipment is modeled by specifying the rate of peak gas consumption and a fractional schedule that is prescribed in Appendix 5.4B. The procedure consists of prescribed power and energy values for use with both the proposed and standard design buildings. No credit for commercial gas energy efficiency features is offered.

The prescribed values are provided in Appendix 5.4A. Schedules are defaulted to be continuous operation.

 

Gas Equipment Power

Applicability

All buildings that have commercial gas equipment

Definition

Commercial gas power is the average power for all commercial gas equipment, assuming constant year-round operation.

Units

Btu/h-ft²

Compliance software shall also use the following prescribed values to specify the latent heat gain fraction and the radiative/convective heat gain split.

For software that specifies the fraction of the heat gain that is lost from the space, this fraction shall be prescribed at 0.

Gas Equipment Power Heat Gain Fractions:

Radiative = 0.15, Latent = 0, Convective = 0

Input Restrictions

The values in Appendix 5.4A are prescribed. However, these values may be overridden with a “0” value for buildings that are designed to use only electricity as the source.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Gas Equipment Schedule

Applicability

All buildings that have commercial gas equipment

Definition

The schedule of operation for commercial gas equipment. This is used to convert gas power to energy use.

Units

Data structure: schedule, fractional

Input Restrictions

Continuous operation is prescribed.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Gas Equipment Location

Applicability

All buildings that have commercial gas equipment

Definition

The assumed location of the gas equipment for modeling purposes.

Units

List (in the space or external)

Input Restrictions

As designed.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Radiation Factor

Applicability

Gas appliances located in the space

Definition

The fraction of heat gain to appliance energy use

Units

Fraction

Input Restrictions

Default value is 0.15. Other values can be used when a detailed inventory of equipment is known. The override value shall be based on data in Table 5C, Chapter 18, ASHRAE HOF, 2009, or similar tested information from the manufacturer.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Usage Factor

Applicability

Gas appliances located in the space

Definition

A duty cycle or usage factor to appliance energy use.

The radiation factor and usage factor are used together to determine the sensible heat gain to the space:

Qsens = Qinput x FU x FR

Where Qinput is the heat input of the equipment in Btu/h or Btu/h-ft2,

FU is the usage factor and

FR is the radiation factor

Units

Fraction

Input Restrictions

Default value is 0.70. Other values can be used when a detailed inventory of equipment is known. The override value shall be based on data in Table 5C, Chapter 18, ASHRAE HOF, 2009, or similar tested information from the manufacturer.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Gas Process Loads

Applicability

Spaces with process loads

Definition

Process load is the gas energy consumption in the conditioned space of a building resulting from an activity or treatment not related to the space conditioning, lighting, service water heating, or ventilating of a building as it relates to human occupancy. Process load may include sensible and/or latent components. 

Compliance software shall model and simulate process loads only if the amount of the process energy and the location and type of process equipment are specified in the construction documents. This information shall correspond to specific special equipment shown on the building plans and detailed in the specifications.

Units

Data structure: sensible (Btu/h), latent (Btu/h)

Input Restrictions

Compliance software shall receive input for sensible and/or latent process load for each zone in the proposed design. The process load input shall include the amount of the process load (Btu/h-ft2) and the thermal zone where the process equipment is located. The modeled information shall be consistent with the plans and specifications of the building.

Standard Design

The standard design shall use the same gas process loads and sensible and latent contribution and radiative/convective split for each zone as the proposed design.

Standard Design:

Existing Buildings

Same as new construction

 

Electric Process Loads

Applicability

Spaces with electric process loads

Definition

Process load is the electrical energy consumption in the conditioned space of a building resulting from an activity or treatment not related to the space conditioning, lighting, service water heating, or ventilating of a building as it relates to human occupancy. 

Data center loads including transformers, uninterruptible power supplies, power delivery units, server fans and power supplies are considered receptacle loads, not process loads, and the equipment schedules are given in Appendix 5.4B.

Compliance software shall model and simulate process loads only if the amount of the process energy and the location and type of process equipment are specified in the construction documents. This information shall correspond to specific special equipment shown on the building plans and detailed in the specifications. The compliance software shall inform the user that the software will output process loads including the types of process equipment and locations on the compliance forms.

Units

Data structure: load (kW) 

For electric process loads, the radiative fraction shall be defaulted to 0.2 and the convective fraction shall be defaulted to 0.8 by the compliance software. The user may enter other values for the radiative/convective split, but the compliance software shall verify that the values add to 1.

Input Restrictions

Compliance software shall receive input for sensible and/or latent process load for each zone in the proposed design. The process load input shall include the amount of the process load (Btu/h-ft2) and the thermal zone where the process equipment is located. The modeled information shall be consistent with the plans and specifications of the building.

Standard Design

The standard design shall use the same process loads and radiative/convective split for each zone as the proposed design.

Standard Design:

Existing Buildings

Same as new construction

 

Gas Process Load Schedule

Applicability

All buildings that have commercial gas equipment

Definition

The schedule of process load operation. Used to convert gas power to energy use.

Units

Data structure: schedule, fractional

Input Restrictions

As designed.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Electric Process Load Schedule

Applicability

All buildings that have commercial gas equipment

Definition

The schedule of electric process load operation.

Units

Data structure: schedule, fractional

Input Restrictions

As designed.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

5.4.10  Water Heating Use

This section defines the water heating load (use rate) and system requirements on a space level.

 

Space Water Heating Use Rate

Applicability

All spaces

Definition

The water heating use rate for a space in a building

Units

Gal/h

Input Restrictions

The values in Appendix 5.4A are prescribed.

Standard Design

Same as the proposed design

Standard Design:

Existing Buildings

Not applicable

 

Space Water Heating Fuel Type

Applicability

All spaces

Definition

A mapping that defines the standard design water heating fuel type for a space

Units

List;  gas or electric

Input Restrictions

As designed

Standard Design

Prescribed from the table in Appendix 5.4A

Standard Design:

Existing Buildings

Not applicable