Exception 1 to Section 140.9(a)1: Individual computer rooms with an ITE design load under 5 tons (18 kW) in a building that does not have any economizers.
Exception 2 to Section 140.9(a)1: A computer room with an ITE design load less than 20 tons (70 kW) may be served by a second fan system without an economizer if it is also served by a fan system with an economizer that also serves other spaces within the building, provided that all of the following are
Exception 1 to Section 140.9(a)3: Expansions of existing computer rooms.
Exception 2 to Section 140.9(a)3: Computer racks with a design load less than 1 kW (0.28 tons) per rack.
Exception 3 to Section 140.9(a)3: Equivalent energy performance based on computational fluid dynamics or other analysis.
Where:
- P is the rated output power in watts (W).
EMOD is an allowance of 0.004 for modular UPSs applicable in commercial 1,500-10,000 W range.
ln is the natural logarithm.
The requirement shall be rounded to the third decimal place for certification and reporting.
Exception to Section 140.9(a)4: Alternating current-output UPS that utilizes standardized NEMA 1-15P or NEMA 5-15P input plug, as specified in ANSI/NEMA WD-6-2016.
AC Output | Voltage and Frequency Dependent | Voltage Independent | Voltage and Frequency Independent |
P≤350 W | 5.71 x 10-5 x P + 0.962 | 5.71 x 10-5 x P + 0.964 | 0.011 x ln(P) + 0.824 |
350 W<P≤1,500 W | 0.982 | 0.984 | 0.011 x ln(P) + 0.824 |
1,500 W<P≤10,000 W | 0.981 – EMOD | 0.980 – EMOD | 0.0145 x ln(P) +0.800 – EMOD |
P>10,000 W | 0.970 | 0.940 | 0.0058 x ln(P) + 0.886 |
Exception 1 to Section 140.9(b)1B: 75 percent of the total Type I and Type II exhaust replacement air is transfer air that would otherwise be exhausted.
Exception 2 to Section 140.9(b)1B: Existing hoods not being replaced as part of an addition or alteration.
Type of Hood | Light Duty Equipment | Medium Duty Equipment | Heavy Duty Equipment | Extra Heavy Duty Equipment |
Wall-mounted Canopy | 140 | 210 | 280 | 385 |
Single Island | 280 | 350 | 420 | 490 |
Double Island | 175 | 210 | 280 | 385 |
Eyebrow | 175 | 175 | Not Allowed | Not Allowed |
Back shelf / Passover | 210 | 210 | 280 | Not Allowed |
Exception to Section 140.9(b)2A: Existing kitchen makeup air units not being replaced as part of an addition or alteration.
(i) 50 percent of the total design exhaust and replacement air system airflow rates; or
(ii) The ventilation rate required as specified by Section 120.1(c)3.
Exception to Section 140.9(b)2B: Existing hoods not being replaced as part of an addition or alteration.
Exception to Section 140.9(b): healthcare facilities.
- User-defined airflow not to exceed 1.0 cfm/ft2 (equivalent to 6 air changes per hour for a 10-foot high ceiling), or
- The regulated minimum occupied circulation rate documented to comply with code, accreditation, or facility environmental health and safety department requirements, or
- The minimum needed to maintain occupied pressurization.
- User-defined airflow not to exceed 0.67 cfm/ft2 (equivalent to 4 air changes per hours for a 10-foot high ceiling), or
- The regulated minimum unoccupied circulation rate documented to comply with code, accreditation, or facility environmental health and safety department requirements, or
- The minimum needed to maintain unoccupied pressurization.
Exception to Section 140.9(c)1: New zones on an existing constant volume exhaust system.
- The sum of the occupied minimum circulation rates of the spaces served by the fan system shall be less than 60 percent of the exhaust fan system design airflow rate.
- The design exhaust fan system power shall not exceed 1.3 watts per cfm of exhaust fan system airflow when operating under full load design conditions.
- The system shall include variable speed controls so that exhaust system fans shall draw no more than 40 percent of the design fan power when the exhaust fan system airflow is 60 percent of the design airflow rate.
- The exhaust fan system airflow rate shall not exceed the larger of:
- The sum of the space exhaust airflow rates served by the system, or
- The minimum acceptable exhaust fan system airflow rate.
- The minimum acceptable exhaust airflow rate, using the procedures and system definitions included in ANSI Z9.5 (2022) Appendix 3, shall be one of the following:
- Less than 60 percent of the exhaust fan system design airflow rate (simple turndown control system), or
- Dynamically reset based on measured wind speed and/or wind direction and assumes worst case emissions rate and shall be less than 60 percent of the exhaust fan system design airflow rate for at least 70 percent of the hours during a typical meteorological year (TY) for the site (wind responsive control system), or
- Dynamically reset based on measured contaminant concentration and shall be less than 60 percent of the exhaust fan system design airflow rate when measured contaminants in the exhaust system plenum are below the threshold contaminant concentration value (monitored control system).
- Exhaust system design and control results in calculated outdoor contaminant concentrations in compliance with applicable federal, state, or local regulations.
- Applicable equipment and systems shall be certified as meeting the acceptance requirements for code compliance, as specified by the Reference Nonresidential Appendix NA7.16. A certificate of acceptance shall be submitted to the enforcement agency that certifies that the equipment and systems meet the acceptance requirements specified in NA7.16.
Occupied Minimum Ventilation ACH
|
≤ 4
|
> 4 and ≤ 6
|
> 6 and ≤ 8
|
> 8 and ≤ 10
|
> 10 and ≤ 12
|
> 12 and ≤ 14
|
Hood Density (linear feet per 10,000 of laboratory space
|
≥ 6
|
≥ 8
|
≥ 10
|
≥ 12
|
≥ 14
|
≥ 16
|
Exception 1 to Section 140.9(c)5: Additions or alterations to existing air handling systems serving existing zones without heating and cooling capacity.
Exception 2 to Section 140.9(c)5: Systems in climate zones 7 or 15.
Exception 3 to Section 140.9(c)5: Systems dedicated to vivarium spaces or to spaces classified as biosafety level 3 or higher.
Exception 4 to Section 140.9(c)5: Systems that:
1. Are located where the outdoor dew point temperature is greater than or equal to 64°F at the ASHRAE 2 percent annual dehumidification design condition, and
2. Include heating and cooling capacity at each zone, and
3. Do not mechanically cool air handler supply air below 80°F when the outdoor dew point temperature is below 60°F.
A. A sensible energy recovery ratio of at least 45 percent at heating design conditions and 25 percent at cooling design conditions.
B. Heat is recovered from at least 75 percent of all lab exhaust air volume.
C. The system includes a run-around coil pump or other means to disable heat recovery.
D. The system includes a bypass damper or other means so that the exhaust air pressure drop through the heat exchanger does not exceed 0.4 inch w.g. when heat recovery is disabled.
Exception 1 to Section 140.9(c)6: Additions or alterations to existing laboratory exhaust systems that do not include exhaust air heat recovery.
Exception 2 to Section 140.9(c)6: Buildings where the total laboratory exhaust rate exceeds 20 cfm/ft2 of roof area.
Exception 3 to Section 140.9(c)6: Locations that meet both of the following:
1. In Climate Zone 6 or 7; and
2. In a jurisdiction where gas heating is allowed.
Exception 4 to Section 140.9(c)6: Buildings with an exhaust air heat recovery system and heat recovery chillers designed to provide at least 40% of the peak heating load from exhaust heat recovery.
Exception 5 to Section 140.9(c)6: Exhaust systems requiring wash down systems such as exhaust systems dedicated to perchloric acid fume hoods.
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.