9.6   Alterations

This section provides a road map and a few relevant summaries that identify the Standards requirements which are unique to alterations. Envelope, mechanical and water heating system alterations must meet all applicable mandatory measures as discussed in Section 9.3; and also must comply with the Standards using the prescriptive or performance approach.  If a building does not meet all applicable prescriptive measures, see Section 9.5.1), then the performance method using of approved compliance software is the alternative, see Section 9.5.2.

Residential lighting alterations need to meet applicable mandatory measures discussed in Section 9.3.3 since there are no prescriptive lighting requirements in residential buildings.

9.6.1    Prescriptive Requirements

Although alterations must meet many of the same prescriptive requirements for new construction and additions, there are several exceptions or special allowances for certain types of alterations.  Table 9-5A provides a detailed outline of envelope requirements for alterations; and Table 9-5B provides a similar outline for HVAC and water heating alterations.  For each type of alteration, the tables list:

1.   The highlights of the mandatory measures applicable to that kind of alteration; and

2.   A summary of the relevant prescriptive measures; and

3.   Key exceptions, exemptions or special allowances to the prescriptive measures; and

4.   The list of prescriptive compliance forms that must be submitted for permit.

9.6.2    Prescriptive Envelope Alterations

Table 9-5A summarizes requirements for the following types of residential envelope alterations:

1.   Adding ceiling or roof insulation to an existing roof; or constructing a new roof on an existing building;

2.   Replacing the roof sheathing of an existing roof;

3.   Replacing part or all of  roof surface of the existing building;

4.   Replacing or adding skylights;

5.   Adding exterior wall insulation; or constructing new walls in an existing building;

6.   Adding raised floor insulation over unconditioned space;

7.   Replacing vertical fenestration: windows, clerestories and glazed doors;

8.   Adding vertical fenestration: windows, clerestories and glazed doors.

Table 9-5A: For Residential Alterations, Summary of Mandatory and Prescriptive Measures

Type of Envelope Alteration

Highlight(s) of Applicable         Mandatory

Measures1

Summary of Relevant Prescriptive Measure(s)2

Exception(s) to the                   Prescriptive Measures

Prescriptive Compliance   Form(s)

Adding Ceiling or Roof Insulation to an Existing Roof;

or a New Roof on an Existing Building

Ceiling w/ Attic:

R-30, U=0.031

CZ 1, 11-16:

R-38, U=0.025

N/A

CF1R-ALT

Roof Rafters:

R-19, U=0.056  §150.0(a)

CZ 2 -10:  R-30, U=0.0.031

Replacing Roof Sheathing

§110.8(j)

CZ 2 - 15: Radiant Barrier  above Attic Spaces

No requirement in

CZ1 and CZ16

CF1R-ALT

Replacing > 50% of the Existing Roof Surface

§110.8(i)

Steep Sloped

(> 2:12):
CZ 10 - 15: Reflect.=0.20 and Emittance=0.75;

or SRI=16

(a) Air space of 1.0" between roof deck and bottom of roofing product; or,

(b) Profile ratio of rise to width of 1:5 for >50% width of roofing product; or,

(c) Existing ducts in attic insulated and sealed per §150.1(c)9; or,
(d) Roof has > R-38 ceiling insulation; or,

(e) Roof has a radiant barrier per §150.1(c)2; or,
(f) There are no ducts in the attic; or,

(g) In CZ10-15, >R-4.0 insulation above the roof deck.

CF1R-ALT

Low Sloped< 2:12:
CZ13 & 15: Reflect.=0.63 and Emittance=0.75;

or SRI=75

(a) There are no ducts in the attic; or,

(b) Reflectance and Roof Deck Insulation R-value in Table
150.2-A are met.

CF1R-ALT

Adding or Replacing

Skylight3

Weighted average U-factor = or < 0.58
Exemption:  Up to 10 ft2 or 0.5% of Conditioned Floor Area, whichever is greater, is exempt from the U-factor requirement §150.0(q)

Must not exceed the 20% Total or 5% West Fenestration Area with a U-factor = 0.32 (all CZs);
in CZ2, 4 & 6-16: SHGC = 0.25
§150.2(b)1.A.

Added fenestration up to 75 ft2 need not meet Total or West-facing fenestration area as per §150.2(b)1A Exception 1.

 

Replacement skylights up to 16 ft2 with a U=0.55 and SHGC=0.30 and not meet the total fenestration and West-facing area requirements as per §150.2(b)1 A Exception 2.

CF1R-ALT

Adding Exterior Framed Wall Insulation3

or a New Wall
in an Existing Building

In 2x4 Framing: R-13, U=0.102

In 2x6 Framing: R-19, U=0.074
Exception: Walls already insulated to

R-11  §150.1(c)

In 2x4 Framing:

R-13, U=0.102

In 2x6 Framing:

R-19, U=0.074      (same as Mandatory)

N/A

CF1R-ALT

 

Table 9-5A: Residential Alterations, Summary of Mandatory and Prescriptive Measures (continued)

Type of Envelope Alteration

Highlight(s) of Applicable
 Mandatory

Measures1

Summary of Relevant Prescriptive Measure(s)2

Exception(s) to the
 Prescriptive Measures

Prescriptive Compliance   Form(s)

Adding Raised Floor Insulation

R-19 or equivalent

U-factor
Exception: Floors over controlled ventilation or unvented crawlspaces per
§150.0(d)

R-19 or equivalent U-factor

(same as Mandatory)

N/A

CF1R-ALT

Replacing Vertical Fenestration4
(Altered Glazing)

Weighted average
U-factor = or < 0.58
Exemption:  Up to 10 ft2 or 0.5% of Conditioned Floor Area, whichever is greater, is exempt from the U-factor requirement      §150.0(q).

All CZs:

U-factor = 0.32

CZ 2, 4 & 6-16: SHGC = 0.25
§150.2(b)1.B.

Replacement of vertical fenestration up to 75 ft2:

U=0.40 (in all CZs) and SHGC=0.35 in CZs 2, 4 & 6-16 as per §150.2(b)1B Exception 1 .

 

CF1R-ALT

Adding Vertical Fenestration4
 (New Glazing) and Greenhouse

Weighted average U-factor = or < 0.58
 Exemption:  Up to 10 ft2 or 0.5% of Conditioned Floor Area, whichever is greater, is exempt from the U-factor requirement §150.0(q).

Must not exceed the 20% Total or 5% West Fenestration Area.
U-factor = 0.32 (in all CZs);
In CZ2, 4 & 6-16: SHGC = 0.25
§150.2(b)1.A.

Added fenestration up to 75 ft2 need not meet total or west-facing fenestration area requirements as per §150.2(b)1A Exception 1 .

 

Added Greenhouse must either meet the maximum U-factor of  0.58 or weighted average U-factor of 0.58 or up to 10ft2 or 0.5% of CFA whichever is greater as per §150.0(q)1.

CF1R-AL

 1: Alterations must comply with all applicable mandatory measures in §110.0 and §150.0 of the Standards as explained in   Chapters 3, 4, 5 and 6 of this 'Manual.

2:  Several prescriptive measures are Climate Zone (CZ) specific.

3:  There are no mandatory measures or prescriptive requirements when altering below-grade or exterior mass walls.

4:  Replacement fenestration is new fenestration that is located in the same existing wall or roof in which the same or larger area of existing fenestration is being removed.  It labeled as "altered.  Any new fenestration area that increases the total net area of fenestration in any existing wall or roof is labeled as "new".


Greenhouse Windows

Greenhouse or garden windows are special windows that project from the façade of the building and are typically five sided structure. An NFRC-rated U-factor for greenhouse windows is typically quite high and may not meet the mandatory requirements for the fenestration U-factor of 0.58.

The ways to meet this mandatory measure for greenhouse windows are:

Must have a maximum U-factor of 0.58 or better; or

Use the area-weighted average for all new and replacement fenestration with a combined mandatory maximum of 0.58 U-factor as per §150.0(q)2; or

The Exception to §150.0(q)1 for up to 10 ft2 or 0.5% of CFA, whichever is greater; or

When using the performance approach Exception 1 as per §150.2(b) - Any dual-glazed greenhouse or garden window installed as part of an alteration complies automatically with the U-factor and meets the requirements as per §150.1(c)3.

9.6.3    Adding Insulation to Existing Roof/Ceilings, Walls and Raised Floors

The prescriptive requirement for alterations is to add the equivalent of the specified level of batt insulation that fits within the cavity of wood framed assemblies:

1.   R-38 in attic spaces in climate zones 1 and 11 through 16; and R-30 in attics in climate zones 2 through 10; or

2.   R-13 in 2x4 exterior walls, and R-19 in 2x6 or greater exterior walls; or

3.   R-19 in raised floors over crawl spaces, over open outdoor areas and over unheated basements and garages. 

9.6.4    Replacing the Roof Surface or Roof Sheathing

STEEP-SLOPED ROOFS (> 2:12)

In climate zones 10 through 15:  if 50% or more of the existing building’s roof surface is being replaced, the minimum cool roof requirement for the replaced steep-sloped roofing area is aged solar reflectance = 0.20, thermal emittance = 0.75 or a minimum SRI = 16. These apply unless any of the following is present which are considered equivalent to the cool roof requirements in §150.2(b)1Hi:

1.   Air space of 1.0" (25mm) between the roof deck and the bottom of the roofing product; or  

2.   Roofing product profile ratio of rise to width is at least 1:5 for >50% width of roofing product; or

cid:image001.jpg@01CDA58E.1B221550

3.   Existing ducts in attic insulated and sealed according to §150.1(c)9; or 

4.   Building has at least R-38 roof/ceiling insulation; or    

5.   Roof of attic spaces has a radiant barrier according to §150.1(c)2; or

6.   There are no ducts in any attic space; or

7.   In CZ10 through 15 only: greater than R-4.0 insulation above the roof deck.

LOW-SLOPED ROOFS (< 2:12)

In climate zones 13 and 15:  if 50% or more of the existing building’s roof surface is being replaced, the minimum cool roof requirements for low-sloped roofs are aged solar reflectance = 0.63, thermal emittance = 0.75 or a minimum SRI = 75 per §150.2(b)1Hii. These apply unless any of the following is present which are considered equivalent to the cool roof requirements in §150.2(b)1Hii:

1.   There are no ducts in any attic space; or

2.   The aged solar reflectance can be traded off with additional insulation being added  at the roof deck as specified in Table 150.2-A

 

Table 9-6 Aged Solar Reflectance Insulation Trade Off Table

Aged Solar Reflectance

Roof Deck
Insulation R-value

Aged Solar Reflectance

Roof Deck
 Insulation R-value

0.62 – 0.60

2

0.44 – 0.40

12

0.59 -0.55

4

0.39 – 0.35

16

0.54 - 0.50

6

0.34 – 0.30

20

0.49 – 0.45

8

0.29 – 0.25

24

 

ROOF SHEATHING

In climate zones 2 through 15: if roof sheathing over an attic space with a continuous radiant barrier is being replaced, a continuous radiant barrier must be re-installed.

9.6.5    Replacement Fenestration

If any fenestration (i.e. windows, skylights, clerestories, and glazed doors) that is being removed and replaced in an exterior wall or roof, it is considered “replacement fenestration”. 

Example 9-14

Question

An existing building, 50 ft2 of total 85 ft2 vertical glazing is being removed from an existing south wall and new glazing will be replaced as part of the alteration in the same opening. What requirements apply?

 

Answer

Since, 50 ft2 is treated as “replacement” fenestration and 35 ft2 is considered existing then the  replacement of fenestration must comply with the measures in §150.2(b)1B; or for this example Exception 1 can used. Vertical fenestration not greater than 75 ft2 can meet the measures by installing fenestration no greater than a U-factor of 0.40 and SHGC of 0.35.

Replacement fenestration is an area of new fenestration which replaces an equal or greater area of glazing removed in the same existing wall or roof area.  It is labeled as “altered” fenestration, and it need not occur in the same exact openings as the glazing being removed as long as it is being installed in the same existing wall or roof surface which remains a part of the existing building.  Any added fenestration area that is larger than the total altered glazing area) is labeled as “new”.

9.6.6    New Fenestration in Alterations

The 2013 Standards have relaxed some of the prescriptive restrictions on new vertical fenestration for alterations in existing dwellings.  When new vertical fenestration is added in existing dwellings, up to 75 square feet are not required to meet the overall total fenestrations limit (20 percent of the CFA) and the west-facing area limit (5 percent of the CFA).  This provides for additional flexibility to meet the Standards requirements using the prescriptive approach, without having to resort to the performance approach.  However, this additional fenestration must meet the prescriptive U-factor and SHGC requirements of Package A or meet the U-factor and SHGC requirements of Exceptions 1 and 2 to Section 150.2(b)1B.

 

Example 9-14

Question

An existing house in climate zone 12 has all single-pane windows. All of the windows will be replaced within existing openings, except a pair of 40 ft2 French doors to replace an existing 30 ft2 window. What requirements apply?

Answer

For prescriptive compliance, replacement fenestration (equal to or less than the area of existing windows in each wall being altered) and new additional fenestration area must both meet the U-factor (0.32) and SHGC (0.25) in Package A. The post-alteration total glazing area must be no greater than 20% of conditioned floor area, and all installed fenestration also must meet applicable mandatory measures.

In order to use the performance approach, at two or more energy measure must be used as a trade-off within the house per §150.2(b)2.  For example, if the homeowner is replacing the 1) water heater along with 2) window replacements, then the Existing + Alterations calculation is available as a compliance alternative.  In that case:

(a) In the Existing + Alterations approach without third party verification, replacement fenestration that achieves the fenestration values in Table 150.2-B is compared to those same values in the Standard Design.  Replacement fenestration that does not reach these values is penalized; or,\

b)  In the Existing + Alterations approach with third party verification, replacement fenestration that achieves the fenestration values in Table 150.2-B is compared to Tables 110.6-A and 110.6-B default values for the existing fenestration condition. Replacement fenestration that does not reach these values is penalized:

(c) New for the 2013 is the use of window films in lieu of fenestration replacement.  Window films are considered as an alteration option to existing fenestration for energy compliance. Similar to fenestration replacement the window film must also meet the Standard Design for altered component with or without third party verification as indicated in Table 150.2-B. Also see window film installation protocols in Reference Appendices RA4.2.3.

Example 9-14

Question

An existing building has all single-pane, metal-frame windows. A proposed remodel will replace all the windows; no other work is being done as part of the remodel. What applies?

Answer

Because two or more altered components are required to use the performance method per §150.2(b)2, only the prescriptive path is available to meet the Standards.  As a result, the area-weighted average of all replacement windows must meet the requirements of Package A, and new fenestration must also meet applicable mandatory measures of §110.6, §117.0 and §150.0

Example 9-15

Question

An existing building has all single-pane, wood-frame windows. Two double-pane, metal-frame greenhouse windows will be added as part of a remodel. How should the greenhouse windows be treated?

Answer

Since greenhouse windows add conditioned volume, but do not add conditioned floor area, this remodel is considered an alteration rather than an addition. For the purposes of alterations, any dual-glazed greenhouse windows installed as part of an alteration may use §150.0(q) to meet the U-factor and Package A to meet SHGC requirement.

If two or more types of altered energy measures are in the existing building, the Existing + Alterations performance method may be used as explained above in the answer to
Example 9-15. All applicable mandatory measures must be met.

Example 9-16

Question

Why the low-sloped roofing product requirement only listed for Climate Zones 13 and 15?

Answer

These two climate zones are the only climate zones which show energy cost-effectiveness for having a low-slope roofing product (cool roof) requirement.

Example 9-17

Question

Why are there so many exceptions to the addition and alterations section that can be considered equivalents to Roofing Products?

Answer

There are several energy features that have a roughly equivalent or greater impact on energy savings than the cool roof requirements. There are older vintage structures that often have ducts under the house rather than in the attics; and newer homes may have materials just slightly below current requirements or equal to one of the items considered to be equivalent.

Often changing one performance measure in a system can have an impact, sometimes reducing or negating the positive benefit of another. In warm months the main concern is heat gain in the attic negatively impacting  ducts, or, by conduction, heating the occupied area ceilings. For example,

 If the ducts are insulated and air leakage controlled to meet current requirements, energy savings are expected to at least equal the benefit of reflective roof coverings.

 

Example 9-19

Question

What happens if I have a low-slope roof on most of the house but steep-sloped roof on another portion?  Do I have to meet two different criteria for the roofing products?

Answer

Yes.  If your house is in climate zones 13 or 15, you will need to meet the low-slope criteria for the areas with low-slope. The areas with steep-slope roof will need to meet the other cool roof criteria.

 

Example 9-18

Question

I am replacing my existing wood shake roof with asphalt shingles. Would this be considered a repair?

Answer

No.  A repair is defined as a reconstruction or renewal for the purpose of maintenance of any component, system or equipment of an existing building. A replacement of any component (i.e. roof top), system, or equipment for which there are requirements in the Standards is considered an alteration and not a repair.

 

Example 9-21

Question

Where do radiant barriers need to be installed when using the prescriptive Package A or meeting the performance standards where credit is taken for retrofitting a radiant barrier in the existing house?

Answer

The radiant barrier only needs to be installed on the underside of an attic roof assembly and the gable wall ends associated with an addition. The prescriptive requirement is the same for entirely new buildings.

Example 9-22

Question

I am considering doing a reroofing on my house. Under what conditions will I be required to put on a cool roof?

Answer

Cool roof requirements are triggered when 50 percent or more of the roof area is being replaced. Prescriptive requirements are waived if one of the Exceptions to §150.2(b)1H below applies:

Prescriptive Exceptions for Steep-Sloped Roofs

1.  Air-Space of 1.0 inch (25 mm) is provided between the top of the roof deck to the bottom of the roofing product; or

2. The installed roofing product has a profile ratio of rise to width of 1 to 5 for 50 percent or greater of the width of the roofing product; or

3. If existing ducts in the attic are insulated and sealed according to § 150.1(c)9 ; or

4. Buildings with at least R-38 ceiling insulation; or

5. If the building has an attic radiant barrier meeting the requirements of §150.1(c)2 ; or

6. Buildings with no ducts in the attic; or

7. If in climate Zones 10-15, R-4 or greater insulation above the roof deck.

Prescriptive Exceptions for Low-Sloped Roofs

1. Buildings with no ducts in the attic; or

2. Aged Solar Reflectance and roof deck insulation R-value in Table 150.2-A are met.

Alternatively, the building may show compliance using the performance approach.

Example 9-23

Question

I am building a 450 ft² addition on my house.  Do I have to meet cool roof requirements in the prescriptive package?

Answer

Yes.  If using prescriptive compliance the roof must meet the cool roof requirements of Package A for the type of roof slope and density. To avoid the cool roof requirements, you may use the performance approach and tradeoff against other energy efficiency features of the addition alone or the existing building by using the Existing + Addition + Alterations approach.

9.6.7    Prescriptive HVAC System and Water Heating Alterations

The Standards apply to alterations of the heating and cooling system whether or not the alterations correspond to an addition to the building. This section describes the conditions where compliance is necessary and describes the corresponding prescriptive requirements.

If the heating and cooling system is left unchanged as part of an addition or alteration, then compliance with the requirements for altered HVAC systems is not necessary. Extension of an existing heating and cooling system, such as extension of a duct is not considered a change to the existing heating and cooling equipment therefore the existing heating and cooling system components are unchanged (except the ducts) and do not need to meet the Standards requirements. However, the extensions of the duct systems must meet mandatory requirements described in Section 9.4.2; and prescriptive requirements described below.

 

Example 9-24

Question

An existing 1,500 ft² single family residence is getting a 500 ft² addition. A new 50 gallon gas water heater will replace the existing water heating system. How do the water heating requirements apply?
Answer

Since this is an alteration to an existing water heating system, no water heating calculations are required for compliance of the addition alone.  However, applicable mandatory measures apply. The water heater must have an Energy Factor equal to or greater than the federal minimum standards, or R-12 insulation wrap. The first 5 ft. of hot and cold pipes must be insulated. If building energy compliance is achieved with the Existing + Addition + Alterations calculation, the EF and other energy features of the water heating system are modeled in the performance method.

Example 9-25

Question

An existing 2,000 ft² single family residence has one 50 gallon gas water heater, and a 600 ft² addition with a new instantaneous gas water heater is proposed. How does this comply?

Answer

When there is an increase in the number of water heaters with an addition, the standards allow addition alone compliance in certain circumstances. Since this is an instantaneous gas water heater, it may be installed if it can be demonstrated that it uses no more energy than a 50 gallon gas non-recirculating storage tank (see Prescriptive Water Heating Alterations above).  Since §150.1(c)8B declares a single instantaneous gas water heater to be equivalent to a standard 50 gallon storage water heater, then no water heating calculations are required. Mandatory measures apply.

Other alternatives are to show compliance with existing-plus-addition or whole building compliance.

Example 9-26

Question

An existing single family residence with one electric water heater has a 500 ft² addition with a 30 gallon electric water heater proposed. Does this comply?

Answer

When there is an increase in the number of water heaters with an addition, the Standards allow addition alone compliance in certain circumstances.

If this residence does not have natural gas connected to the building and the new water heater has an EF equal to or greater than the federal minimum standards, the system automatically complies. No water heating calculations are submitted.

If it does have natural gas connected, then the new water heater must be natural gas, or calculations are required to show the proposed water heater would use no more TDV energy than a 50 gallon natural gas water heater with an EF equal to the federal minimum standards.

9.6.8    HVAC "Changeouts"

The Standards make a distinction between two types of HVAC "changeout" situations:

1.   Entirely New or Complete Replacement Space Conditioning Systems;

2.   Altered Space Conditioning Systems.

The differences in the requirements for these two types of HVAC changeout situations are discussed in the following sections.

9.6.9    Entirely New or Complete Replacement Space Conditioning Systems

When an Entirely New or Complete Replacement Space Conditioning Systems is installed, the system must meet all applicable mandatory measures, including:

§150.0(h)– Space conditioning equipment loads, design, installation, etc.;

§150.0(i) – Thermostat requirements;

§150.0(j)2 – Refrigerant line insulation thickness;

§150.0(j)3 – Refrigerant line insulation protection;

§150.0(m)1 – California Mechanical Code(CMC) compliance;

§150.0(m)2 – Factory fabricated duct system UL requirements;

§150.0(m)3 – Field fabricated duct system UL requirements;

§150.0(m)4 – Duct R-value minimum ratings;

§150.0(m)5 – Duct insulation thickness and R-value;

§150.0(m)6 – Duct labeling requirements;

§150.0(m)7 – Backdraft damper requirements on vent systems;

§150.0(m)8 – Gravity ventilation system dampers;

§150.0(m)9 – Protection of insulation;

§150.0(m)10 – Prohibition of using porous inner core;

§150.0(m)11 – Duct system sealing and leakage testing for new systems;

§150.0(m)12 – Air filtration requirements;

§150.0(m)13 – HSPP/PSPP, mandatory return duct sizing (or diagnostically tested airflow and fan efficacy);

§150.0(m)15 – Requirements for zonally controlled systems;

These systems must also meet the prescriptive requirements found in:

§150.1(c)6 – Allowed heating system types;

§150.1(c)7 – Space heating and cooling system minimum efficiencies and refrigerant charge verification in climate zones 2, 8 through 15.

§150.1(c)9 -  Duct insulation requirements;

§150.1(c)10 – Central fan integrate systems added or required as part of an addition or alteration must meet the 0.58 watts per cfm requirement.

These requirements are discussed in detail in Chapter 4, HVAC Requirements.

Note: Completely New or Replacement Duct Systems in multifamily dwelling units shall meet the 12% (total leakage protocol), or 6% (leakage to outside protocol) criteria used for newly constructed systems (may also use the smoke test protocol if the system does not meet these criteria).  Otherwise, altered duct systems in multifamily dwelling units shall meet the 15% (total leakage protocol), or 10% (leakage to outside protocol), or smoke test criteria given in 150.2(b)1Dii(b).

A system installed in an existing dwelling shall be considered an Entirely New or Complete Replacement Space Conditioning System when:

1.   the air handler and all of the system heating/cooling equipment ( e.g. outdoor condensing unit and indoor cooling or heating coil for split systems; or complete replacement of a package unit),are new, and

2.   the duct system meets the definition of an Entirely New or Complete Replacement Duct System (including systems less than 40 feet in length).

An altered duct system installed in an existing home shall be considered an Entirely New or Complete Replacement Duct System when:

1.   at least 75 percent of the duct material is new, and

2.   any remaining components from the previous system are accessible and can be sealed.

Altered duct systems that do not meet the definition of Entirely New or Complete Replacement Duct Systems shall be considered an Extension of an Existing System. 

Space conditioning systems that do not meet the definition of Entirely New or Complete Replacement Space Conditioning Systems shall be considered Altered Space Conditioning Systems.

9.6.10  Altered Duct Systems – Duct Sealing Requirements

Entirely New or Complete Replacement Duct Systems must meet the mandatory requirements of:

§150.0(m)12 – Air filtration requirements, and

§150.0(m)13 – HSPP/PSPP, mandatory return duct sizing (or diagnostically tested airflow and fan efficacy).

These requirements are discussed in detail in Chapter 4

Entirely New or Complete Replacement Duct Systems must also be sealed to the criteria for “new duct systems” found in Table RA3.1-2, discussed below.

Because Entirely New or Complete Replacement Duct Systems can also include the original air handler, which may leak substantially more than new equipment.  An attempt should be made to seal the duct system to meet the 6 percent (of nominal system central fan airflow) leakage rate criteria.  If the 6 percent leakage rate criteria cannot be met, a smoke test should be performed to verify that the excess leakage is coming only from the furnace cabinet (air handler cabinet), and not from other accessible portions of the duct system.  Note that the protocol for Smoke Test of Accessible-duct Sealing given in Reference Residential Appendix RA3.1.4.3.7 makes an exception for the furnace cabinet (air handler cabinet).

Note that this will satisfy the sealing requirement and does not cause the system to no longer meet the definition of an Entirely New or Complete Replacement Duct Systems.

Altered duct systems that do not meet the definition of Entirely New or Complete Replacement Duct Systems shall be considered an Extension of an Existing System.  These duct systems are required to meet one of the leakage criteria for “altered existing systems” cases in Table RA3.1-2.

Because duct sealing is a mandatory measure, alterations to an existing duct system, such as adding or replacing sections of duct, will trigger duct sealing.  However, cost-effectiveness must also be taken into account.  Having to seal an entire system because one foot of duct is being removed may not be cost effective all by itself.  The standards set the length of 40 feet of duct as a criterion to trigger this requirement. 

If 40 feet of duct are being added or replaced, this work alone can trigger the requirement for duct sealing and field verification.  The system would have to meet one of the leakage criteria for “altered existing systems” cases in Table RA3.1-2. 

In 'addition to the duct sealing requirements, the added or replaced ducts must also meet the air distribution requirements of §150.0(m) and the duct insulation requirements of §150.1(c)9. Note that the air distribution and duct insulation requirements must be complied with in all climate zones; however, these requirements apply to only new or replaced ducts, the existing and unaltered ducts do no need to comply with these requirements.

Installing 40 feet or less of new or replacement ducts alone will not trigger the sealing requirements described above; however, the new ducts and connections must still meet the air distribution and duct insulation requirements of §150.0(m) and §150.1(c)9.

9.6.11  Altered Space-Conditioning Systems - Duct Sealing and Insulation

Existing duct systems must be sealed and verified by a HERS rater when portions of the heating and cooling system are altered. The requirement applies in all climate zones.

9.6.12  An air handler is installed or replaced.

Ducts must be sealed (as described below) under any of the following circumstances:

1.   An outdoor condensing unit of a split system air conditioner or heat pump is installed or replaced;

2.   A cooling or heating coil is installed or replaced;

3.   More than 40 feet of new or replacement ducts are installed in unconditioned space

The requirements apply to the duct system that is affected by any one of the alterations 'listed above. If a residence has more than one duct system, only the ducts connected to the altered equipment need to be sealed and verified.

There are three options for showing compliance for existing duct systems 'listed below.  The rater or installing contractor must at least attempt compliance with the first option (15 percent leakage); then any of the other options can be utilized:

a.   Total leakage is less than 15 percent of nominal system fan airflow (RA3.1.4.3.1);

b.   Leakage to the outside is less than 10 percent of system fan airflow (RA3.1.4.3.4);

c.   If the first option (15 percent) leakage target cannot be met, then compliance can be achieved by sealing all accessible leaks verified by a HERS rater inspection.  When using this option sampling is not allowed (RA3.1.4.3.5-7).

d.   HERS field verification is required for all options 'listed above. For options 1, and 2, verification can be accomplished through sampling as described in Sampling for Additions or Alterations below. For option 3, sampling is not allowed; a certified HERS rater must do the visual inspection and the smoke test on every house that chooses option 3.

e.   Since test equipment must be set up for the first three options, it may be most efficient to test and record the results for the existing system and then attempt to meet each option sequentially until compliance is achieved.

f.    There are a few cases where duct sealing and duct leakage verification are not required.  These exceptions include the following:

g.   Ducts that have already been sealed, tested, and certified by a HERS rater;

h.   Duct systems with less than 40 ft of duct in unconditioned spaces;

Duct systems that are insulated or sealed with asbestos.

9.6.13  Accessible Ducts

Several code sections and protocols require a smoke test to demonstrate that all accessible leaks have been sealed. 

Accessible is defined Joint Appendix JA1 as “having access thereto, but which first may require removal or opening of access panels, doors, or similar obstructions.”

Ducts located in an attic or crawlspaces are generally considered accessible because code requires access to those spaces.  Access is usually gained by opening a door, hatch, or other moveable panel.  If this can be done without causing damage that would need to be repaired, this is considered accessible.  It is not expected that drywall sections have to be cut or damaged to gain access,

Some judgment is required in determining if ducts are accessible or not.   The local code enforcement agency will have the final say when it is not immediately obvious. 

For example:

If the ducts are buried under insulation, and gaining access to the leaks in these ducts would require substantially disturbing the insulation this is probably not considered accessible;

If a leak in the duct system is in too small a space between framing members for an average size person to be able to reach the joint to seal it, then this is probably not considered accessible;

If ducts are suspended far above the ground and reaching them would require scaffolding or special equipment other than normal ladders, then these are probably not considered accessible;

If sheet metal ducts are wrapped with insulation and a smoke test indicates multiple small leaks along the lengthwise seams in the ducts in many locations, it is probably not cost effective to remove the insulation to find and seal these leaks.  However, if one or more location shows a very obvious and substantial leak, it should be sealed.

All other portions of the duct system for which a smoke test identifies the presence of leakage must be sealed in order to comply. The exemption for inaccessible portions of the duct system is applicable only if the other criteria for duct leakage compliance cannot be met.

The installing contractor may perform a smoke test to locate and seal accessible leaks, or assess whether or not the duct leaks are accessible. However, compliance by smoke test and sealing all accessible leaks must be determined by a smoke test that has been conducted by a HERS rater.

9.6.14  Refrigerant Charge Verification

In climate zones 2, and 8-15, when a refrigerant containing component of an air conditioner or heat pump is replaced or installed in an existing building, §150.2(b)1F requires systems that do not have a CID installed to have refrigerant charge field verified in accordance with all applicable procedures specified in Reference Residential Appendix Sections RA3.2.2, or Reference Residential Appendix RA1.

The RCV procedures in RA3.2 are not intended to replace the equipment manufacturer’s charging procedures and specifications. The installer must first charge the system according to the manufacturer’s instructions and specifications. It is important to know that the procedures in RA3.2 are not procedures for charging a system; rather, they are procedures for verifying proper charge. HERS Raters are not allowed to adjust the refrigerant charge in systems that they are verifying. Raters are also prohibited from performing the weigh-in charge verification procedures. However, when specified by the Standards, a Rater may observe the installer while the installer performs the weigh-in procedure to verify compliance as specified in Section RA3.2.3.2 (described below).

A.   Charge Indicator Display. As an alternative to RCV the installer may install a special device called a charge indicator display (CID).  This device provides real-time monitoring of the air conditioning system and will show a warning visible to the home’s occupants when the system is either over or undercharged, or if the system airflow rate does not meet the minimum requirement.  The display unit must be located within one foot of the thermostat.  §150.1(c)7Aib states:

(When applicable, systems shall) be equipped with a charge indicator display (CID) device that provides a clearly visible indication to the occupant when the air conditioner fails to meet the required system operating parameters specified in the applicable section of Reference Joint Appendix JA6 for the installed CID technology. The CID indication display shall be constantly visible and within one foot of the air conditioners thermostat. CID installations shall be confirmed by field verification and diagnostic testing utilizing the procedures specified in Reference Residential Appendix RA3.4.2.

Minimum Airflow. When refrigerant charge verification is required for compliance, the system must also comply with the minimum airflow requirement specified in RA3.2.2.7 if the airflow verification protocol in RA3.3 can be applied to the system.

Altered HVAC systems must meet the minimum 300 cfm/ton airflow rate compliance criterion; example include but not limited to replacing the outdoor condensing unit, replacing the furnace or air handler, and entire replacement of the duct system.

Entirely New or Complete Replacement Space Conditioning Systems, as specified in §150.2(b)1C, must meet the minimum 350 cfm/ton airflow rate compliance criterion or the duct design alternative specified in 150.0(m)13.

Alternative to Refrigerant Charge and Verification requiring at least 300 cfm per ton of airflow. If the altered HVAC that requires RC&V is not able to comply with the 300 cfm per ton of airflow required under subsection Reference Residential Appendix RA3.2.2.7.2, the HVAC installer may choose the alternative procedure outlined in Reference Residential Appendix RA3.2.2.7.3, Alternative to Compliance with Minimum System Airflow Requirements for Altered Systems, provided that the system thermostat is an Occupant Controlled Smart Thermostat (OCST) which conforms to the requirements of Reference Joint Appendix JA5

Under RA3.2.2.7.3, installer must take a series of remedial steps, including but not limited to cleaning filters, removing obstructions from registers and dampers, replacing crushed or blocked ducts, cleaning the evaporator coil, making sure that the air handler is set to high speed and conforms to manufacturer specifications, and enlarging/adding the return duct and the return grill.  These steps must be HERS verified by a HERS rater.  Again, as mentioned above, when the installer chooses this option, the system thermostat must be an OCST.

B.   Applicability of the protocols. The refrigerant charge verification (RCV) protocols in RA3.2 and RA1 are applicable only to air-cooled air conditioners and air-source heat pumps.  Equipment types such as ground source, water source, and absorption air conditioners and heat pumps cannot be verified using the protocols in RA3.2 and RA1. When a system other than an air-cooled air conditioner or air-source heat pump is installed, the requirements in Standards §110.1 may provide further direction for compliance. 

If an aspect of the RA3.2.2 or RA1 verification protocol is not applicable to the system, alternative requirements may be specified by applicable subsections of §150.2(b)1F, however the procedures in RA3.2.2 or RA1 that are applicable to the system shall be performed. 

For example, if a system does not have both a high side and low side refrigerant access port, thus cannot conform to the subcooling or superheat refrigerant charge verification procedure, but is a ducted system that can conform to the airflow measurement protocol; the system must comply with the minimum airflow requirement specified in RA3.2.2.7.  Similarly, if the outdoor temperature is below 55°F which precludes use of the RA3.2.2 protocol for verification of the charge, and if the RA1 protocol cannot be used, then the weigh-in charging procedure in Reference Residential Appendix Section RA3.2.3.1 shall be used, and the minimum system airflow rate shall be verified as required by RA3.2.2.7.

The installer must determine which procedures are applicable to a system and verify compliance accordingly. 

C.   Thermostats. When an existing system has a refrigerant containing component added or replaced, the thermostat must be upgraded to a digital setback type that meets §110.2(c)

Package Units. Package units are typically pre-charged at the factory prior to shipment. When a new package unit is being installed or is replacing an older unit it may not require RCV if the installer can document that the manufacturer certified correct refrigerant charge at the factory. The installer must submit a certificate of installation documenting this and third party verification of refrigerant charge by a HERS rater is not required. This only applies to new equipment shipped from the manufacturer. Any modification to existing equipment that adds or replaces refrigerant containing components voids the manufacturer’s certification. It is also important to note that this does not relieve the contractor from the requirement to verify that the system meets the minimum 300 cfm per ton airflow rate requirement.

D.   Mini-Splits and Other System Types. Some air-cooled air conditioning systems and air-source heat pumps cannot use the standard charge verification procedure, as specified in RA3.2.2, due to the design or construction of the system components. These include certain types of “mini-split” systems and variable speed condenser systems. In these cases, the installer must use the weigh-in charge procedures, as specified in RA3.2.3.1, and these systems must be HERS verified using the, as specified in RA3.2.3.2 procedure for HERS Rater observation of the weigh in charge procedure. These systems must also be equipped with an Occupant Controlled Smart Thermostat (OCST) which conforms to the requirements of Reference Joint Appendix JA5.

It is therefore important that the installation of these types of systems be coordinated with the third party verification. When these systems are ducted, they are still subject to the minimum system airflow requirements.

1.   Winter Refrigerant Charge Verification. Most systems will normally be verified using the RA3.2.2 standard charge verification procedure to demonstrate compliance. However, when the outdoor temperature is less than 55oF, and the Standard Charge verification procedure cannot be used, the installer may elect to use the weigh-in charge method to demonstrate compliance.  Compliance with HERS verification when the outdoor temperatures are less than 55oF can be demonstrated using one of two alternatives:

A.   The installer may use the weigh-in charging procedure, but elect to have the system verified by a HERS rater using the RA3.2.2 Standard Charge Verification procedure at a later time when the temperature is warmer; however, this option can delay the project; or

B.   The EXCEPTION to Section 150.2(b)1Fi provides for an alternative HERS verification procedure if the weigh-in method is used. This exception allows the installer to elect to utilize the HERS Rater verification procedure in Reference Residential Appendix Section RA3.2.3.2 in which the Rater observes the installer while the installer performs the weigh-in charging procedure. However, when the HVAC installer elects this procedure for verification, as specified in RA3.2.3.2, the system thermostat must be an Occupant Controlled Smart Thermostat (OCST) which conforms to the requirements of Reference Joint Appendix JA5.

C.   Weigh-in Procedure During Warm Weather. The installer may also opt to use the weigh-in procedure when the outdoor temperature is at or above 55oF, but in this case the rater must use the standard charge verification procedure.

D.   Weigh-in Procedure Description. The weigh-in procedure involves charging the system by determining the appropriate weight of refrigerant based on the size of the equipment and refrigerant lines rather than by actual performance of the system.  Systems utilizing the weigh-in procedure by the installer for any reason may not be third party verified by using sample groups.

There are two basic variations of the weigh-in procedures.  One involves the adjustment to the amount of refrigerant in a system by adding or removing a fraction of the refrigerant as specified by the manufacturer (weigh-in charge adjustment).  The other involves evacuating the entire system and recharging it with the correct total amount of refrigerant, by weight (weigh-in total charge).

The weigh-in charge adjustment procedure may only be used when a new factory-charged condenser is being installed and the manufacturer provides adjustment specifications based on evaporator coil size and refrigerant line size and length.

The weigh-in total charge may be used for any weigh-in procedure but still requires manufacturer’s adjustment specifications.

E.   Standard Charge Procedure Description. The standard charge verification procedure also has two basic variations.  One is for systems that have a fixed orifice and the other is for systems that have a variable metering device such as a thermostatic expansion valve (TXV) or electronic expansion valve (EXV).

Both procedures, whether performed by the installer or the rater require that adequate airflow be confirmed prior to verifying charge.  If the airflow is less than the minimum requirement of 300 cfm per ton, the system is not operating near its designed capacity or efficiency and the standard charge verification procedure is not valid.

The standard charge verification procedures involve taking refrigerant line temperatures and pressures, calculating equipment performance parameters and comparing those to targets either provided by the manufacturer or obtained from standard tables.  All temperature and pressure measurements must be taken using calibrated digital meters.  Analog gauges are no longer allowed for refrigerant charge verification procedures due to a lack of accuracy and precision.

In systems that have metering devices, the proper installation and performance can be verified by similar measurements and is an important part of the standard charge verification procedure for systems that have metering devices.

F.   Verifying Minimum System Airflow. The procedures for measuring total system airflow are found in RA3.3.  They include plenum pressure matching using a fan flow meter, a flow grid, a powered flow hood and the traditional (non-powered flow hood).  The airflow verification procedures for refrigerant charge verification no longer include the temperature split method.

If a system does not meet the minimum airflow requirements, remedial steps may be required to bring the airflow up.  More airflow is generally better for systems with air conditioning.  Not only does this allow proper refrigerant charge to be verified, but it also improves the overall performance of the system.  When able to be performed on a system, regardless of the refrigerant charge verification procedure, minimum system airflow must always be verified.  Note that §150.2(b)1F states that systems must be installed with “all applicable procedures”.  This includes the minimum system airflow requirements.

In some cases, improving airflow may be cost prohibitive and there is a process for documenting this in RA3.2.2.7.3.  When this option is used, verification by sample groups is not allowed.

G.   Temperature Measurements. To properly perform the standard refrigerant charge verification procedure, a means of taking an accurate return air dry-bulb temperature must be provided by the installer.  In most systems, this is accomplished by drilling a 5/16” measurement access hole (MAH) in the return side of the air handler or return plenum as shown in Figure RA3.2-1.  In some cases the correct location for these holes may not be accessible and an alternative location may be provided as long as an accurate return air temperature measurement of the air as it enters the return side of the equipment can be made.

In other cases, taking the return air dry-bulb temperature at the return grill may be appropriate.  This is true when the return is located entirely within conditioned space and not subject to leakage or conduction that may change the temperature of the air after it passes through the return grill and before it enters the evaporator coil.  This may also apply to equipment where the return grill is an integral part of the air handler, such as enclosed soffit-mounted air handlers (aka, “pancake units”).

E.   Maintaining 70°F Return Air Temperature. During the data collection portion of the standard charge verification procedures, the return air dry bulb temperature, as measured at the MAH, must remain at or above 70°F.  This is to ensure proper refrigerant charge conditions, including but not limited to preventing the moisture on the coil from freezing.  This requirement may be problematic during cooler outdoor conditions (above 55°F but below 70°F).  The return air temperature can be maintained above 70°F by utilizing the home’s heating system or supplemental heaters is permissible.  <refer to Blueprint language on this topic>.  Note that the weigh-in method is always an option for the installer in these cases.

F.   Airflow and Fan Efficacy

In all climate zones when an entirely new or replacement duct system (refer to section 9.6.9, above) is installed, the central forced air fan of all ducted air conditioners and heat pumps must simultaneously, in every zonal control mode, demonstrate an airflow of greater than 350 CFM/ton of nominal cooling, and a fan watt draw of less than 0.58 W/CFM in accordance with the procedures in Reference Residential Appendix RA3.3.  

As an alternative to the field verified air flow and fan efficacy requirements, the system’s return ducts can be sized according to Tables 150.0-C or 150.0-D.

In 'addition to either the airflow/fan efficacy or return duct sizing alternative, the system installer must provide in the supply plenum, a hole for the placement of a static pressure probe (HSPP) or a permanently installed static pressure probe (PSPP), downstream of the evaporator coil that meets the specifications of Residential Reference Appendix RA3.3.1.

<Insert Diagram>

These requirements are mandatory measures and cannot be traded off by using the performance approach.

These requirements are discussed in more detail in Chapter 4 of this 'manual.

Heating-only space-conditioning systems are not required to meet the prescriptive cooling coil airflow and fan watt draw requirements.

G.   Sampling for Alterations

When compliance for an alteration requires field verification and diagnostic testing, the building owners or their agents may choose to have testing and field verification completed for the dwelling unit alone, or as part of a closed sample group of dwelling units for which the same installing company has completed work that requires testing and field verification for compliance.

Registration of the compliance documentation is required and the procedures for registration of compliance documentation must be followed as described in Chapter 2 of this Residential Compliance Manual, and in Residential Reference Appendix RA2.

Notes regarding sampling for alterations:

1.   The sample group shall be no larger than seven;

2.   The installing company may request a smaller group for sampling; 

3.   Homes in a sample group must all have the same set of features to be verified (duct testing, airflow/fan efficacy, refrigerant charge, etc.);

4.   Homes with systems utilizing the weigh in method for refrigerant charge verification by the installer cannot be sampled;

5.   Whenever the HERS rater for the group is changed, a new group will be established; 

6.   Field verification and diagnostic testing shall be completed by the HERS rater for at least one randomly selected dwelling unit in each group; 

7.   Re-sampling, full testing and corrective action shall be completed if necessary, as specified by the Residential Reference Appendix RA2.6.3;

8.   The installing contractor must self test and register certificates of installation for all features to be tested prior to the rater choosing a home for verification by sampling.

H.   Third Party Quality Control Program

An approved Third Party Quality Control Program may serve some of the functions of HERS raters for field verification and diagnostic testing purposes but does not have authority to sign the Certificate of Field Verification and Diagnostic Testing (CF-4R) as a HERS rater, as specified in Residential Reference Appendix  RA2.7.

When a Third Party Quality Control Program is used, the HERS rater must still submit completed, signed, registered copies of the CF-4R to the enforcement agency, the installing contractor, and the builder or building owner for all dwellings that must demonstrate compliance.

I.    Setback Thermostat

When a split system air conditioner or heat pump is altered by the installation or replacement of any refrigerant containing component and the existing thermostat is not a setback thermostat, then a new setback thermostat must be installed as described in Chapter 4 of this 'manual and as specified in §150.2(b)1F.

J.   Fuel Switching

For prescriptive compliance, new electric resistance heating systems are prohibited in alterations unless the system being replaced is an electric resistance heating system. If the existing system is gas, propane, or LPG, then new electric resistance systems are not permitted. However, changing from a gas, propane, or LPG space heating system to an electric heat pump is allowed as long as the heat pump efficiency meets minimum efficiency standards, and the heat pump installed size is shown to result in no more TDV energy use than the standard design heat pump using the performance method as specified in §150.2(b)1C.

Table 9-7 – Acceptable Replacement Heating System Fuel Source(s)

Existing Heating
System Fuel Source

Acceptable Replacement Heating
System Fuel Source(s)

Electric

Electric, natural gas, or equipment with efficiency equal to or better than existing system*

Natural gas

Natural gas, or equipment with efficiency equal to or better than existing system* or a heat pump with equal or lower TDV energy use than a standard design system.

LPG

 

Liquefied petroleum gas, natural gas, or equipment/ system with efficiency equal to or better than existing system* or a heat pump with equal or lower TDV energy use than a standard design system.

* Proof that equipment has an efficiency that is equal to or better than the existing system can be demonstrated by an approved compliance program or other approved alternative calculation method to compare the TDV energy use of the existing system to the proposed system.

 

Table 9-5B summarizes requirements for the following types of residential mechanical and water heating system alterations:

1.   New or complete replacement space conditioning system: all new equipment and all new ducts with more than 40 linear feet of ducts in unconditioned or indirectly conditioned space;

2.   Altered space conditioning system with forced air ducts;

3.   Altered mechanical cooling system;

4.   Altered duct systems: when more than 40 linear feet of new or replacement ducts are installed in unconditioned or indirectly conditioned space;

5.   Installed a zonally controlled central forced air system;

6.   Replacing water heaters and altering hot water pipes.

Since there are some overlaps in Table 9-5B between a few mandatory and prescriptive measures depending on the kind of alteration, it is important to accurately identify the type(s) of alteration within the permitted scope of work.  For example, duct sealing and HERS testing is a mandatory measure when there is a new or complete replacement space conditioning system and greater than 40 linear feet of ducts in unconditioned space.  However, when only new or replacement ducts are being installed, and there is no new space conditioning equipment involved, duct sealing and HERS testing is a prescriptive measure.  A key to using Table 9-5B effectively is to have a good understanding of the scope of the proposed alterations.

 

Example 9-27 

Question

Do I have to seal my ducts if I replace my outdoor units in my existing house without changing the indoor unit?

Answer

Yes, replacing the outdoor unit (or indoor unit) by itself will trigger the duct sealing and verification requirement (§150.2(b)1E).  However, there are two exceptions that might apply:

1. If the ducts have been previously sealed and verified as sealed, the ducts do not have to be sealed again and re-verified. 

2. Less than 40 linear feet of the duct system is located in unconditioned spaces such as attics or crawl spaces.

 

Example 9-28

Question

I have an existing electric furnace and I’m adding a new bedroom. Can I extend the existing ducts to the new room and use the existing furnace?

Answer

Yes. If ducts are extended from an existing space conditioning system §150.2(b)1D allows the existing system but requires duct sealing if more than 40 linear feet of the new duct system is located in unconditioned or indirectly conditioned space such as in an attic or crawl space. . The existing furnace must have adequate heating capacity to meet California Building Code requirements for the additional space.

 

 

Example 9-29  

Question

I am adding a bedroom to an existing house which uses a central forced air natural gas furnace. I would like to heat the room with an electric resistance baseboard heater rather than extend the existing ductwork to reach the new space. Is this allowed?

Answer

No. If using prescriptive compliance and since the existing system is gas, the addition cannot use an electric heating system. Options for heating the space include:

Extending the existing natural gas furnace system as long as there is adequate capacity to meet the California Building Code requirement;

Heating the added bedroom with an electric resistance heater is allowed if the performance approach is taken and the relatively high TDV energy consumption of the electric resistance heater is made up by TDV energy reductions from energy efficiency measures in the addition or in an accompanying alteration.

Note: If there are more than 40 linear feet of added ducts being located in unconditioned or indirectly conditioned space, then the ducts must be sealed, tested and the ducts must be verified as sealed by a HERS rater.

Example 9-30 

Question

My central gas furnace stopped working. Since it is about 30 years old I decided to get a new more efficient unit rather than repair the existing one. What are the requirements?

 

Answer

Mandatory requirements apply to the components being replaced. The furnace, of course, must meet minimum efficiency requirements, but all systems sold in California should already meet the minimum efficiency requirements. If the existing thermostat is not a setback thermostat, it must be replaced with a setback thermostat, as specified in §150.2(b)1F that meets the requirements described earlier in this chapter.

All new ducts must meet insulation and construction requirements. In climate zones 2, 9-16, all existing and new ducts must be sealed and HERS verified, as specified §150.2(b)1E.

Prescriptively, the new heating unit must also be a natural gas unit.    

The performance approach could be applied but only if the alteration includes “tradeoffs between two or more altered components that are 'listed in TABLE 150.2-B” (insulation, fenestration, space conditioning equipment, air distribution systems, water heating system, roofing and other measures).  Thus if other alterations are also being done one could specify other heating equipment such as heat pumps, electric resistance etc as long as the overall project has a lower TDV energy consumption than the “standard design”  efficiency.  When using the performance approach one can decide to either use the default standard design efficiencies that the alteration is compared against.  Alternately one can hire a HERS rater to document the existing efficiencies and these existing efficiencies can be used in the standard design of performance calculation.

 

Example 9-31 

Question

As part of an upgrade in an existing house, one of the ducts is being replaced because of deterioration of the insulation and jacket. What requirements apply to the replacement duct?

Answer

This is an alteration since no new conditioned space is being added. The mandatory measures for ducts apply. If more than 40 ft of altered duct is in unconditioned or indirectly conditioned space, then the requirements of §150.2(b)1D require diagnostic testing and HERS verification of the whole duct system.

 

Example 9-32 

Question

An up-flow air-handling unit with a furnace and air conditioning coil is located on a platform in the garage of an existing house. The platform is used as a return air plenum. The air-handling unit is being replaced and the platform is being repositioned to the corner of the garage (3 feet away from the current location). What requirements apply to this alteration?

Answer

The mandatory requirements apply to this alteration. In particular, §150.0(m) prohibits raised platforms or building cavities from being used to convey conditioned air (including return air and supply air). When the platform is relocated, it is being altered, and the mandatory requirement applies. Ducts made from sheet metal, duct board or flexible ducts must be installed to carry the return air to the replaced air handler. This requirement would not apply if the platform were not being altered.

In 'addition since the air handler is being replaced the prescriptive duct sealing requirements apply per §150.2(b)1E , unless the ducts have been previously sealed and confirmed through verification or there is less than 40 linear feet of ducts in unconditioned spaces.

 

Example 9-33

Question: 

What is meant by the term "air handler"?

Answer:

The term "air handler" is used to identify the system component that provides the central system forced air movement for the ducted heating or cooling space-conditioning system.  The term "air handler" may be properly used to identify various types of central system forced air-moving components that must meet the functional requirements for different types of space-conditioning systems.  For instance:  A "gas furnace" air handler includes a gas combustion heat exchanger, and the central system fan, but does not include a DX cooling coil; An "electric furnace" air handler has electric heating coils, and the central system fan, but does not include a DX cooling coil;  A "fan-coil unit" air handler for a split system heat pump has a DX cooling/heating coil and the central system fan;  A hydronic heat pump air handler includes the air-side DX coil, compressor, water-cooled condenser, and the central system fan.  There are other air handler configuration variations as well. 

 

Example 9-34

Question

I have a residential building that was constructed in the 1920’s. It has a freestanding gas furnace and I want to change it to an electric wall heater. Is this permitted?

Answer

No. §150.2(b)1Cii states that the new space-conditioning system be limited to natural gas, liquefied petroleum gas, or the existing fuel type unless it can be demonstrated that the TDV energy use of the new system is more efficient than the existing system. For your situation you would have to use gas or a heat pump for compliance.

 

Example 9-35  

RESERVED



 

 

Table 9-8 Summary of Prescriptive HVAC & Water Heating Alterations

 

Type of Mechanical System Alteration

Highlight(s) of Applicable Mandatory Measures

Summary of Relevant Prescriptive Measure(s)

Exception(s) to the Prescriptive Measures

Prescriptive Compliance Form(s)

New or Complete Replacement Space Conditioning System (New Equipment and All New Ducts > 40 ft.in Unconditioned or Indirectly Conditioned Space)

New Equipment must meet all minimum efficiency and other requirements in Sections 150.0(h), 150.0(i), 150.0(j)2, 150.0(j)3, 150.0(m)1 thru 11: duct sealing & HERS testing with forced air duct systems

All requirements of Section 150.1(c)6, 7, 9 &10; and heating system limited to natural gas, LPG or existing fuel type

Exemption form fuel type requirement if new system can be shown to use less TDV energy than the existing system.

CF-1R-ALT or CF-1R-ALT-HVAC; MF-1R (CF-1R must be registered w/a HERS Provider)

Altered Space Conditioning System with Forced Air Ducts

New equipment must meet all the minimum efficiency and other requirements in Sections 150.0(h), 150.0(i), 150.0(j)2, 150.0(j)3,  150.0(m)1

Duct Sealing & HERS testing per Section 150.2(b)1.E

(1) Duct systems documented a previously sealed and HERS tested; or,
(2) Duct systems with < 40 lineal feet in unconditioned spaces; or,
(3) Existing duct system constructed, insulated or sealed with asbestos

CF-1R-ALT or CF-1R-ALT-HVAC; MF-1R (CF-1R must be registered w/a HERS Provider)

Altered(5) Mechanical cooling (Refrigerant-Containing) System

New equipment must meet all the minimum efficiency and other requirements in Sections 110.2(c), 150.0(h), 1550.0(i), 150.0(j)2,150.0(j)3, 150.0(m)1 thru 11

In CZ2, 8-15: refrigerant charge per RA3.2.2 and & HERS testing per Section 150.2(b)1 F ia.; or refrigerant weigh-in charging per RA3.2.3.1 & HERS testing

(1) Package systems w/correct, verified and documented refrigerant charge by manufacturer do not require HERS testing
(2) When outdoor temperature < 55° F. and refrigerant weigh-in charging used and HERS test RA3.2.3.2 used, system thermostat must be Demand Response.

CF-1R-ALT or CF-1R-ALT-HVAC; MF-1R (CF-1R must be registered w/a HERS Provider)

Altered Duct Systems:

When > 40ft. of New or Replacement Ducts are installed in Unconditioned or Indirectly Conditioned Space

New Ducts must meet applicable portions of Sections 150.0(m)1 thru 11 including duct insulation in Table 150.1-A. Entirely new and complete replacement duct systems must meet additional requirements in Sections 150.0(m)12 & 13.

New or Replacement Duct System: duct sealing & HERS testing per Section 150.2(b)1.D.ii.a. Extension of Existing Ducts By > 40ft: HERS testing of existing duct system per Section 150.2(b)D.ii.b.

Exception to 150.2(b)D.ii.b. Duct Sealing: when existing duct system is constructed, insulated or sealed with asbestos.

CF-1R-ALT or CF-1R-ALT-HVAC; MF-1R (CF-1R must be registered w/a HERS Provider)

Installing Zonally Controlled Central Forced Air System

Airflow > 350 CFM/T on cooling, Fan < 0.58 W/CFM: HERS Testing Section 150.1(m)15

Bypass ducts that deliver conditioned supply air directly to the return duct airflow may not be used. Section 150.0(c)13

N/A

CF-1R-ALT or CZ-Specific CF-1R-ALT-HVAC; MF-1R (CF-1R must be registered w/ a HERS Provider)

Replacement Water Heaters and Altered Piping

New equipment must meet minimum efficiency and other requirements in Sections 110.1, 110.3 and 150.0(j)2 Exception to 150.0(j)2:

Inaccessible piping requires no insulation

(1) A natural gas or propane water heater that meets the requirements of Section 150.1(c)8 with no recirculation system; or, (2) If not natural gas is connected to the building: an electric water heater with an Energy Factor = or > that required by the Appliance Efficiency Regulations and a storage tank < or = 60 gal and no recirculation system

According to a calculation method approved by the CEC: Any water heating system that uses no more TDV energy than the prescriptive natural gas/propane water heater; or when no natural gas is connected to the building, any water heating system that uses no more TDV energy than the prescriptive electric water heater.

CF-1R-ALT; or CF-1R-ALT-HVAC; MF-1R

Note 1: Alterations must comply with all applicable mandatory measures in Sections 110 and 150 of the Standards as explained in
Chapters 3, 4, 5 and 6 of this Manual.

Note 5: Non-setback thermostats must be replaced with setback thermostats per Section 110.2(c) when alterations include installation or replacement of the compressor, condensing coil, evaporator coil, refrigerant metering device or refrigerant piping.

 

 

 

Table 9-9: Residential Alteration, Summary of Mandatory and Prescriptive Measures

Type of Mechanical System Alteration

Highlight(s) of Applicable Mandatory Measures1

Summary of Relevant Prescriptive Measure(s)

Exception(s) to the
Prescriptive Measures

Prescriptive Compliance
Form(s)

New or Complete Replacement Space Conditioning System

(New Equipment and All New Ducts > 40 ft. in Unconditioned or Indirectly Conditioned Space)

New equipment must meet all minimum efficiency and other requirements in §150.0(h), 150.0(i), 150.0(j)2, 150.0(j)3, 150.0(m)1 thru 11: duct sealing & HERS testing with forced air duct systems

All requirements of §150.1(c)6,7,9 & 10; and heating system limited to natural gas, LPG or existing fuel type

Exemption from fuel type requirement if new system can be shown to use less TDV energy than the existing system.

CF1R-ALT or CF1R-ALT-HVAC;
(CF1R must be registered w/ a HERS Provider)

Altered Space Conditioning System with Forced Air Ducts

New equipment must meet all the minimum efficiency and other requirements in §150.0(h), §150.0(i), §150.0(j)2, §150.0(j)3, §150.0(m)1 thru 11

Duct sealing & HERS testing per §150.2(b)1.E

(1) Duct systems documented as previously sealed and HERS tested; or,
(2) Duct systems with < 40 lineal feet in unconditioned spaces; or,
(3) Existing duct system constructed, insulated or sealed with asbestos

CF1R-ALT or CF1R-ALT-HVAC;
(CF1R must be registered w/ a HERS Provider)

Altered(5) Mechanical Cooling (Refrigerant-Containing) System

New equipment must meet all the minimum efficiency and other requirements in §110.2(c), §150.0(h), §150.0(i), §150.0(j)2, §150.0(j)3, §150.0(m)1 thru 11

In CZ2, 8-15: refrigerant charge per RA3.2.2 and & HERS testing per §150.2(b)1.F.i.a.; or refrigerant weigh-in charging per RA3.2.3.1 & HERS testing

(1) Packaged systems w/ correct, verified and documented refrigerant charge by manufacturer do not require HERS testing
(2) When outdoor temperature < 55
°F and refrigerant weigh-in charging used and HERS test RA3.2.3.2 used, system thermostat must be Demand Response.

CF1R-ALT or CF1R-ALT-HVAC;
(CF1R must be registered w/ a HERS Provider)

Altered Duct Systems:
When > 40 ft. of New or Replacement Ducts are Installed in Unconditioned or Indirectly Conditioned Space

New ducts must meet applicable portions of §150.0(m)1 thru 11 including duct insulation in Table 150.1-A.  Entirely new and complete replacement duct systems must meet additional  requirements in §150.0(m)12 & 13.

New or Replacement Duct System:  duct sealing & HERS testing per §150.2(b)1.D.ii.a.
Extension of Existing Ducts By > 40 ft: HERS testing of existing duct system per §150.2(b)D.ii.b.

Exception to 150.2(b)D.ii.b. Duct Sealing: when existing duct system is constructed, insulated or sealed with asbestos.

CF1R-ALT or CF1R-ALT-HVAC;
(CF1R must be registered w/ a HERS Provider)