NA7.15 Escalator and Moving Walkway Speed Control
NA7.15.1 Construction Inspection

Verify and document the following prior to functional testing:

  1. Variable speed drive is installed on the escalator.
  2. Occupancy sensor has been located to minimize false signals.
  3. Occupancy sensors do not trigger from pedestrians on adjacent escalators.
  4. Occupancy sensors do not encounter any obstructions that could adversely affect desired performance.
  5. Ultrasonic occupancy sensors do not emit audible sound
NA7.15.2 Functional Testing

For each escalator or moving walkway being tested, confirm the following:

  1. Verify the amount of time necessary to ride the entire length of the escalator while standing still.
  2. Stand away from the escalator. After being in an unoccupied condition for more than three times the length of time for a full ride, the escalator should slow down.
  3. Approach the escalator entrance while in an unoccupied condition from multiple angles to ensure passenger detection cannot be bypassed.
  4. Verify the slow speed setting is 10 ft/min.
  5. Verify the full speed setting is below 100 ft/min.
  6. Verify the acceleration and deceleration of speed changes. The acceleration shall not exceed 1 ft/sec sq.
  7. Approach the escalator in an unoccupied condition at an average walking pace. The escalator should reach full speed before boarding.
  8. Approach the escalator in an unoccupied condition at an average walking pace in the wrong direction. An alarm should signal to alert that the pedestrian is approaching in the wrong direction.

This panel displays referenced content when certain links are clicked.

This website and the messages contained in its webpages are funded by customers unless otherwise noted.
This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2026 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.