Welcome to the 2025 Reference Ace Beta

Should you find any issues, please let us know using the contact form on the right of the page. Thank you!

SECTION 110.2 - MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

Certification by Manufacturers. Any space-conditioning equipment listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section

(a) Efficiency. Equipment shall meet the applicable efficiency requirements in Tables 110.2-A through 110.2-L, subject to the following:
1. If more than one efficiency standard is listed for any equipment in Tables 110.2-A through 110.2-L, the equipment shall meet all the applicable standards that are listed; and
2. If more than one test method is listed in Tables 110.2-A through 110.2-L, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and
3. Where equipment serves more than one function, it shall comply with the efficiency standards applicable to each function; and
4. Where a requirement is for equipment rated at its "maximum rated capacity" or "minimum rated capacity," the capacity shall be as provided for and allowed by the controls, during steady-state operation.

Exception 1 to Section 110.2(a): 

      Water-cooled centrifugal water-chilling packages that are not designed for operation at ANSI/AHRI Standard 550/590 test conditions of 44°F leaving chilled water temperature and 85°F entering condenser water temperature with 3 gallons per minute per ton condenser water flow shall have a maximum full load kW/ton and NPLV ratings adjusted using the following equation:

Adjusted maximum full-load kW/ton rating = (full-load kW/ton from Table 110.2-D)/Kadj

Adjusted maximum NPLV rating = (IPLV from Table 110.2-D)/Kadj

Where:

Kadj = (A) × (B)

A = 0.00000014592 × (LIFT)4 – 0.0000346496 × (LIFT)3+0.00314196 × (LIFT)2 – 0.147199 × (LIFT) + 3.9302

LIFT = LvgCond – LvgEvap (°F)

LvgCond = Full-load leaving condenser fluid temperature (°F)

LvgEvap = Full-load leaving evaporator fluid temperature (°F)

B = (0.0015 × LvgEvap) + 0.934

The adjusted full-load and NPLV values are only applicable for centrifugal chillers meeting all of the following full-load design ranges:

    Minimum Leaving Evaporator Fluid Temperature: 36°F

    Maximum Leaving Condenser Fluid Temperature: 115°F

    LIFT ≥ 20°F and ≤ 80°F

Centrifugal chillers designed to operate outside of these ranges are not covered by this exception.


Exception 2 to Section 110.2(a): Positive displacement (air-cooled and water-cooled) chillers with a leaving evaporator fluid temperature higher than 32°F shall show compliance with Table 110.2-D when tested or certified with water at standard rating conditions, per the referenced test procedure.
Exception 3 to Section 110.2(a): Equipment primarily serving refrigerated warehouses or commercial refrigeration.
(b) Controls for heat pumps with supplementary heaters

Control requirements for heat pumps with supplementary heaters in single-family residential buildings are specified in Section 150.0(h)7 and Section 150.0(i)2.  Heat pumps with supplementary heaters in nonresidential and multifamily buildings shall have controls:
                                                                                                             
1. That prevent supplementary heater operation when the heating load can be met by the heat pump alone
  2. In which the cut-on temperature for heat pump heating is higher than the cut-on temperature for supplementary heating, and the cut-off temperature for heat pump heating is higher than the cut-off temperature for supplementary heating.
Exception 1 to Section 110.2(b): The controls may allow supplementary heater operation during:

A. Defrost; and

B. Transient periods such as start-ups and following room thermostat setpoint advance, if the controls provide preferential rate control, intelligent recovery, staging, ramping or another control mechanism designed to preclude the unnecessary operation of supplementary heating.

Exception 2 to Section 110.2(b): Room air-conditioner heat pumps.
(c) Thermostats. All heating or cooling systems not controlled by a central energy management control system (EMCS) shall have a setback thermostat.
 
1. Setback capabilities. All thermostats shall have a clock mechanism that allows the building occupant to program the temperature setpoints for at least four periods within 24 hours. Thermostats for heat pumps shall meet the requirements of Section 110.2(b).
Exception to Section 110.2(c): Gravity gas wall heaters, gravity floor heaters, gravity room heaters, noncentral electric heaters, fireplaces or decorative gas appliances, wood stoves, room air conditioners, and room air-conditioner heat pumps.
(d) Gas-fired and oil-fired furnace standby loss controls. Gas-fired and oil-fired forced air furnaces with input ratings ≥ 225,000 Btu/hr shall also have an intermittent ignition or interrupted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥ 225,000 Btu/hr, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.


(e) Open and closed-circuit cooling towers. All open and closed-circuit cooling tower installations shall comply with the following:
  1. Be equipped with conductivity controls that maximize cycles of concentration based on local water quality conditions. Controls shall automate system bleed and chemical feed based on conductivity. Conductivity controllers shall be installed in accordance with manufacturer’s specifications in order to maximize accuracy.
  2. Documentation of maximum achievable cycles of concentration. Building owners shall document the cycles of concentration achievable based on local water supply conditions as reported annually by the local water supplier, and using the calculations below. The calculations are intended to determine maximum achievable cycles of concentration based on the parameters identified in Table 110.2-A-1. Building owner shall document maximum achievable cycles of concentration on the mechanical compliance form which shall be reviewed and signed by the Professional Engineer (P.E.) of Record.

The maximum achievable cycles of concentrations are based on the local water supply quality as reported by the local water supplier, and shall be the minimum of:

A. 2970 divided by the conductivity of the entering make-up water

B. 1845 divided by the total dissolved solids of the entering make-up water

C. 540 divided by the M-alkalinity excluding galvanized steel of the entering make-up water

D. 450 divided by the M-alkalinity including galvanized steel of the entering make-up water

E. 540 divided by the calcium hardness of the entering make-up water

F. 270 divided by the chlorides       of the entering make-up          water

G. 225 divided by the sulfates

of the entering make-up water

H. 135 divided by the silica of the entering make-up water



Where:

C = Conductivity of the entering make-up water.

H = Calcium hardness of the entering make-up water.

M = M-alkalinity excluding galvanized steel of the entering make-up water. 

T = Max skin temperature

3.  Cooling towers shall not allow blowdown until one or more of the parameters in Table 110.2- A-1 reaches the maximum value specified:


Table 110.2-A-1 RECIRCULATING WATER PROPERTIES
Recirculating Water Parameters Maximum Values
Conductivity (micro-siemens/cm) 2970 micro-siemens/cm
Total dissolved solids (ppm) 1845 ppm
Total alkalinity as CaCO3 (ppm) excluding galvanized steel 540 ppm
Total alkalinity as CaCO3 (ppm) galvanized steel (passivated) 450 ppm
Calcium hardness as CaCO3 (ppm) 540 ppm
Chlorides as Cl (ppm) 270 ppm
Sulfates (ppm) 225 ppm
Silica (ppm) 135 ppm
Langelier saturation index (LSI) 2.5 (LSI)


4.  Be equipped with a flow meter with an analog output for flow either hardwired or available through a gateway on the makeup water line.

5.  Be equipped with an overflow alarm to prevent overflow of the sump in case of makeup water valve failure. Overflow alarm shall send an audible signal or provide an alert via the energy management control system to the tower operator in case of sump overflow.

6. Be equipped with efficient drift eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counter-flow towers and 0.005 percent for cross-flow towers.

7.   Conductivity controls and overflow alarm shall be verified according to NA 7.5.18.

6. Be equipped with efficient drift eliminators...
7. Conductivity controls and overflow alarm shall be verified according to NA 7.5.18.
Exception to Section 110.2(e): Open and closed circuit cooling towers with rated capacity < 150 tons.
(f) Low leakage air-handling units. To qualify as a low leakage air-handling unit for use for meeting the requirements for applicable low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Sections 150.1(b) and 140.1, the manufacturer shall certify to the Energy Commission that the air-handling unit meets the specifications in Reference Joint Appendix JA9.
TABLE 110.2-A AIR CONDITIONERS AND CONDENSING UNITS - MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type Size Category Efficiency Test Procedure
Air conditioners, air cooled both split system and single package ≥ 65,000 Btu/h and < 135,000 Btu/h 11.2 EER*
Federal Minimum IEER*
AHRI 340/360
Air conditioners, air cooled both split system and single package ≥ 135,000 Btu/h and < 240,000 Btu/h 11.0 EER*
Federal Minimum IEER*
AHRI 340/360
Air conditioners, air cooled both split system and single package ≥ 240,000 Btu/h and < 760,000 Btu/h 10.0 EER*
Federal Minimum IEER*
AHRI 340/360
Air conditioners, air cooled both split system and single package ≥ 760,000 Btu/h 9.7 EER*
12.5 IEER*
AHRI 340/360
Air conditioners, water cooled ≥ 65,000 Btu/h and < 135,000 Btu/h Federal Minimum EER*
13.9 IEER*
AHRI 340/360
Air conditioners, water cooled ≥135,000 Btu/h and < 240,000 Btu/h Federal Minimum EER*
13.9 IEER*
AHRI 340/360
Air conditioners, water cooled ≥240,000 Btu/h and < 760,000 Btu/h Federal Minimum EER*
13.6 IEER*
AHRI 340/360

(CONTINUED) TABLE 110.2-A AIR CONDITIONERS AND CONDENSING UNITS - MINIMUM EFFICIENCY REQUIREMENTS
Equipment Type Size Category Efficiency Test Procedure
Air conditioners, water cooled ≥ 760,000 Btu/h 12.2EERa
13.5 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled ≥65,000 Btu/h and
<135,000 Btu/h
Federal
Minimum EERa
12.3 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled ≥ 135,000 Btu/h
and
< 240,000 Btu/h
Federal
Minimum EERa
12.2 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled ≥240,000 Btu/h
and
< 760,000 Btu/h
Federal
Minimum EERa
12.1 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled ≥ 760,000 Btu/h 11.7 EERa
11.9 IEERa
AHRI 340/360
Condensing units, air cooled ≥ 135,000 Btu/h 10.5 EER
Federal
Minimum IEER
AHRI 365
Condensing units, water cooled ≥ 135,000 Btu/h 13.5 EER
Federal
Minimum IEER
AHRI 365
Condensing units, evaporatively cooled ≥ 135,000 Btu/h 13.5 EER
Federal
Minimum IEER
AHRI 365

       a    Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat.

      b     Applicable test procedure and reference year are provided under the definitions.


TABLE 110.2-B HEAT PUMPS, MINIMUM EFFICIENCY REQUIREMENTS
Equipment Type Size Category Rating Condition Efficiency* Test Procedure*
Air Cooled (Cooling Mode), both split system and single package ≥ 65,000 Btu/h and < 135,000 Btu/h 11.0 EER AHRI 340/360 Federal Minimum IEER
Air Cooled (Cooling Mode), both split system and single package ≥ 135,000 Btu/h and < 240,000 Btu/h 10.6 EER AHRI 340/360 Federal Minimum IEER
Air Cooled (Cooling Mode), both split system and single package ≥ 240,000 Btu/h 9.5 EER AHRI 340/360 Federal Minimum IEER
Water source (cooling mode) ≥ 65,000 Btu/h and < 135,000 Btu/h 86°F entering water Federal Minimum EER ISO-13256-1
Groundwater source (cooling mode) ≥ 135,000 Btu/h 59°F entering water 18.0 EER ISO-13256-1
Ground source (cooling mode) ≥ 135,000 Btu/h 77°F entering water 14.1 EER ISO-13256-1
Water source
water-to-water  (cooling mode)
≥ 135,000 Btu/h 86°F entering water 10.6 EER ISO-13256-2
Groundwater source water-to-water (cooling mode) ≥ 135,000 Btu/h 59°F entering water 16.3 EER ISO-13256-2
Ground source brine-to-water (cooling mode) ≥ 135,000 Btu/h 77°F entering water 12.1 EER ISO-13256-2
Air Cooled (Heating Mode) Split system and single package ≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) 47° F db/43° F wb outdoor air Federal Minimum COP AHRI 340/360

(CONTINUED) TABLE 110.2-B HEAT PUMPS, MINIMUM EFFICIENCY REQUIREMENTS
Equipment Type Size Category Rating Condition Efficiency* Test Procedure*
Air Cooled (Heating Mode) Split system and single package ≥ 65,000 Btu/h and < 135,000 Btu/h (cooling capacity) 17° F db/15° F wb outdoor air 2.25 COP AHRI 340/360
Air Cooled (Heating Mode) Split system and single package ≥ 135,000 Btu/h and < 240,000 Btu/h (cooling capacity) 47° F db/43° F wb outdoor air Federal Minimum COP AHRI 340/360
Air Cooled (Heating Mode) Split system and single package ≥ 240,000 Btu/h and < 760,000 Btu/h 47° F db/43° F wb outdoor air Federal Minimum COP AHRI 340/360
Air Cooled (Heating Mode) Split system and single package ≥ 135,000 Btu/h (cooling capacity) 17° F db/15° F wb outdoor air 2.05 COP AHRI 340/360
Water source (heating mode) < 135,000 Btu/h (cooling capacity) 68°F entering water Federal Minimum COP ISO-13256-1
Water source (heating mode) ≥ 135,000 Btu/h and < 240,000 Btu/h 68°F entering water Federal Minimum COP ISO-13256-1
Groundwater source (heating mode) < 135,000 Btu/h (cooling capacity) 50°F entering water 3.7 COP ISO-13256-1
Ground source (heating mode) < 135,000 Btu/h (cooling capacity) 32°F entering water 3.2 COP ISO-13256-1
Water source water-to-water (heating mode) < 135,000 Btu/h (cooling capacity) 68°F entering water 3.7 COP ISO-13256-2
Groundwater source water-to-water (heating mode) < 135,000 Btu/h (cooling capacity) 50°F entering water 3.1 COP ISO-13256-2
Ground source brine-to-water (heating mode) < 135,000 Btu/h (cooling capacity) 32°F entering water 2.5 COP ISO-13256-2


a Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat.

b Applicable test procedure and reference year are provided under the definitions


TABLE 110.2-C AIR-COOLED GAS-ENGINE HEAT PUMP


Equipment Type Size Category Subcategory or Rating Condition Efficiency Test Procedurea
Air-Cooled Gas-Engine Heat Pump
(Cooling Mode)
All Capacities 95°F db Outdoor Air 0.60 COP ANSI Z21.40.4A
Air-Cooled Gas-Engine Heat Pump
(Heating Mode)
All Capacities 47°F db/43°F wb Outdoor Air 0.72 COP ANSI Z21.40.4A

a Applicable test procedure and reference year are provided under the definitions.


TABLE 110.2-D WATER CHILLING PACKAGES – MINIMUM EFFICIENCY REQUIREMENTS


Equipment Type Size Category Path A Efficiency a,c Path B Efficiency a,c Test Procedure c
Air Cooled, With Condenser Electrically Operated <150 Tons ≥10.100 EER
≥ 13.700 IPLV
≥9.700 EER
≥ 15,000 IPLV
AHRI 550/590
Air Cooled, With Condenser Electrically Operated ≥150 Tons ≥10.100 EER
≥14.000 IPLV
≥9.700 EER
≥16.100 IPLV
AHRI 550/590
Air Cooled, Without Condenser Electrically Operated All Capacities Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements. Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements. AHRI 550/590
Water Cooled, Electrically Operated, Reciprocating All Capacities Reciprocating units must comply with the water-cooled positive displacement efficiency requirements. Reciprocating units must comply with the water-cooled positive displacement efficiency requirements. AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement <75 Tons ≥0.750kW/ton
≤0.600 IPLV
≥0.780 kW/ton
≤0.500 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement ≥75 tons and
<150 tons
≥0.720 kW/ton
≤0.560 IPLV
≥0.750 kW/ton
≤0.490 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement ≥150 tons and
<300 tons
≥0.660 kW/ton
≤0.540 IPLV
≥0.680 kW/ton
≤0.440 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement ≥300 Tons
and <600 tons
≥0.610kW/ton
≤0.520 IPLV
≥0.625 kW/ton
≤0.410 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement ≥600 Tons ≥0.560 kW/ton
≤0.500 IPLV
≥0.585 kW/ton
≤0.380 IPLV
AHRI 550/590


CONTINUED: TABLE 110.2-D WATER CHILLING PACKAGES – MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type

Size Category

Path A Efficiency a,b

Path B Efficiency a,b

Test Procedure c

Water Cooled, Electrically Operated, Centrifugal

< 150 Tons

≤ 0.610 kW/ton

≤ 0.550IPLV

≤ 0.695 kW/ton

≤ 0.440 IPLV

AHRI 550/590

Water Cooled, Electrically Operated,

Centrifugal

≥ 150 tons and

< 300 tons

≤ 0.610 kW/ton

≤ 0.550 IPLV

≤ 0.635 kW/ton

≤ 0.400 IPLV

AHRI 550/590

Water Cooled, Electrically Operated,

Centrifugal

≥ 300 tons and

< 400 tons

≤ 0.560 kW/ton

≤ 0.520 IPLV

≤ 0.595 kW/ton

≤ 0.390 IPLV

AHRI 550/590

Water Cooled, Electrically Operated, Centrifugal

≥ 400 tons and

< 600 tons

≤ 0.560 kW/ton

≤ 0.500 IPLV

≤ 0.585 kW/ton

≤ 0.380 IPLV

AHRI 550/590

Water Cooled, Electrically Operated,

Centrifugal

≥ 600 tons

≤ 0.560 kW/ton

≤ 0.500 IPLV

≤ 0.585 kW/ton

≤ 0.380 IPLV

AHRI 550/590

Air Cooled Absorption,

Single Effect

All Capacities

≥0.600 COP

N.A. d

AHRI 560

Water Cooled Absorption, Single Effect

All Capacities

≥ 0.700 COP

N.A. d

AHRI 560

Absorption Double Effect, Indirect-Fired

All Capacities

≥ 1.000 COP

≥ 1.050 IPLV

N.A. d

AHRI 560

Absorption Double Effect, Direct-Fired

All Capacities

≥ 1.000 COP

≥1.000 IPLV

N.A. d

AHRI 560

Water Cooled Gas Engine Driven Chiller

All Capacities

≥ 1.2 COP

≥ 2.0 IPLV

N.A. d

ANSI Z21.40.4A


a No requirements for:

  1. Centrifugal chillers with design leaving evaporator temperature < 36°F; or
  2. Positive displacement chillers with design leaving fluid temperature ≤ 32°F; or
  3. Absorption chillers with design leaving fluid temperature < 40°F.

b Must meet the minimum requirements of Path A or Path B. However, both the full load (COP) and IPLV must be met to fulfill the requirements of the applicable Path.

c See Section 100.1 for definitions.

d N.A. means not applicable.



TABLE 110.2-E PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT
Equipment Type Total System Heat Rejection Capacity at Rated Conditions Subcategory or Rating Condition Performance Requireda, b, c, d Test Proceduree
Propeller or axial fan Open-circuit cooling towers
All
95°F entering water
85°F leaving water
75°F entering air wb
≥ 42.1 gpm/hp

CTI ATC-105

and

CTI STD-201

RS


Centrifugal fan Open-circuit cooling towers
All

95°F entering water

85°F leaving water

75°F entering air wb

≥ 20.0 gpm/hp

CTI ATC-105

and

CTI STD-201

RS

Propeller or axial fan closed-circuit cooling towers All 102°F entering water
90°F leaving water
75°F entering air wb
≥ 16.1 gpm/hp CTI ATC-105S
and
CTI STD-201
RS
Centrifugal fan closed-circuit cooling towers All 102°F entering water
90°F leaving water
75°F entering air wb
≥ 7.0 gpm/hp CTI ATC-105S
and
CTI STD-201
RS
Propeller or axial fan evaporative condensers All R-448A test fluid
165°F entering gas temp
105°F condensing temp
75°F entering air wb
≥ 157,000
Btu/h • hp
CTI ATC-106
Propeller or axial fan evaporative condensers All Ammonia test fluid
140°F entering gas temp
96.3°F condensing temp
75°F entering air wb
≥ 134,000
Btu/h • hp
CTI ATC-106
Centrifugal fan evaporative condensers All R-448A test fluid
165°F entering gas temp
105°F condensing temp
75°F entering air wb
≥ 135,000
Btu/h • hp
CTI ATC-106

(CONTINUED) TABLE 110.2-E PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT
Equipment Type Total System Heat Rejection Capacity at Rated Conditions Subcategory or Rating Condition Performance Requireda, b, c, d Test Proceduree
Centrifugal fan evaporative condensers All Ammonia test fluid
140°F entering gas temp
96.3°F condensing temp
75°F entering air wb
≥ 110,000
Btu/h · hp
CTI ATC-106
Air cooled condensers All 125°F condensing temperature
190°F entering gas temperature
15°F subcooling
95°F entering drybulb
≥ 176,000 Btu/h · hp AHRI 460
Propeller or axial fan dry coolers (air-cooled fluid coolers) All 115°F entering water
105°F leaving water
95°F entering air db
> 4.5 gpm/hp CTI ATC-105DS



a For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the given rated conditions divided by the fan motor nameplate power.

b For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the given rated conditions divided by the sum of the fan motor nameplate rated power and the integral spray pump motor nameplate power.

c For purposes of this table dry cooler performance is defined as the process water flow rating of the unit at the given thermal rating condition divided by the total fan motor nameplate power of the unit and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power of the unit.

d Open cooling towers shall be tested using the test procedures in CTI ATC-105. Performance of factory assembled open cooling towers shall be either certified as base models as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency. Open factory assembled cooling towers with custom options added to a CTI certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the associated base model or at the manufacturer’s stated performance, whichever is less. Base models of open factory assembled cooling towers are open cooling towers configured in exact accordance with the Data of Record submitted to CTI as specified by CTI STD-201. There are no certification requirements for field erected cooling towers.

e Applicable test procedure and reference year are provided under the definitions. For refrigerated warehouses or commercial refrigeration applications, condensers shall comply with requirements specified by Section 120.6(a) or Section 120.6(b).


TABLE 110.2-F Electrically Operated Variable Refrigerant Flow (VRF) Air Conditioners Minimum Efficiency Requirements


Equipment Type Size Category Heating Section Type Sub-Category or Rating Condition Minimum Efficiency Test Procedure*
VRF Air Conditioners, Air Cooled <65,000 Btu/h All VRF Multi-split System 13.0 SEER Before 1/1/2023
Federal Minimum SEER2 On or After 1/1/2023
AHRI 1230 Before 1/1/2023
AHRI 210/240 On or After 1/1/2023
VRF Air Conditioners, Air Cooled ≥65,000 Btu/h and <135,000 Btu/h Electric Resistance (or none) VRF Multi-split System 10.5 EER
Federal Minimum IEERb
AHRI 1230
VRF Air Conditioners, Air Cooled ≥135,000 Btu/h and <240,000 Btu/h Electric Resistance (or none) VRF Multi-split System 10.3 EER
Federal Minimum IEERb
AHRI 1230
VRF Air Conditioners, Air Cooled ≥240,000 Btu/h Electric Resistance (or none) VRF Multi-split System 9.5 EER
Federal Minimum IEERb
AHRI 1230

a Applicable test procedure and reference year are provided under the definitions.

b IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.


TABLE 110.2-G Electrically Operated Variable Refrigerant Flow (VRF) Air Conditioners Minimum Efficiency Requirements

Equipment Type Size Category Heating Section Type Sub-Category or Rating Condition Minimum Efficiency Test Procedure*
VRF Air Cooled, (cooling mode) <65,000 Btu/h All VRF Multi-split System 13.0 SEER Before 1/1/2023
Federal Minimum = SEER2 On or after 1/1/2023
AHRI 1230 Before 1/1/2023
AHRI 210/240 On or After 1/1/2023
VRF Air Cooled, (cooling mode) ≥65,000 Btu/h and <135,000 Btu/h Electric Resistance (or none) VRF Multi-split System* 10.3 EER
Federal Minimum IEER
AHRI 1230
VRF Air Cooled, (cooling mode) ≥135,000 Btu/h and <240,000 Btu/h Electric Resistance (or none) VRF Multi-split System* 9.9 EER
Federal Minimum IEER
AHRI 1230
VRF Air Cooled, (cooling mode) ≥240,000 Btu/h Electric Resistance (or none) VRF Multi-split System* 9.1 EER
Federal Minimum IEER
AHRI 1230
VRF Water source (cooling mode) <65,000 Btu/h All VRF Multi-split System*
86°F entering water
12.0 EER
Federal Minimum IEER
AHRI 1230
VRF Water source (cooling mode) ≥65,000 Btu/h and <135,000 Btu/h All VRF Multi-split System*
86°F entering water
12.0 EER
Federal Minimum IEER
AHRI 1230
VRF Water source (cooling mode) ≥135,000 Btu/h and < 240,000 All VRF Multi-split System*
86°F entering water
10.0 EER
Federal Minimum IEER
AHRI 1230
VRF Water source (cooling mode) ≥ 240,000 Btu/h All VRF Multi-split System* 86°F entering water 10.0 EER
Federal Minimum IEER
AHRI 1230

TABLE 110.2-G Electrically Operated Variable Refrigerant Flow (VRF) Air Conditioners Minimum Efficiency Requirements

(CONTINUED) TABLE
Equipment Type Size Category Heating Section Type Sub-Category or Rating Condition Minimum Efficiency Test Procedure*
VRF Groundwater source (cooling mode) <135,000 Btu/h All VRF Multi-split System *
59°F entering water
16.2 EER AHRI 1230
VRF Groundwater source (cooling mode) ≥135,000 Btu/h All VRF Multi-split System *
59°F entering water
13.8 EER AHRI 1230
VRF Ground source (cooling mode) <135,000 Btu/h All VRF Multi-split System *
77°F entering water
13.4 EER AHRI 1230
VRF Ground source (cooling mode) ≥135,000 Btu/h All VRF Multi-split System *
77°F entering water
11.0 EER AHRI 1230
VRF Air Cooled (heating mode) <65,000 Btu/h
(cooling capacity)
--- VRF Multi-split System 7.7 HSPF Before 1/1/2025
7.5 HSPF2 On or after 1/1/2025
AHRI 1230 Before 1/1/2025
AHRI 210/240 On or After 1/1/2025
VRF Air Cooled (heating mode) ≥65,000 Btu/h
and
<135,000 Btu/h
(cooling capacity)
--- VRF Multi-split system
47°F db/ 43°F wb outdoor air
Federal Minimum COP AHRI 1230
VRF Air Cooled (heating mode) ≥65,000 Btu/h
and
<135,000 Btu/h
(cooling capacity)
--- VRF Multi-split system
17°F db/ 15°F wb outdoor air
2.25 COP AHRI 1230


CONTINUED: TABLE 110.2-G Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency Requirements

Equipment Type

Size Category

Heating Section Type

Sub-Category or Rating Condition

Minimum Efficiency

Test Procedure b

VRF Air Cooled (heating mode)

≥135,000 Btu/h (cooling capacity)

---

VRF Multi-split system

17ºF db/15ºF wb outdoor air

 2.05 COP

AHRI 1230

VRF Water source (heating mode)

< 65,000 Btu/h (cooling capacity)

---

VRF Multi-split System 68oF entering water

Federal Minimum COP

AHRI 1230

VRF Water source (heating mode)

≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)

---

VRF Multi-split System

68ºF entering water

 

Federal Minimum COP

AHRI 1230

VRF Water source (heating mode)

≥135,000 Btu/h and < 240,000 Btu/h (cooling capacity)

---

VRF Multi-split System

68ºF entering water

 

Federal Minimum COP

AHRI 1230

VRF Water source (heating mode)

≥ 240,000 Btu/h

(cooling capacity)

---

VRF Multi-split System 

68oF entering water

Federal Minimum COP

AHRI 1230

VRF Groundwater source (heating mode)

<135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

50ºF entering water

3.6 COP

AHRI 1230

VRF Groundwater source (heating mode)

≥135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

50ºF entering water

3.3 COP

AHRI 1230

VRF Ground source (heating mode)

<135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

32ºF entering water

3.1 COP

AHRI 1230

VRF Ground source (heating mode)

≥135,000 Btu/h

(cooling capacity)

---

VRF Multi-split System

32ºF entering water

2.8 COP

AHRI 1230

a.    Deduct 0.2 from the required EERs and IEERs for Variable Refrigerant Flow (VRF) Multi-split system units with a heating recovery section.

b.    Applicable test procedure and reference year are provided under the definitions.

c.    IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.


TABLE 110.2-H DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements

Equipment Type Energy Recovery Subcategory or Rating Condition Minimum Efficiency Test Procedure
Air cooled (dehumidification mode) Without energy recovery NA 3.8 ISMRE2 AHRI 920
Air source heat pumps (dehumidification mode) Without energy recovery NA 3.8 ISMRE2 AHRI 920
Water cooled (dehumidification mode) Without energy recovery Cooling Tower Condenser Water 4.7 ISMRE2 AHRI 920
Water source heat pump (dehumidification mode) Without energy recovery Ground source, closed and open loop 4.6 ISMRE2 AHRI 920
Water source heat pump (dehumidification mode) Without energy recovery Water source 3.8 ISMRE2 AHRI 920
Air source heat pumps (heating mode) Without energy recovery NA 2.05 ISCOP2 AHRI 920
Water source heat pump (heating mode) Without energy recovery Ground source, closed and open loop 2.13 ISCOP2 AHRI 920
Water source heat pump (heating mode) Without energy recovery Water source 2.13 ISCOP2 AHRI 920
Air cooled (dehumidification mode) With energy recovery NA 5.0 ISMRE2 AHRI 920
Air source heat pumps (dehumidification mode) With energy recovery NA 5.0 ISMRE2 AHRI 920


CONTINUED: TABLE 110.2-H DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements
Equipment Type Energy Recovery Subcategory or Rating Condition Minimum Efficiency Test Procedure*
Water cooled (dehumidification mode) With energy recovery Cooling tower condenser water 5.1 ISMRE2 AHRI 920
Water source heat pump (dehumidification mode) With energy recovery Ground source, closed and open loop 5.0 ISMRE2 AHRI 920
Water source heat pump (dehumidification mode) With energy recovery Water source 4.6 ISMRE2 AHRI 920
Air source heat pumps (heating mode) With energy recovery 3.2 ISCOP2 AHRI 920
Water source heat pump (heating mode) With energy recovery Ground source, closed and open loop 3.5 ISCOP2 AHRI 920
Water source heat pump (heating mode) With energy recovery Water source 4.04 ISCOP2 AHRI 920

a Applicable test procedure and reference year are provided under the definitions.






TABLE 110.2-I Heat Pump and Heat Recovery Chiller Packages, Cooling Operation Minimum Efficiency Requirements

Equipment Type Size Category Refrigerating Capacitya, tonR Cooling Operation Efficiencyb,c,d, e, Air Source EER (FL/IPLV), Btu/W h, Liquid Source Power Input per
Capacity (FL/IPLV), kW/tonR

Cooling Operation Efficiencyb,c,d, e Air Source EER (FL/IPLV), Btu/W h, Liquid Source Power Input per
 Capacity (FL/IPLV), kW/tonR

Test Procedure
Air Source < 150 > 5.595 FL
> 13.02 IPLV.IP
> 9.215 FL
> 15.01 IPLV.IP
AHRI/550/590
Air Source > 150 > 5.595 FL
> 13.30 IPLV.IP
> 9.215 FL
> 15.30 IPLV.IP
AHRI/550/590
Liquid source electrically operated positive displacement > 11.25f and < 150 < 0.7895 FL
< 0.6316 IPLV.IP
< 0.8211 FL
< 0.5263 IPLV.IP
AHRI/550/590
Liquid source electrically operated positive displacement > 150 and < 300 < 0.7579 FL
< 0.5895 IPLV.IP
< 0.7895 FL
< 0.5158 IPLV.IP
AHRI/550/590
Liquid source electrically operated positive displacement > 300 and < 400 < 0.6947 FL
< 0.5684 IPLV.IP
< 0.7158 FL
< 0.4632 IPLV.IP
AHRI/550/590
Liquid source electrically operated positive displacement > 400 and < 600 < 0.6421 FL
< 0.5474 IPLV.IP
< 0.6579 FL
< 0.4316 IPLV.IP
AHRI/550/590
Liquid source electrically operated positive displacement > 600 < 0.5895 FL
< 0.5263 IPLV.IP
< 0.6158 FL
< 0.4000 IPLV.IP
AHRI/550/590
Liquid source electrically operated centrifugal > 11.25f and < 150 < 0.6421 FL
< 0.5789 IPLV.IP
< 0.7316 FL
< 0.4632 IPLV.IP
AHRI/550/590
Liquid source electrically operated centrifugal > 150 and < 300 < 0.6190 FL
< 0.5748 IPLV.IP
< 0.6684 FL
< 0.4211 IPLV.IP
AHRI/550/590
Liquid source electrically operated centrifugal > 300 and < 400 < 0.5895 FL
< 0.5526 IPLV.IP
< 0.6263 FL
< 0.4105 IPLV.IP
AHRI/550/590
Liquid source electrically operated centrifugal > 400 and < 600 < 0.5895 FL
< 0.5263 IPLV.IP
< 0.6158 FL
< 0.4000 IPLV.IP
AHRI/550/590
Liquid source electrically operated centrifugal > 600 < 0.5895 FL
< 0.5263 IPLV.IP
< 0.6158 FL
< 0.4000 IPLV.IP
AHRI/550/590

a.    The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chilling package.

b.    Cooling rating conditions are standard rating conditions defined in AHRI 550/590 (I-P), Table 4, except for liquid cooled centrifugal chilling packages which can adjust cooling efficiency for nonstandard rating conditions using Kadj procedure in accordance with Section 110.2(a).

c.    For cooling operation, compliance with both the FL and IPLV is required, but only compliance with Path A or Path B cooling efficiency is required.

d.    For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.

e.    For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c.

f.    Water to water heat pumps with capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.


TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements Equipment Type: Air Source

Equipment Type: Air Source

Size Category Refrigerating Capacitya, TonR, Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
< 150 47 db
43 wb
> 3.29 > 2.77 > 2.31 N/A AHRI 550/590
< 150
17 db
15 wb
> 2.029 > 1.775 > 1.483 N/A AHRI 550/590
> 150 47 db
43 wb
> 3.29 > 2.77 > 2.31 N/A AHRI 550/590
> 150 17 db
15 wb
> 2.029 > 1.775 > 1.483 N/A AHRI 550/590

(CONTINUED) TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements

Equipment Type: Liquid source electrically operated positive displacement


Size Category Refrigerating Capacitya, TonR, Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
11.25h and < 150 44 > 4.64 > 3.68 > 2.68 NA AHRI 550/590
11.25h and < 150
65 NA NA NA > 3.55 AHRI 550/590
> 150 and < 300 44 > 4.64 > 3.68 > 2.68 NA AHRI 550/590
> 150 and < 300 65 NA NA NA > 3.55 AHRI 550/590
> 300 and < 400 44 > 4.64 > 3.68 > 2.68 NA AHRI 550/590
> 300 and < 400 65 NA NA NA > 3.55 AHRI 550/590
> 400 and < 600 44 > 4.93 > 3.96 > 2.97 NA AHRI 550/590
> 400 and < 600 65 NA NA NA > 3.9 AHRI 550/590
> 600 44 > 4.93 > 3.96 > 2.97 NA AHRI 550/590
> 600 65 NA NA NA > 3.9 AHRI 550/590

(CONTINUED) TABLE 110.2-J Heat Pump and Heat Recovery Chiller Packages, Heat Pump, Heating Operation– Minimum Efficiency Requirements

Equipment Type: Liquid source electrically operated centrifugal


Size Category Refrigerating Capacitya, TonR, Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Heat Pump Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
> 11.25h and < 150
44° > 4.64 > 3.68 > 2.68 NA AHRI 550/590
> 11.25h and < 150 44° NA NA NA > 3.55 AHRI 550/590
> 150 and < 300 44° > 4.64 > 3.68 > 2.68 NA AHRI 550/590
> 150 and < 300 65° NA NA NA > 3.55 AHRI 550/590
> 300 and < 400 44° > 4.64 > 3.68 > 2.68 NA AHRI 550/590
> 300 and < 400 65° NA NA NA > 3.55 AHRI 550/590
> 400 and < 600 44° > 4.93 > 3.96 > 2.97 NA AHRI 550/590
> 400 and < 600 65° NA NA NA > 3.9 AHRI 550/590
> 600 44° > 4.93 > 3.96 > 2.97 NA AHRI 550/590
> 600 65° NA NA NA > 3.9 AHRI 550/590

a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chilling package.

b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating.

c. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.

d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.

e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I.

f. For applications where the chilling package is installed to operate only in heating, compliance only with the heating performance COPH is required at only one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with cooling performance is not required.

g. For heat pump chilling package applications where the cooling capacity is not being used for conditioning, compliance with the heating performance COPH is only required at one of the heating AHRI 550/590 (I-P) standard rating conditions of Low, Medium, High, or Boost. Compliance with the cooling performance is required as defined in footnotes b and c of Table 110.2-I, except as noted in footnote f.

h. Water to water heat pumps with capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.

i. Source leaving liquid temperature.

  • 1. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.
  • 2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.
  • 3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used.

j. NA means the requirements are not applicable.

TABLE 110.2-K DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements

Equipment Type: Air Source


Size Category Refrigerating Capacitya, TonR, Simultaneous Cooling and Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
< 150 47 db
43 wb
NAj NAj NAj NAj AHRI 550/590
< 150 17 db
15 wb
NAj NAj NAj NAj AHRI 550/590
> 150 47 db
43 wb
NAj NAj NAj NAj AHRI 550/590
> 150 17 db
15 wb
NAj NAj NAj NAj AHRI 550/590

(CONTINUED) TABLE 110.2-K DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements

Equipment Type: Liquid source electrically operated positive displacement


Size Category Refrigerating Capacitya, TonR, Simultaneous Cooling and Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
> 11.25h and < 150 44 > 8.33 > 6.41 > 4.42 NA AHRI 550/590
> 11.25h and < 150 65 NA NA NA > 6.150 AHRI 550/590
> 150 and < 300 44 > 8.33 > 6.41 > 4.42 NA AHRI 550/590
> 150 and < 300 65 NA NA NA > 6.150 AHRI 550/590
> 300 and < 400 44 > 8.33 > 6.41 > 4.42 NA AHRI 550/590
> 300 and < 400 65 NA NA NA > 6.150 AHRI 550/590
> 400 and < 600 44 > 8.9 > 6.98 > 5 NA AHRI 550/590
> 400 and < 600 65 NA NA NA > 6.85 AHRI 550/590
> 600 44 > 8.9 > 6.98 > 5 NA AHRI 550/590
> 600 65 NA NA NA > 6.85 AHRI 550/590

(CONTINUED) TABLE 110.2-K DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements

Equipment Type: Liquid source electrically operated centrifugal


Size Category Refrigerating Capacitya, TonR, Simultaneous Cooling and Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Simultaneous Cooling and Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
< 11.25h and < 150 44i > 8.33 > 6.41 > 4.42 NAj AHRI 550/590
> 11.25h and < 150 65i NAj NAj NAj > 6.150 AHRI 550/590
> 150 and < 300 44i > 8.33 > 6.41 > 4.42 NAj AHRI 550/590
> 150 and < 300 65i NAj NAj NAj > 6.150 AHRI 550/590
> 300 and < 400 44i > 8.33 > 6.41 > 4.42 NAj AHRI 550/590
> 300 and < 400 65i NAj NAj NAj > 6.150 AHRI 550/590
> 400 and < 600 44i > 8.9 > 6.98 > 5 NAj AHRI 550/590
> 400 and < 600 65i NAj NAj NAj > 6.85 AHRI 550/590
> 600 44i > 8.9 > 6.98 > 5 NAj AHRI 550/590
> 600 65i NAj NAj NAj > 6.85 AHRI 550/590

a. The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chilling package.

b. For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating.

c. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.

d. For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.

e. For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot- Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I.

f. Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.

g. For simultaneous cooling and heating chillers applications where there is simultaneous cooling and heating, compliance with the simultaneous cooling performance heat recovery COPSHC is only required at one of the heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, High, or Boost. Compliance with cooling performance is required as defined in footnotes b and c of Table 110.2-I.

h. Water to water heat pumps with capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.

i. Source leaving liquid temperature.

  • 1. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.
  • 2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.
  • 3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used.

j. NA means the requirements are not applicable.


TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements

Equipment Type: Air Source


Size Category Refrigerating Capacitya, TonR, Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
< 150 47 db,
43 wb
NA NA NA NA AHRI 550/590
< 150 17 db,
15 wb
NA NA NA NA AHRI 550/590
> 150 47 db,
43 wb
NA NA NA NA AHRI 550/590
< 150 17 db,
15 wb
NA NA NA NA AHRI 550/590

(CONTINUED) TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements

Equipment Type: Liquid source electrically operated positive displacement


Size Category Refrigerating Capacitya, TonR, Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
> 11.25h and < 150 44° > 8.33 > 6.41 > 4.862 > 4.42 AHRI 550/590
> 11.25and < 150 65° N/A N/A N/A N/A AHRI 550/590
> 150 and < 300 44° > 8.33 > 6.41 > 4.862 > 4.42 AHRI 550/590
> 150 and < 300 65° N/A N/A N/A N/A AHRI 550/590
> 300 and < 400 44° > 8.33 > 6.41 > 4.862 > 4.42 AHRI 550/590
> 300 and < 400 65° N/A N/A N/A N/A AHRI 550/590
> 400 and < 600 44° > 8.9 > 6.98 > 5.5 > 5 AHRI 550/590
> 400 and < 600 65° N/A N/A N/A N/A AHRI 550/590
> 600 44° > 8.9 > 6.98 > 5.5 > 5 AHRI 550/590
> 600 65° N/A N/A N/A N/A AHRI 550/590

(CONTINUED) TABLE 110.2-L Heat Pump and Heat Recovery Chiller Packages, Heat Recovery, Heating Operation– Minimum Efficiency Requirements

Equipment Type: Liquid source electrically operated centrifugal


Size Category Refrigerating Capacitya, TonR, Heating Source Conditions (leaving liquid) or OAT (db/wb)b °F Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Low, 95 F/105 F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Medium, 105°F/120°F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, High, 120°F/140°F
Heat Recovery Heating Full Load Heating Efficiency (COPH)c,d,e,f,g, W/W, Entering/Leaving Heating
Liquid Temperature, Boost, 120°F/140°F
Test Procedure
> 11.25h and < 150 44° > 8.33 > 6.41 > 4.862 > 4.42 AHRI 550/590
> 11.25h and < 150 65° N/A N/A N/A N/A AHRI 550/590
> 150 and ≤ 300 44° > 8.33 > 6.41 > 4.862 > 4.42 AHRI 550/590
> 150 and ≤ 300 65° N/A N/A N/A N/A AHRI 550/590
> 300 and ≤ 400 44° > 8.33 > 6.41 > 4.862 > 4.42 AHRI 550/590
> 300 and ≤ 400 65° N/A N/A N/A N/A AHRI 550/590
> 400 and ≤ 600 44° > 8.9 > 6.98 > 5.5 > 5 AHRI 550/590
> 400 and ≤ 600 65° N/A N/A N/A N/A AHRI 550/590
> 600 44° > 8.9 > 6.98 > 5.5 > 5 AHRI 550/590
> 600 65° N/A N/A N/A N/A AHRI 550/590


a.    The size category is the full-load net refrigeration cooling mode capacity, which is the capacity of the evaporator available for cooling of the thermal load external to the chilling package.

b.    For air source heat pumps, compliance with both the 47 F and 17 F heating source outdoor air temperature (OAT) rating efficiency is required for heating.

c.    Heating full load rating conditions are at standard rating conditions defined in AHRI 550/590 (I-P), Table 4, includes the impact of defrost for air source heating ratings.

d.    For units that operate in both cooling and heating, compliance with both the cooling and heating efficiency is required.

e.    For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I.

f.    For liquid source heat recovery chilling packages that have capabilities for heat rejection to a heat recovery condenser and a tower condenser the COPHR applies to operation at full load with 100 percent heat recovery (no tower rejection). Units that only have capabilities for partial heat recovery shall meet the requirements of Table 110.2-D Water Chilling Packages Minimum Efficiency.

g.    For heat recovery heating chilling package applications where there is simultaneous cooling and heating, compliance with the heating performance heat recover COPHR is only required at one of the four heating AHRI 550/590 (I-P) standard ratings conditions of Low, Medium, Hot-Water 1 or Hot-Water 2. Compliance with the cooling only performance is required as defined in footnotes b and c of Table 110.2-I.

h.    Water to water heat pumps with capacity less than 135,000 Btu/h are included in Table 110.2-B Heat Pumps, Minimum Efficiency Requirements.

i.    Source leaving liquid temperature.

  1. The cooling evaporator liquid flow rate used for the heating rating for a reverse cycle air to water heat pump shall be the flow rate determined during the full load cooling rating.
  2. The cooling evaporator liquid flow rate for the simultaneous cooling and heating and heat recovery liquid cooled chilling packages rating shall be the liquid flow rates from the cooling operation full load rating.
  3. For heating only fluid to fluid chiller packages, the evaporator flow rate obtained with an entering liquid temperature of 54 F and a leaving liquid temperature of 44 F shall be used.

j.    NA means the requirements are not applicable.

Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code 


This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2025 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.