SECTION 110.2 – MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

 

 

Certification by Manufacturers. Any space-conditioning equipment 'listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.

(a)        Efficiency.

 

 

Equipment shall meet the applicable efficiency requirements in TABLE 110.2-A through TABLE 110.2-K subject to the following:

1.   If more than one efficiency standard is 'listed for any equipment in TABLE 110.2-A through TABLE 110.2-K, the equipment shall meet all the applicable standards that are 'listed; and

2.   If more than one test method is 'listed in TABLE 110.2-A through TABLE 110.2-K, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and

3.   Where equipment serves more than one function, it shall comply with the efficiency standards applicable to each function; and

4.   Where a requirement is for equipment rated at its "maximum rated capacity" or "minimum rated capacity," the capacity shall be as provided for and allowed by the controls, during steady-state operation.

EXCEPTION 1 to Section 110.2(a): Water-cooled centrifugal water-chilling packages that are not designed for operation at ANSI/AHRI Standard 550/590 test conditions of 44°F leaving chilled water temperature and 85°F entering condenser water temperature with 3 gallons per minute per ton condenser water flow shall have a maximum full load kW/ton and NPLV ratings adjusted using the following equation:

Adjusted maximum full-load kW/ton rating = (full-load kW/ton from TABLE 110.2-D) / Kadj

Adjusted maximum NPLV rating = (IPLV from TABLE 110.2-D) / Kadj

Where:

Kadj = (A) x (B)

A = 0.00000014592 x (LIFT)4 – 0.0000346496 x (LIFT)3+0.00314196 x (LIFT)2 – 0.147199 x (LIFT) + 3.9302

LIFT = LvgCond – LvgEvap (°F)

LvgCond = Full-load leaving condenser fluid temperature (°F)

LvgEvap = Full-load leaving evaporator fluid temperature (°F)

B = (0.0015 x LvgEvap) + 0.934

The adjusted full-load and NPLV values are only applicable for centrifugal chillers meeting all of the following full-load design ranges:

•     Minimum Leaving Evaporator Fluid Temperature: 36°F

•     Maximum Leaving Condenser Fluid Temperature: 115°F

•     LIFT ≥ 20°F and ≤ 80°F

Centrifugal chillers designed to operate outside of these ranges are not covered by this exception.

EXCEPTION 2 to Section 110.2(a): Positive displacement (air-cooled and water-cooled) chillers with a leaving evaporator fluid temperature higher than 32°F shall show compliance with TABLE 110.2-D when tested or certified with water at standard rating conditions, per the referenced test procedure.

EXCEPTION 3 to Section 110.2(a): Equipment primarily serving refrigerated warehouses or commercial refrigeration.

(b)       Controls for Heat Pumps with Supplementary Electric Resistance Heaters.

 

 

Heat pumps with supplementary electric resistance heaters shall have controls:

1.   That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and

2.   In which the cut-on temperature for compression heating is higher than the cut-on temperature for supplementary heating, and the cut-off temperature for compression heating is higher than the cut-off temperature for supplementary heating.

EXCEPTION 1 to Section 110.2(b): The controls may allow supplementary heater operation during:

A.   Defrost; and

B.   Transient periods such as start-ups and following room thermostat setpoint advance, if the controls provide preferential rate control, intelligent recovery, staging, ramping or another control mechanism designed to preclude the unnecessary operation of supplementary heating.

EXCEPTION 2 to Section 110.2(b): Room air-conditioner heat pumps.

(c)        Thermostats.

 

 

All heating or cooling systems not controlled by a central energy management control system (EMCS) shall have a setback thermostat.

1.   Setback Capabilities. All thermostats shall have a clock mechanism that allows the building occupant to program the temperature setpoints for at least four periods within 24 hours. Thermostats for heat pumps shall meet the requirements of Section 110.2(b).

EXCEPTION to Section 110.2(c): Gravity gas wall heaters, gravity floor heaters, gravity room heaters, non-central electric heaters, fireplaces or decorative gas appliances, wood stoves, room air conditioners, and room air-conditioner heat pumps.

(d)       Gas-Fired and Oil-Fired Furnace Standby Loss Controls.

 

 

Gas-fired and oil-fired forced air furnaces with input ratings ≥225,000 Btu/hr shall also have an intermittent ignition or interrupted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥225,000 Btu/h, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.

(e)        Open and Closed Circuit Cooling Towers.

 

 

All open and closed circuit cooling tower installations shall comply with the following:

1.   Be equipped with Conductivity or Flow-based Controls that maximize cycles of concentration based on local water quality conditions. Controls shall automate system bleed and chemical feed based on conductivity, or in proportion to metered makeup volume, metered bleed volume, recirculating pump run time, or bleed time. Conductivity controllers shall be installed in accordance with manufacturer’s specifications in order to maximize accuracy.

2.   Documentation of Maximum Achievable Cycles of Concentration. Building owners shall document the maximum cycles of concentration based on local water supply as reported annually by the local water supplier, and using the calculator approved by the Energy Commission. The calculator is intended to determine maximum cycles based on a Langelier Saturation Index (LSI) of 2.5 or less. Building owner shall document maximum cycles of concentration on the mechanical compliance form which shall be reviewed and signed by the Professional Engineer (P.E.) of Record.

3.   Be equipped with a Flow Meter with an analog output for flow either hardwired or available through a gateway on the makeup water line.

4.   Be equipped with an Overflow Alarm to prevent overflow of the sump in case of makeup water valve failure. Overflow alarm shall send an audible signal or provide an alert via the Energy Management Control System to the tower operator in case of sump overflow.

5.   Be equipped with Efficient Drift Eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counter-flow towers and 0.005 percent for cross-flow towers.

EXCEPTION to Section 110.2(e): Towers with rated capacity < 150 tons.

(f)        Low Leakage Air-Handling Units.

 

 

To qualify as a low leakage air-handling unit for use for meeting the requirements for applicable low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Sections 150.1(b) and 140.1, the manufacturer shall certify to the Energy Commission that the air-handling unit meets the specifications in Reference Joint Appendix JA9.

TABLE 110.2-A AIR CONDITIONERS AND CONDENSING UNITS –
MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type

Size Category

Efficiency a,b

Test Procedurec

Air conditioners,

air cooled

both split system

and single package

≥ 65,000 Btu/h and

< 135,000 Btu/h

11.2 EER

12.9 IEER

 

ANSI/AHRI 340/360

 

≥ 135,000 Btu/h and

< 240,000 Btu/h

11.0 EER

12.4 IEER

ANSI/AHRI 340/360

≥ 240,000 Btu/h and

< 760,000 Btu/h

10.0 EER

11.6 IEER

≥ 760,000 Btu/h

9.7 EER

11.2 IEER

Air conditioners,

water cooled

≥ 65,000 Btu/h and

< 135,000 Btu/h

12.1 EER

13.9 IEER

ANSI/AHRI 340/360

≥135,000 Btu/h and

< 240,000 Btu/h

12.5 EER

13.9 IEER

ANSI/AHRI 340/360

≥240,000 Btu/h and

< 760,000 Btu/h

12.4 EER

13.6 IEER

ANSI/AHRI 340/360

≥ 760,000 Btu/h

12.2EER

13.5 IEER

ANSI/AHRI 340/360

Air conditioners,  evaporatively cooled

≥65,000 Btu/h and

< 135,000 Btu/h

12.1 EERb

12.3 IEERb

ANSI/AHRI 340/360

≥ 135,000 Btu/h and

< 240,000 Btu/h

12.0 EERb

12.2 IEERb

ANSI/AHRI 340/360

≥240,000 Btu/h and

< 760,000 Btu/h

11.9 EERb

12.1 IEERb

ANSI/AHRI 340/360

≥ 760,000 Btu/h

11.7 EERb

11.9 IEERb

ANSI/AHRI 340/360

Condensing units,

air cooled

≥ 135,000 Btu/h

10.5 EER

11.8 IEER

ANSI/AHRI 365

 

Condensing units,

water cooled

≥ 135,000 Btu/h

13.5 EER

14.0 IEER

Condensing units, evaporatively cooled

≥ 135,000 Btu/h

13.5 EER

14.0 IEER

a IEERs are only applicable to equipment with capacity control as specified by ANSI/AHRI 340/360 test procedures

b Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat.

c Applicable test procedure and reference year are provided under the definitions.

TABLE 110.2-B HEAT PUMPS,
MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type

Size Category

Efficiency a, b

Test Procedurec

Air Cooled

(Cooling Mode)

both split system and single package

≥ 65,000 Btu/h and  
< 135,000 Btu/h

 

11.0 EER

12.2 IEER

ANSI/AHRI 340/360

 

≥ 135,000 Btu/h and

< 240,000 Btu/h

 

10.6 EER

11.6 IEER

≥  240,000 Btu/h

 

9.5 EER

10.6 IEER

Water source (cooling mode)

≥ 65,000 Btu/h and  
< 135,000 Btu/h

86ºF entering water

13.0 EER

ISO-13256-1

Groundwater source (cooling mode)

< 135,000 Btu/h

59ºF entering water

18.0 EER

ISO-13256-1

Ground source (cooling mode)

< 135,000 Btu/h

77ºF entering water

14.1 EER

ISO-13256-1

Water source water-to-water (cooling mode)

< 135,000 Btu/h

86ºF entering water

10.6 EER

ISO-13256-2

Groundwater source water-to-water
(cooling mode)

< 135,000 Btu/h

59ºF entering water

16.3 EER

ISO-13256-1

Ground source brine-to-water (cooling mode)

< 135,000 Btu/h

77ºF entering water

12.1 EER

ISO-13256-2

Air Cooled (Heating Mode)
Split system and single package

≥ 65,000 Btu/h and
< 135,000 Btu/h
(cooling capacity)

47° F db/43° F wb  
outdoor air

3.3 COP

ANSI/AHRI 340/360

≥ 135,000 Btu/h and
< 240,000 Btu/h

17° F db/15° F wb  
outdoor air

2.25 COP

 

Groundwater source (heating mode)

≥ 135,000 Btu/h
(cooling capacity)

47° F db/43° F wb  
outdoor air

3.2 COP

ISO-13256-1

Ground source (heating mode)

< 135,000 Btu/h
(cooling capacity)

17° F db/15° F wb  
outdoor air

2.05 COP

ISO-13256-1

CONTINUED: TABLE 110.2-B HEAT PUMPS, MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type

Size Category

Subcategory or Rating Condition

Efficiency a

Test Procedurec

Water source

(heating mode)

< 135,000 Btu/h

(cooling capacity)

68ºF entering water

4.3 COP

ISO-13256-1

≥ 135,000 Btu/h and

< 240,000 Btu/h

68ºF entering water

2.90 COP

Groundwater source (heating mode)

< 135,000 Btu/h

(cooling capacity)

50ºF entering water

3.7 COP

ISO-13256-1

Ground source

(heating mode)

< 135,000 Btu/h

(cooling capacity)

32ºF entering water

3.2 COP

ISO-13256-1

Water source water-to-water

(heating mode)

< 135,000 Btu/h

(cooling capacity)

68ºF entering water

3.7 COP

ISO-13256-2

Groundwater source water-to-water

(heating mode)

< 135,000 Btu/h

(cooling capacity)

50ºF entering water

3.1 COP

ISO-13256-2

Ground source brine-to-water

(heating mode)

 

< 135,000 Btu/h

(cooling capacity)

32ºF entering water

2.5 COP

ISO-13256-2

a IEERs are only applicable to equipment with capacity control as as specified by ANSI/AHRI 340/360 test procedures.

b Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat.

c Applicable test procedure and reference year are provided under the definitions.

 

TABLE 110.2-C  AIR-COOLED GAS-ENGINE HEAT PUMPS

Equipment Type

Size Category

Subcategory or Rating Condition

Efficiency

Test Procedurea

Air-Cooled Gas-Engine 'Heat Pump (Cooling Mode)

All Capacities

95° F db
Outdoor Air

0.60 COP

ANSI Z21.40.4A

Air-Cooled Gas-Engine 'Heat Pump (Heating Mode)

All Capacities

47° F db/43° F wb
Outdoor Air

0.72 COP

ANSI Z21.40.4A

a  Applicable test procedure and reference year are provided under the definitions.

 

TABLE 110.2-D WATER CHILLING PACKAGES
MINIMUM EFFICIENCY REQUIREMENTS a,b

Equipment Type

Size Category

Path A Efficiency a,b

Path B Efficiency a,b

Test Procedure c

Air Cooled, With Condenser Electrically Operated

< 150 Tons

≥ 10.100 EER

≥ 13.700 IPLV

≥ 9.700 EER

≥15.800 IPLV

AHRI 550/590

 

≥ 150 Tons

≥  10.100 EER
≥ 14.000 IPLV

≥ 9.700 EER

≥16.100 IPLV

Air Cooled,
Without Condenser
Electrically Operated

All Capacities

Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements..

Water Cooled, Electrically Operated, Reciprocating

All Capacities

Reciprocating units must comply with the water-cooled positive displacement efficiency requirements

AHRI 550/590

Water Cooled,
Electrically Operated Positive Displacement

< 75 Tons

≤0.750 kW/ton

≤ 0.600 IPLV

≤ 0.780 kW/ton

≤ 0.500 IPLV

AHRI 550/590

≥ 75 tons and < 150 tons

≤ 0.720 kW/ton

0.560 IPLV

≤ 0.750 kW/ton

≤ 0.490 IPLV

≥ 150 tons and < 300 tons

≤ 0.660 kW/ton

≤ 0.540 IPLV

≤ 0.680 kW/ton

≤ 0.440 IPLV

≥ 300 tons and < 600 tons

≤ 0.610 kW/ton

≤ 0.520 IPLV

≤ 0.625 kW/ton

≤ 0.410 IPLV

> 600 tons

≤ 0.560 kW/ton

≤ 0.500 IPLV

≤ 0.585 kW/ton

≤ 0.380 IPLV

Water Cooled, Electrically Operated, Centrifugal

< 150 Tons

0.610 kW/ton

≤ 0.550 IPLV

≤ 0.695 kW/ton

≤ 0.440 IPLV

≥ 150 tons and < 300 tons

≤ 0.610 kW/ton

≤ 0.550 IPLV

≤ 0.635 kW/ton

≤ 0.400 IPLV

≥ 300 tons and < 400 tons

≤ 0.560 kW/ton

≤ 0.520 IPLV

≤ 0.595 kW/ton

≤ 0.390 IPLV

≥ 400 tons and < 600 tons

≤ 0. 560 kW/ton

≤ 0. 500 IPLV

≤ 0. 585 kW/ton

≤ 0. 380 IPLV

≥ 600 tons

≤ 0.560 kW/ton

≤ 0.500 IPLV

≤ 0.585 kW/ton

≤ 0.380 IPLV

Air Cooled Absorption,

Single Effect

All Capacities

≥0.600 COP

N.A. d

ANSI/AHRI 560

 

Water Cooled Absorption, Single Effect

All Capacities

≥ 0.700 COP

N.A. d

Absorption Double Effect, Indirect-Fired

All Capacities

≥ 1.000 COP

≥ 1.050 IPLV

N.A. d

Absorption Double Effect, Direct-Fired

All Capacities

≥ 1.000 COP

≥1.000 IPLV

N.A. d

Water Cooled Gas Engine Driven Chiller

All Capacities

1.2 COP
2.0 IPLV

N.A. d

ANSI Z21.40.4A

No requirements for:
•  Centrifugal chillers with design leaving evaporator temperature < 36°F; or
•  Positive displacement chillers with design leaving fluid temperature ≤ 32°F;
• or Absorption chillers with design leaving fluid temperature < 40°F

Must meet the minimum requirements of Path A or Path B. However,
 both the full load (COP) and IPLV must be met to fulfill the requirements
 of the applicable Path.

See Section 100.1 for definitions

NA means not applicable

 

TABLE 110.2-E  PACKAGED TERMINAL AIR CONDITIONERS AND PACKAGED
TERMINAL HEAT PUMPS – MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type

Size Category (Input)

Subcategory or Rating Condition

Efficiency

Test Procedure c

PTAC (Cooling mode)

Newly constructed or newly conditioned buildings or additions

All Capacities

95°F db Outdoor Air

14.0 - (0.300 x Cap/1000) a EER

ANSI/
AHRI/
CSA 310/380

PTAC (Cooling mode) Replacements b

All Capacities

95°F db Outdoor Air

10.9 - (0.213 x Cap/1000) a EER

PTHP  (Cooling mode) Newly constructed or newly conditioned buildings or additions

All Capacities

95°F db Outdoor Air

14.0 - (0.300 x Cap/1000) a EER

PTHP (Cooling mode)

Replacements b

All Capacities

95°F db Outdoor Air

10.8 - (0.213 x Cap/1000) a EER

PTHP  (Heating Mode) Newly constructed or newly conditioned buildings or additions

All Capacities

-

3.7 - (0.052 x Cap/1000) a COP

PTHP  (Heating mode)Replacements b

All Capacities

-

2.9 - (0.026 x Cap/1000) a COP

SPVAC (Cooling Mode)

<65,000 Btu/h

95°F db / 75°F wb
Outdoor Air

11.0 EER

ANSI/AHRI 390

 

≥65,000 Btu/h and
<135,000 Btu/h

95°F db / 75°F wb
Outdoor Air

10.0 EER

≥135,000 Btu/h and
<240,000 Btu/h

95°F db / 75°F wb
Outdoor Air

10.0 EER

SPVAC (Cooling Mode) nonweatherized space constrained

≤ 30,000 Btu/h

"95F db / 75F wb

outdoor air"

9.20 EER

> 30,000 Btu/h and

≤ 36,000 Btu/h

"95F db / 75F wb

outdoor air"

9.00 EER

SPVHP (Cooling Mode)

<65,000 Btu/h

95°F db / 75°F wb
Outdoor Air

10.0 EER

≥65,000 Btu/h and
<135,000 Btu/h

95°F db / 75°F wb
Outdoor Air

10.0 EER

≥135,000 Btu/h and
<240,000 Btu/h

95°F db / 75°F wb
Outdoor Air

10.0 EER

SPVHP (Cooling Mode) nonweatherized space constrained

≤ 30,000 Btu/h

95°F db / 75°F wb
Outdoor Air

9.20 EER

> 30,000 Btu/h and

≤ 36,000 Btu/h

95°F db / 75°F wb
Outdoor Air

9.00 EER

SPVHP (Heating Mode)

<65,000 Btu/h

47°F db / 43°F wb
Outdoor Air

3.3 COP

≥65,000 Btu/h and
<135,000 Btu/h

47°F db / 43°F wb
Outdoor Air

3.0 COP

≥135,000 Btu/h and
<240,000 Btu/h

47°F db / 43°F wb
Outdoor Air

3.0 COP

SPVHP (Heating Mode) nonweatherized space constrained

≤ 30,000 Btu/h

47°F db / 43°F wb Outdoor Air

3.00 COP

> 30,000 Btu/h and

≤ 36,000 Btu/h

47°F db / 43°F wb
Outdoor Air

3.00 COP

a  Cap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation.  If the unit’s capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation
b Replacement units must be factory labeled as follows: "MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEWLY CONSTRUCTED BUILDINGS." Replacement efficiencies apply only to units with existing sleeves less than 16 inches high or less than 42 inch wide and having a cross-sectional area less than 670 square inches.
c Applicable test procedure and reference year are provided under the definitions.

TABLE 110.2-F   HEAT TRANSFER EQUIPMENT

Equipment Type

Subcategory

Minimum Efficiencya

Test Procedure b

Liquid-to-liquid heat exchangers

Plate type

NR

ANSI/AHRI 400

 

a  NR - means no requirement
b  Applicable test procedure and reference year are
     provided under the definitions

 

TABLE 110.2-G PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT

Equipment Type

Total System Heat Rejection Capacity at Rated Conditions

Subcategory or Rating Condition

Performance Required ,a ,b, c, d

Test Procedure e

Propeller or axial fan

Open-circuit cooling towers

All

95°F entering water

85°F leaving water

75 °F entering air wb

>42.1 gpm/hp

CTI ATC-105
and
CTI STD-201
RS

Centrifugal fan

Open-circuit cooling towers

All

95°F entering water

85°F leaving water

75 °F entering air wb

> 20.0 gpm/hp

Propeller or axial fan

closed-circuit  cooling towers

All

102°F entering water

90°F leaving water

75 °F entering air wb

> 16.1 gpm/hp

Centrifugal fan

closed-circuit cooling towers

All

102°F entering water

90°F leaving water

75 °F entering air wb

> 7.0 gpm/hp

Propeller or axial fan

evaporative condensers

All

   R-507A test fluid

165F entering gas temp

105F condensing temp

75F entering air wb"

≥ 157,000

     Btu/h • hp

CTI ATC-106

 

All

   Ammonia test fluid

140F entering gas temp

96.3F condensing temp

75F entering air wb"

≥ 134,000

     Btu/h • hp

Centrifugal fan

evaporative condensers

All

   R-507A test fluid

165F entering gas temp

105F condensing temp

75F entering air wb"

≥ 135,000
Btu/h • hp

All

   Ammonia test fluid

140F entering gas temp

96.3F condensing temp

75F entering air wb"

≥ 110,000

     Btu/h • hp

Air cooled condensers

All

125°F condensing temperature

R22 test fluid

190°F entering gas temperature

15°F subcooling

95°F entering drybulb

>176,000
 Btu/h
hp

ANSI/AHRI 460

 

a For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the given rated conditions divided by the fan motor nameplate power.

b For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the given rated conditions divided by the sum of the fan motor nameplate rated power and the integral spray pump motor nameplate power .

c   For purposes of this table air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power.

d Open cooling towers shall be tested using  the test procedures in CTI ATC-105.  Performance of factory assembled open cooling towers shall be either certified as base models as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency.  Open factory assembled cooling towers with custom options added to a CTI certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the associated base model or at the manufacturer’s stated performance, whichever is less.  Base models of open factory assembled cooling towers are open cooling towers configured in exact accordance with the Data of Record submitted to CTI as specified by CTI STD-201.  There are no certification requirements for field erected cooling towers.

e Applicable test procedure and reference year are provided under the definitions. For refrigerated warehouses or commercial refrigeration applications, condensers shall comply with requirements specified by Section 120.6(a)|topic=(a) Mandatory Requirements for Refrigerated Warehouses or Section 120.6(b)|topic=(b) Mandatory Requirements for Commercial Refrigeration or 120.6(b)

 

TABLE 110.2-H Electrically Operated Variable Refrigerant Flow (VRF) Air Conditioners
Minimum Efficiency Requirements

Equipment Type

Size Category

Heating Section Type

Sub-Category or Rating Condition

Minimum Efficiency

Test Procedurea

VRF Air Conditioners,
Air Cooled

<65,000 Btu/h

All

VRF Multi-split System

13.0 SEER

ANSI/AHRI 1230

≥65,000 Btu/h and <135,000 Btu/h

Electric Resistance (or none)

VRF Multi-split System

11.2 EER
15.5  IEER
b

≥135,000 Btu/h and <240,000 Btu/h

Electric Resistance (or none)

VRF Multi-split System

11.0 EER
14.9 IEER
b

≥240,000 Btu/h

Electric Resistance (or none)

VRF Multi-split System

10.0 EER
13.9

 IEER b

a   Applicable test procedure and reference year are provided under the definitions.
b  IEERs are only applicable to equipment with capacity control as specified by ANSI/AHRI 1230 test procedures.

 

TABLE 110.2-I Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps -
Minimum Efficiency Requirements

Equipment Type

Size Category

Heating Section Type

Sub-Category or Rating Condition

Minimum Efficiency

Test Procedure b

VRF Air Cooled, (cooling mode)

<65,000 Btu/h

All

VRF Multi-split System

13.0 SEER

AHRI 1230

 

≥65,000 Btu/h and <135,000 Btu/h

Electric Resistance (or none)

VRF Multi-split System a

11.0 EER
14.6 IEER
c

≥135,000 Btu/h and <240,000 Btu/h

Electric Resistance (or none)

VRF Multi-split System a

10.6 EER
13.9 IEER c

≥240,000 Btu/h

Electric Resistance (or none)

VRF Multi-split System a

9.5 EER
12.7 IEER
c

VRF Water source

(cooling mode)

<65,000 Btu/h

All

VRF Multi-split systemsa 86ºF entering water

12.0 EER
15.8 IEER

AHRI 1230

≥65,000 Btu/h and

<135,000 Btu/h

All

VRF Multi-split Systema 86ºF entering water

12.0 EER
15.8 IEER

≥135,000 Btu/h and < 240,000

All

VRF Multi-split Systema 86ºF entering water

10.0 EER
13.8 IEER

≥ 240,000 Btu/h

All

VRF Multi-split Systema 86oF entering water

10.0 EER
12.0 IEER

VRF Groundwater source (cooling mode)

<135,000 Btu/h

All

VRF Multi-split Systema 59ºF entering water

16.2 EER

AHRI 1230

135,000 Btu/h

All

VRF Multi-split Systema 59ºF entering water

13.8 EER

VRF Ground source (cooling mode)

<135,000 Btu/h

All

VRF Multi-split Systema 77ºF entering water

13.4 EER

AHRI 1230

 

135,000 Btu/h

All

VRF Multi-split Systema 77ºF entering water

11.0 EER

VRF Air Cooled (heating mode)

<65,000 Btu/h

(cooling capacity)

- - -

VRF Multi-split System

7.7 HSPF

AHRI 1230

≥65,000 Btu/h and

<135,000 Btu/h

(cooling capacity)

- - -

VRF Multi-split system47ºF db/ 43ºF wb outdoor air

3.3 COP

VRF Multi-split system17ºF db/15ºF wb outdoor air

2.25 COP

≥135,000 Btu/h

(cooling capacity)

- - -

VRF Multi-split system 47ºF db/ 43ºF wb outdoor air

3.2 COP

VRF Multi-split system 17ºF db/15ºF wb outdoor air

2.05 COP

VRF Water source
(heating mode)

<135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

68ºF entering water

4.2 COP

AHRI 1230

≥135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

68ºF entering water

3.9 COP

VRF Groundwater source (heating mode)

<135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

50ºF entering water

3.6 COP

AHRI 1230

≥135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

50ºF entering water

3.3 COP

VRF Ground source

(heating mode)

<135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

32ºF entering water

3.1 COP

AHRI 1230

≥135,000 Btu/h (cooling capacity)

---

VRF Multi-split System

32ºF entering water

2.8 COP

a  Deduct 0.2 from the required EERs and IEERs for Variable Refrigerant Flow (VRF) Multi-split system units with a heating recovery section.
b  Applicable test procedure and reference year are provided under the definitions.
c IEERs are only applicable to equipment with capacity control as specified by ANSI/AHRI 1230 test procedures.

 

TABLE 110.2-J Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units,
Warm-Air Duct Furnaces, and Unit Heaters

Equipment Type

Size Category (Input)

Subcategory or Rating Conditionb

Minimum Efficiencyd,e

Test Procedurea

Warm-Air Furnace, Gas-Fired

≥ 225,000 Btu/h

Maximum Capacityb

80% Et

Section 2.39, Thermal Efficiency, ANSI Z21.47

Warm-Air Furnace, oil-Fired

≥ 225,000 Btu/h

Maximum Capacityb

81% Et

Section 42, Combustion, UL 727

Warm-Air Duct Furnaces, Gas-Fired

All Capacities

Maximum Capacityb

80% Ec

Section 2.10, Efficiency, ANSI Z83.8

Warm-Air Unit Heaters, Gas-Fired

All Capacities

Maximum Capacityb

80% Ec

Section 2.10, Efficiency, ANSI Z83.8

Warm-Air Unit Heaters, Oil-Fired

All Capacities

Maximum Capacityb

81% Ec

Section 40, Combustion, UL 731

a Applicable test procedure and reference year are provided under the definitions.
b Compliance of multiple firing rate units shall be at maximum firing rate.
c Combustion units not covered by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430 (3-phase power or cooling capacity greater than or equal to 19 kW) may comply with either rating.
d Et= thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.
e Ec= combustion efficiency (100% less flue losses). See test procedure for detailed discussion.
f As of August 8, 2008, according to the Energy Policy Act of 2005, units must also include interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.

 

TABLE 110.2-K  Gas- and Oil-Fired Boilers,
Minimum Efficiency requirements

Equipment Type

Sub Category

Size Category (Input)

Minimum
Efficiency b,c

Test Procedure a

 

 

 

Before 3/2/2020

After 3/2/2020

 

Boiler, hot water

Gas-Fired

< 300,000 Btu/h

82% AFUE

82% AFUE

DOE 10 CFR Part 430

≥ 300,000 Btu/h and

≤ 2,500,000 Btu/h d

80% Et

80% Et

DOE 10 CFR Part 431

>  2,500,000 Btu/h e

82% Ec

82% Ec

Oil-Fired

< 300,000 Btu/h

84% AFUE

84% AFUE

DOE 10 CFR Part 430

≥ 300,000 Btu/h and

≤ 2,500,000 Btu/h d

82% Et

82% Et

DOE 10 CFR Part 431

>  2,500,000 Btu/h e

84% Ec

84% Ec

Boiler, steam

Gas-Fired

< 300,000 Btu/h

80% AFUE

80% AFUE

DOE 10 CFR Part 430

Gas-Fired all, except natural draft

≥ 300,000 Btu/h and

≤ 2,500,000 Btu/h d

79% Et

79% Et

DOE 10 CFR Part 431

> 2,500,000 Btu/h e

79% Et

79% Et

DOE 10 CFR Part 431

Gas-Fired, natural draft

≥ 300,000 Btu/h and

≤ 2,500,000 Btu/h d

77% Et

79% Et

DOE 10 CFR Part 431

>  2,500,000 Btu/h e

77% Et

79% Et

DOE 10 CFR Part 431

Oil-Fired

< 300,000 Btu/h

82% AFUE

82% AFUE

DOE 10 CFR Part 430

≥ 300,000 Btu/h and

≤ 2,500,000 Btu/h d

81% Et

81% Et

DOE 10 CFR Part 431

> 2,500,000 Btu/h e

81% Et

81% Et

DOE 10 CFR Part 431

a  Applicable test procedure and reference year are provided under the definitions.
Ec = combustion efficiency (100% less flue losses). See reference document for detailed information

Et= thermal efficiency. See test procedure for detailed information.
d  Maximum capacity - minimum and maximum ratings as provided for and allowed by the unit’s controls.
e Included oil-fired (residual).

 

NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code