Appendix NA3 – Fan Motor Efficiencies
Table NA3-1 – Fan Motor Efficiencies (< 1 HP)
Nameplate or Brake Horsepower
Standard Fan Motor Efficiency
NEMA* High Efficiency
Premium Efficiency
1/20
40%
...
...
1/12
49%
...
...
1/8
55%
...
...
1/6
60%
...
...
1/4
64%
...
...
1/3
66%
...
...
1/2
70%
76.0%
80.0%
3/4
72%
77.0%
84.0%

NOTE: For default drive efficiencies, see Nonresidential ACM Reference Manual

*NEMA - Proposed standard using test procedures.

Minimum NEMA efficiency as specified by test IEEE 112b Rating Method.

Table NA3-2 – Fan Motor Efficiencies (1 HP and over)

Open MotorsOpen MotorsOpen MotorsOpen MotorsEnclosed MotorsEnclosed MotorsEnclosed MotorsEnclosed Motors
Motor Horsepower
2 pole 3600 rpm4 pole 1800 rpm6 pole 1200 rpm8 pole 900 rpm2 pole 3600 rpm4 pole 1800 rpm6 pole 1200 rpm8 pole 900 rpm
177.085.582.574.077.085.582.574.0
1.584.086.586.575.584.086.587.577.0
285.586.587.585.585.586.588.582.5
385.589.588.586.586.589.589.584.0
586.589.589.587.588.589.589.585.5
7.588.591.090.288.589.591.791.085.5
1089.591.791.789.590.291.791.088.5
1590.293.091.789.591.092.491.788.5
2091.093.092.490.291.093.091.789.5
2591.793.693.090.291.793.693.089.5
3091.794.193.691.091.793.693.091.0
4092.494.194.191.092.494.194.191.0
5093.094.594.191.793.094.594.191.7
6093.695.094.592.493.695.094.591.7
7593.695.094.593.693.695.494.593.0
10093.695.495.093.694.195.495.093.0
12594.195.495.093.695.095.495.093.6
15094.195.895.493.695.095.895.893.6
20095.095.895.493.695.496.295.8
94.1
25095.095.895.494.595.896.295.8
94.5
30095.495.895.4-95.896.295.8
-
35095.495.895.4-95.896.295.8-
40095.895.895.8-95.896.295.8-
45095.896.296.2-95.896.295.8-
50095.896.296.2-95.896.295.8-
loading