EXCEPTION 1 to Section 140.9(a)1: Individual computer rooms with an ITE design load under 5 tons (18 kW) in a building that does not have any economizers.
EXCEPTION 2 to Section 140.9(a)1: A computer room with an ITE design load less than 20 tons (70 kW) may be served by a second fan system without an economizer if it is also served by a fan system with an economizer that also serves other spaces within the building, provided that all of the following are met:
EXCEPTION 1 to Section 140.9(a)3: Expansions of existing computer rooms.
EXCEPTION 2 to Section 140.9(a)3: Computer racks with a design load less than 1 kW (0.28 tons) per rack.
EXCEPTION 3 to Section 140.9(a)3: Equivalent energy performance based on computational fluid dynamics or other analysis.
Where:
- P is the rated output power in watts (W).
EMOD is an allowance of 0.004 for modular UPSs applicable in commercial 1,500-10,000 W range.
ln is the natural logarithm.
The requirement shall be rounded to the third decimal place for certification and reporting.
EXCEPTION to Section 140.9(a)4: Alternating current-output UPS that utilizes standardized NEMA 1-15P or NEMA 5-15P input plug, as specified in ANSI/NEMA WD-6-2016.
Voltage and Frequency Dependent | Voltage Independent | Voltage and Frequency Independent | |
P≤350 W | 5.71 x 10-5 x P + 0.962 | 5.71 x 10-5 x P + 0.964 | 0.011 x ln(P) + 0.824 |
350 W<P≤1,500 W | 0.982 | 0.984 | 0.011 x ln(P) + 0.824 |
1,500 W<P≤10,000 W | 0.981 – EMOD | 0.980 – EMOD | 0.0145 x ln(P) +0.800 – EMOD |
P>10,000 W | 0.970 | 0.940 | 0.0058 x ln(P) + 0.886 |
EXCEPTION 1 to Section 140.9(b)1B: 75 percent of the total Type I and Type II exhaust replacement air is transfer air that would otherwise be exhausted.
EXCEPTION 2 to Section 140.9(b)1B: Existing hoods not being replaced as part of an addition or alteration.
Type of Hood | Light Duty Equipment | Medium Duty Equipment | Heavy DutyEquipment | Extra HeavyDuty Equipment |
Wall-mounted Canopy | 140 | 210 | 280 | 385 |
Single Island | 280 | 350 | 420 | 490 |
Double Island | 175 | 210 | 280 | 385 |
Eyebrow | 175 | 175 | Not Allowed | Not Allowed |
Backshelf / Passover | 210 | 210 | 280 | Not Allowed |
EXCEPTION to Section 140.9(b)2A: Existing kitchen makeup air units not being replaced as part of an addition or alteration.
(i) 50 percent of the total design exhaust and replacement air system airflow rates; or
(ii) The ventilation rate required as specified by Section 120.1(c)3.
EXCEPTION to Section 140.9(b)2B: Existing hoods not being replaced as part of an addition or alteration.
EXCEPTION to Section 140.9(b): healthcare facilities.
EXCEPTION 1 to Section 140.9(c)1: Laboratory exhaust systems serving zones where constant volume is required by the Authority Having Jurisdiction, facility Environmental Health & Safety department or other applicable code.
EXCEPTION 2 to Section 140.9(c)1: New zones on an existing constant volume exhaust system.
EXCEPTION to Section 140.9(c)3B: Laboratory exhaust systems where applicable local, state, or federal exhaust treatment requirements specify installation of air treatment devices that cause more than 1 in. of water pressure drop.
Occupied Minimum Ventilation ACH
|
≤ 4
|
> 4 and ≤ 6
|
> 6 and ≤ 8
|
> 8 and ≤ 10
|
> 10 and ≤ 12
|
> 12 and ≤ 14
|
Hood Density (linear feet per 10,000 ft3 of laboratory space
|
≥ 6
|
≥ 8
|
≥ 10
|
≥ 12
|
≥ 14
|
≥ 16
|
EXCEPTION to Section 140.9(c): healthcare facilities.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.