NA6.2 Default U-factor

Equation NA6-1

UT= C1 + (C2 X Uc)

Where:

UT = U-factor Is the Total Performance of the fenestration including glass and frame

C1 = Coefficient selected from Table NA6-6

C2 = Coefficient selected from Table NA6-6

UC = Center of glass U-factor calculated in accordance with NFRC 100 Section 4.5.3.1 (http://www.nfrc.org/software.aspx)

Table NA6-6 – U-factor Coefficients

Product Type
Frame Type
C 1
C 2
Site-Built Vertical Fenestration
Metal
0.311
0.872
Site-Built Vertical Fenestration
Metal Thermal Break
0.202
0.867
Site-Built Vertical Fenestration
Non-Metal
0.202
0.867
Skylights with a Curb
Metal
0.711
1.065
Skylights with a Curb
Metal Thermal Break
0.437
1.229
Skylights with a Curb
Non-Metal
0.437
1.229
Skylights with no Curb
(Deck Mounted)
Metal
0. 310
0. 878
Skylights with no Curb
(Deck Mounted)
Metal Thermal Break
0. 195
0. 882
Skylights with no Curb
(Deck Mounted)
Non-Metal
0.310
0.878

This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2024 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.