8.5 HVAC Issues

8.5.1 No Cooling Installed

When a building has no cooling system, the software simulates a hypothetical system with the characteristics required by Table 150.1-A as if a cooling system were installed. The result is neither a penalty nor a credit.

8.5.2 Wood Heat

When natural gas is not available, and all other eligibility criteria are met (see Chapter 4), a wood heating system is simulated as a hypothetical system with the characteristics required by Table 150.1-A or -B for a typical heating system. When all eligibility criteria are met, the backup system is not modeled; otherwise, see Section 8.5.3.

8.5.3 Multiple HVAC Systems

Buildings with multiple HVAC systems are treated as follows:

  1. For buildings with more than one system type, equipment type, or fuel type, where the types do not serve the same floor area, model the building zone or floor area served by each unique type separately.
  2. Supplemental heating may be ignored if (1) the capacity of the supplemental unit does not exceed 2 kilowatts (kW) or 7,000 British thermal units per hour, and (2) the supplemental unit is controlled by a time-limiting device that does not allow it to run for more than 30 minutes. (§150.1[c]6.)
    In a building with a central gas furnace and an appliance-rated gas fireplace, the furnace is the primary system, and the fireplace is the supplemental system. In this case, the controls for the fireplace would not need to meet the setback thermostat requirements (Exception to §110.2[c]).
  3. For single family buildings served by more than one heating or cooling system, equipment type, or fuel type, model the least efficient system. For any areas served by electric resistance heat and another heating system (except for wood heating meeting all eligibility criteria), the electric resistance system is the least efficient system.

When there is more than one system meeting the heating or cooling load for the same space, all systems must meet all mandatory requirements of the Energy Standards.

8.5.4 HERS Verified Efficiency

When higher than minimum efficiency is modeled, a HERS Rater must verify the efficiency. This includes:

  • Seasonal Energy Efficiency Ratio (SEER) or Seasonal Energy Efficiency Ratio 2 (SEER2)
  • Energy Efficiency Ratio (EER) or Energy Efficiency Ratio 2 (EER2)
  • Combined Energy Efficiency Ratio (CEER)
  • Heating Seasonal Performance Factor (HSPF) or Heating Seasonal Performance Factor 2 (HSPF2)

8.5.5 Existing + Addition + Alteration Approach

The performance approach may be used to show compliance for alterations to existing buildings, additions, and existing + addition + alteration as discussed in Chapter 9. When existing conditions are unknown, the default assumptions in Table 8-1 must be used. The standard design for an altered component shall be the higher efficiency of existing conditions or the requirements stated in Table 8.1 Standard Design for an Altered Component For components not being altered, the standard design shall be based on the existing conditions. When the third-party verification option is specified as a requirement, all components proposed for alteration for which the additional credit is taken must be verified.

Table 8-1 Standard Design for an Altered Component

Altered Component
Standard Design Without Third Party Verification of Existing Conditions Shall be Based On
Standard Design With Third Party Verification of Existing Conditions Shall be Based On
Ceiling Insulation, Wall Insulation, and Raised-floor Insulation
The requirements of Sections 150.0(a), (c), and (d)
The existing insulation R-value
Fenestration
The U-factor of 0.40 and SHGC value of 0.35. The glass area shall be the glass area of the existing building.
If the proposed U-factor is ≤ 0.40 and SHGC value is ≤ 0.35, the standard design shall be based on the existing U-factor and SHGC values as verified. Otherwise, the standard design shall be based on the U-factor of 0.40 and SHGC value of 0.35. The glass area shall be the glass area of the existing building.
Window Film
The U-factor of 0.40 and SHGC value of 0.35.
The existing fenestration in the alteration shall be based on Table 110.6-A and Table 110.6-B.
Doors
The U-factor of 0.20. The door area shall be the door area of the existing building.
If the proposed U-factor is < 0.20, the standard design shall be based on the existing U-factor value as verified. Otherwise, the standard design shall be based on the U-factor of 0.20. The door area shall be the door area of the existing building.
Space-Heating and Space-Cooling Equipment
Table 150.1-A for equipment efficiency requirements; Section 150.2(b)1C for entirely new or complete replacement systems;
Section 150.2(b)1F for refrigerant charge verification requirements.
The existing efficiency levels.
Air Distribution System – Duct Sealing
The requirements of Sections 150.2(b)1D and 150.2(b)1E
The requirements of Sections 150.2(b)1D and 150.2(b)1E
Air Distribution System – Duct Insulation
The proposed efficiency levels.
The existing efficiency levels.
Water Heating Systems
The requirements of Section 150.2(b)1Hii
The existing efficiency level.
Roofing Products
The requirements of Section 150.2(b)1I
The requirements of Section 150.2(b)1I
All Other Measures
The proposed efficiency levels.
The existing efficiency levels.

Source: California Energy Commission Energy Code Table 150.2-D

This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2024 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.