2.10 . Additions/Alterations

Addition and alteration compliance is based on Energy Code, Section 150.2. The energy budget for additions and alterations is based on TDV energy. Alterations must model the entire dwelling unit. Additions may be modeled as addition alone, as “existing+addition+alteration,” or the entire building may be modeled as an entirely new building (whole building, Section 150.2[c]).

Additions that are 1,000 ft2 or less are exempt from dwelling unit ventilation requirements of Section 150.0(o)1C, Section 150.0(o)1E, or Section 150.0(o)1F. When an addition to any building creates a new dwelling unit, this exception does not apply.

The standard design does not include:

   Cool roof when an addition is 300 ft2 or less.

   Ventilation cooling for additions that are 1,000 ft2 or less.

   Solar generation/PV requirements.

2.10.1        Accessory Dwelling Units

When an accessory dwelling unit (ADU) is detached and newly constructed, it must comply using the whole building approach as described in Section 2.10.2 Whole Building. When an ADU is created by conditioning an existing unconditioned space and is either attached or detached, it may comply using any of the compliance approaches allowed for additions as described in Section 2.10.3 Alteration-Alone Approach or Section 2.10.4 Addition-Alone Approach.

2.10.2        Whole Building

The entire proposed building, including all additions or alterations or both, is modeled the same as a newly constructed building. The building complies if the proposed design uses equal to or less energy than the standard design.

2.10.3        Alteration-Alone Approach

The proposed alteration alone floor area is modeled. The alteration requirements of Section 150.2(b) are applied to any features that do not exist.

2.10.4        Addition-Alone Approach

The proposed addition alone is modeled the same as a newly constructed building except that the internal gains are prorated based on the size of the dwelling. None of the exceptions included for prescriptive additions, which are implemented in the existing plus addition plus alteration compliance approach (Section 2.10.5 Existing+ Addition_ Alteration Approach), are given to the addition alone approach. (See Energy Code, Section 150.2[a]2B The addition complies if the proposed design uses equal to or less space heating, space cooling, and water heating TDV energy than the standard design.

The addition-alone approach shall not be used when alterations to the existing building are proposed. Modifications to any surfaces between the existing building and the addition are part of the addition and are not considered alterations.

Proposed Design

The user shall indicate that an addition alone is being modeled and enter the conditioned floor area of the addition. Any surfaces that are between the existing building and the addition are not modeled or are treated as adiabatic surfaces. All other features of the addition shall be modeled the same as a newly constructed building.

When an existing HVAC system is extended to serve the addition, the standard design shall assume the same efficiency for the HVAC equipment as the proposed design. (See Section 2.4.1 Heating Subsystems and Section 2.4.6 Cooling Subsystems.)

When a dual-glazed greenhouse or garden window is installed in an addition or alteration, the proposed design U-factor can be assumed to be 0.30.

Standard Design

The addition alone is modeled the same as a newly constructed building, with the following exceptions:

Ø When roofing requirements are included in Table 150.1-A, they are included in the standard design if the added conditioned floor area is greater than 300 ft2.

Ø When ventilation cooling (whole-house fan) is required by Table 150.1-A, it is included in the standard design when the added conditioned floor area is greater than 1,000 ft2. The capacity shall be based on 1.5 CFM/ft2 of conditioned floor area for the entire dwelling unit conditioned floor area.

Ø When compliance with IAQ requirements of Section 150.0(o) apply to an addition with greater than 1,000 ft2 added, the conditioned floor area of the entire dwelling unit shall be used to determine the required ventilation airflow. For additions with 1,000 ft2 or less of added conditioned floor area, no IAQ requirements apply.

Ø PV requirements are not included.

Ø The standard design HVAC system is a natural gas furnace (or propane if natural gas is not available) if the proposed design has a gas heating system. The standard design HVAC system is a split heat pump if the proposed design has an electric heating system. See Section 2.4.1 Heating Subsystems for equipment efficiencies and operating details for each type of system. The cooling system for the standard design building is a nonzonal control system, split-system ducted cooling system, meeting the minimum requirements of the Appliance Efficiency Regulations. See Section 2.4.6 Cooling Subsystems for equipment efficiencies and operating details for each type of system.

Ø The domestic water heating system is a natural gas tankless (or propane if natural gas is not available) if the proposed design has a gas water heating system. The standard design water heating system is a heat pump water heater if the proposed design has an electric water heating system. For additions 500 square feet or less, the standard design is an instantaneous electric water heater if the proposed design is an instantaneous electric water heater, or the standard design is an electric consumer storage water heater less than or equal to 20 gallons if the proposed design is an electric consumer storage water heater less than or equal to 20 gallons.

2.10.5        Existing + Addition + Alteration Approach

Energy Code Section 150.2(a)2 contains the provisions for additions and Section 150.2(b)2 for alterations when the existing building is included in the calculations. These provisions are the “Existing + Addition + Alteration” (or “E+A+A”) performance approach.

Proposed Design

The proposed design is modeled by identifying each energy feature as part of the existing building (as existing, altered, or new), or as part of the addition. The compliance software uses this information to create an E+A+A standard design using the rules in the standards that take into account whether altered components meet or exceed the threshold at which they receive a compliance credit and whether any related measures are triggered by altering a given component.

For building surfaces and systems designated below, all compliance software must provide an input field with labels for the proposed design, which define how the standard design requirements are established based on the option selected by the software user:

   Existing: The surface or system remains unchanged within the proposed design. (Both standard design and proposed design have the same features and characteristics.)

   Altered: the surface or system is altered in the proposed design. No verification of existing conditions is assumed with this designation.

   Verified Altered: the surface or system is altered in the proposed design, and the original condition is verified by a HERS Rater (an optional selection).

   New: a new surface or system is added in the proposed design (may be in the existing building or the addition).

Deleted features are not included in the proposed design.

Section 150.2, Table 150.2-D specifies the details of the standard design for altered components based on whether verification of existing conditions is selected or not:

   Altered with no third-party verification of existing conditions (the default selection). This compliance path does not require an on-site inspection of existing conditions prior to the start of construction. The attributes of the existing condition are undefined, with the standard design for altered components based on Section 150.2, Table 150.2-D, and the climate zone. Energy compliance credit or penalty is a function of the difference between the value for that specific feature allowed in Table 150.2-D and the modeled/installed efficiency of the feature.

   Verified Altered existing conditions. This compliance path requires that a HERS Rater perform an on-site inspection of pre-alteration conditions prior to construction. If an altered component or system meets or exceeds the prescriptive alteration requirements, the compliance software uses the user-defined and verified existing condition as the standard design value. Energy compliance credit is then based on the difference between the verified existing condition for that altered feature and the modeled/installed efficiency of the proposed design.

QII

Standard Design

The standard design includes QII for additions greater than 700 ft2 in any low-rise single-family residential building in Climate Zones 1-16 (Section 150.2[a]1Bv).

The provisions of Section 150.2(a)1Aiv, as applied to converting an existing unconditioned space to conditioned space, are accommodations made by the HERS Rater in the field. No adjustments to the energy budget are made.

PV

Standard Design

The standard design does not include PV for additions and alterations.

Roof/Ceilings

Standard Design

The standard design roof/ceiling construction assembly is based on the proposed design assembly type as shown in Table 27. For additions equal to or less than 700 ft2, radiant barrier requirements follow Option C (Section 150.1[c]9B). The standard design for unaltered ceilings and roofs is the existing condition.

Table 27: Standard Design for Roofs/Ceilings

Proposed Design Roof/Ceiling Types

Addition < 300 ft2

Addition > 300 ft2 and < 700 ft

Addition > 700 ft2

Altered

Verified Altered

Roof Deck Insulation (below-deck, where required) at vented attic

NR

NR

CZ 4, 8-16 = R-19

 

CZ 3, 5-7 = NR CZ 1, 2, 4, 8-16 = R-14/U-0.039

Existing

Ceilings Below Attic

 CZ 1, 2, 4, 8-16 = R-38
CZ 3, 5-7 = R-30

 CZ 1, 2, 4, 8-16 = R-38
CZ 3, 5-7 = R-30

 

CZ 1, 2, 4, 8-16 = R-38

CZ 3, 5-7 = R-30

CZ 5, 7 = R-19 CZ 1-4, 6, 8-16 = R-49

 

Existing

Non-Attic (Cathedral)
Ceilings and Roofs

R-22/U-0.043

R-22/U-0.043

Same as above

R-19/U-0.054

Existing

Radiant Barrier

 

CZ 2-15 REQ
CZ 1, 16 NR

CZ 2-15 REQ
CZ 1, 16 NR

CZ 2, 3, 5-7 REQ

CZ 1, 4, 8-16 NR

NR

Existing

Roofing Surface

(Cool Roof) Steep-Sloped

NR

CZ 10-15 =0.20 Reflectance, =0.75 Emittance

CZ 10-15 =0.20 Reflectance, =0.75 Emittance

CZ 4, 8-15
=0.20 Reflectance =0.75 Emittance

Existing

Roofing Surface

(Cool Roof) Low-Sloped

NR

CZ 13, 15 = 0.63 Reflectance, =0.75 Emittance

CZ 13, 15 = 0.63 Reflectance, =0.75 Emittance

CZ 4, 6-15
=0.63 Reflectance =0.75 Emittance

Existing

Above Deck Insulation, Low-Sloped

NR

NR

NR

CZ 1, 2, 4, 8-16 R-14 continuous

Existing

Source: California Energy Commission

Exterior Walls and Doors

Proposed Design

Existing structures with insulated wood-framed walls that are being converted to conditioned space using an E+A+A approach are allowed to show compliance using the existing wall framing, without having to upgrade to current prescriptive continuous insulation requirements. The walls are modeled as an assembly with the existing framing and either R-15 (in 2x4 framing) or R-21 (in 2x6 framing) insulation (Exception to Section 150.0[c]1 and Section 150.2[a]1).

Standard Design

The areas, orientation, and tilt of existing, new, and altered net exterior wall areas (with windows and doors subtracted) are the same in the existing and addition portions of standard design as in the proposed design.

If the proposed wall area is framed, the gross exterior wall area (excluding knee walls) is equally divided among the four building orientations: front, left, back and right. The gross exterior wall area of any unframed walls is also equally divided among the four orientations in the standard design.

The standard design exterior wall construction assembly is based on the proposed design assembly type as shown in Table 28. Framed walls are modeled as 16-in. on center wood framing. The standard design for unaltered walls is the existing condition.

The standard design for exterior opaque or swinging doors is 0.20 U-factor. Fire-rated doors (from the house to garage) use the proposed design door U-factor as the standard design U-factor.

Table 28: Standard Design for Walls and Doors

Proposed Design Exterior Wall Assembly Type or Door

Addition

 

Altered

Verified Altered

Framed & Non-Mass Exterior Walls

CZ 1-5, 8-16 = R-21+R-5 in 2x6 (U0.048)

CZ 6-7 = R-15+R-4 in 2x4 (U-0.065)

R-13 in 2x4

R-20 in 2x6

Existing

Wood framed existing walls where siding is not removed, or an

extension of an existing wall

R-15 in 2x4

R-21 in 2x6

R-13 in 2x4

R-20 in 2x6

 

 

Existing

Framed Wall Adjacent to Unconditioned
(e.g., Demising or Garage Wall)

R-15 in 2x4

R-21 in 2x6

R-13 in 2x4

R-20 in 2x6

Existing

Above Grade Mass Interior Insulated

CZ 1-15 = R-13 (0.077)

CZ 16 = R-17 (0.059)

N/R Mandatory requirements have no insulation for mass walls

Existing

Below Grade Mass Interior Insulation

CZ 1-15 = R-13 (0.077)

CZ 16 = R-15 (0.067)

N/R Mandatory requirements have no insulation for mass walls

Existing

Swinging Doors

0.20

0.20

Existing

Source: California Energy Commission

Fenestration

Proposed Design

Fenestration areas are modeled in the addition as new. In an existing building, they may be existing, altered, or new. Altered (replacement) fenestration is defined in Section 150.2(b)1B as “existing fenestration area in an existing wall or roof [which is] replaced with a new manufactured fenestration product... Up to the total fenestration area removed in the existing wall or roof....“ Altered also includes fenestration installed in the same existing wall, even if in a different location on that wall. Added fenestration area in an existing wall or roof is fenestration that did not previously exist and is modeled as new.

Standard Design

Standard design fenestration U-factor and SHGC are based on the scope of the project (addition vs. alteration), and for additions the square footage is taken into consideration as well, as shown in Table 29. Vertical glazing includes all fenestration in exterior walls such as windows, clerestories, and glazed doors. Skylights include all glazed openings in roofs and ceilings.

New fenestration in an alteration is modeled with the same U-factor and SHGC as required for an addition.

West-facing limitations are combined with the maximum fenestration allowed and are not an additional allowance.

The standard design is set for fenestration areas and orientations as shown in Table 29:

   Proposed design < allowed percentage of total fenestration area:

In the existing building, the standard design uses the same area and orientation of each existing or altered fenestration area (in the respective existing or altered wall or roof.)

In the addition, new fenestration is divided equally among the four project compass points similar to new gross wall areas in the addition described above.

   Proposed design > allowed percentage of total fenestration area:

The standard design first calculates the allowed total fenestration area as the total existing and altered fenestration area in existing or altered walls and roofs. Added to this is the percentage of fenestration allowed in the addition, based on the conditioned floor area of the addition.

Table 29: Standard Design for Fenestration (in Walls and Roofs)

Proposed Design Fenestration Type

Addition < 400 ft2

Addition > 400 and < 700 ft2

Addition > 700 ft2

Altered

Verified Altered

Vertical Glazing: Area and Orientation

75 ft2 or 30%

120 ft2 or 25%

175 ft2 or 20%

See full description below.

Existing

West Facing Maximum Allowed

CZ 2, 4, 6 -15=60 ft2

CZ 2, 4, 6 -15=60 ft2

CZ 2, 4, 6 -15=70 ft2 or 5%

NR

NR

Vertical Glazing:
U-Factor

0.30

0.30

0.30

0.40

See below

Vertical Glazing: SHGC

CZ 2, 4, 6-15=0.23 CZ 1,3, 5 & 16=0.35

CZ 2, 4, 6-15=0.23 CZ 1,3, 5 & 16=0.35

CZ 2, 4, 6-15=0.23
 CZ 1,3, 5 & 16=0.35

CZ 2, 4, 6-15=0.35 CZ 1,3, 5 & 16=0.35

Existing

Skylight:
Area and Orientation

No skylight area in the standard design

No skylight area in the standard design

No skylight area in the standard design

NR

Existing

Skylight: U-Factor

0.30

0.30

0.30

0.55

Existing

Skylight: SHGC

CZ 2, 4, 6 -15=0.23

CZ 1,3 5 & 16=0.35

CZ 2, 4, 6 -15=0.23
CZ 1,3 5 & 16=0.35

CZ 2, 4, 6 -15=0.23
CZ 1,3 5 & 16=0.35

CZ 2, 4, 6 -15=0.30
CZ 1,3 5 & 16=0.35

Existing

Source: California Energy Commission

Overhangs, Sidefins, and Other Exterior Shading

Standard Design

The standard design for a proposed building with overhangs, sidefins, and exterior shades is shown in Table 30. Exterior shading (limited to bug screens) is treated differently than fixed overhangs and sidefins, as explained in Section 2.5.6.9 Exterior Shading.

Table 30: Standard Design for Overhangs, Sidefins, and Other Exterior Shading

Proposed Design Shading Type

Addition

 

Altered

Verified Altered

Overhangs and Sidefins

No overhangs or sidefins

Proposed altered condition

Same as altered

Exterior Shading

Standard (bug screens on fenestration, none on skylights)

Proposed altered condition

Existing exterior shading

Window Film

 

No window film

Proposed altered condition

Existing exterior shading

Source: California Energy Commission

Window Film

Proposed Design

A window film must have at least a 15-year warranty and is treated as a window replacement. The values modeled are either the default values from Tables 110.6-A and 110.6-B or the NFRC Window Film Energy Performance Label.

Floors

Standard Design

Table 150.2-C requires that the standard design be based on the mandatory requirements from Section 150.0(d). The standard design for floors is shown in Table 31.

Table 31: Standard Designs for Floors

Proposed Design
Floor Type

Addition

 

Altered (mandatory)

Verified Altered

Raised Floor
Over Crawl Space
or Over Exterior

R-19 in 2x6 16” o.c. wood framing

R-19 in 2x6 16” o.c. wood framing

If proposed U < 0.037, standard design = existing raised; if proposed U > 0.037, standard design = 0.037

Slab-on-Grade: Unheated

CZ1-15: R-0

CZ16: R-7 16” vertical

R-0

Existing unheated slab-on-grade

Slab-on-Grade: Heated

CZ1-15: R-5 16” vertical

CZ 16: R-10 16” vertical

CZ1-15: R-5 16” vertical

CZ 16: R-10 16” vertical

Existing heated slab-on-grade

Raised Concrete Slab

CZ1,2,11,13,14,16: R-8
CZ3-10: R-0
CZ12,15: R-4

R-0

Existing raised concrete slab

Source: California Energy Commission

Thermal Mass

Standard Design

The standard design for thermal mass in existing plus addition plus alteration calculations is the same as for all newly constructed buildings as explained in Section 2.5.4.1 Internal Thermal Mass.

Air Leakage and Infiltration

Standard Design

Standard design air leakage and infiltration are shown in Table 32.

Table 32: Standard Design for Air Leakage and Infiltration

Proposed Air Leakage and Infiltration

Addition

 

Altered

 

Verified Altered

Single-Family Residential Buildings

5 ACH50

5 ACH50

Diagnostic testing of existing ACH50 value by HERS Rater

Source: California Energy Commission

Space Conditioning System

Standard Design

The standard design for space-conditioning systems is shown in Table 33.

When cooling ventilation (whole-house fan) is required by Section 150.1 and Section 150.2, the capacity is 1.5 CFM/ft2 of conditioned floor area for the entire dwelling unit.

When compliance with IAQ requirements of Section 150.0(o) apply to an addition with greater than 1,000 ft2 added, the conditioned floor area of the entire dwelling unit is used to determine the required ventilation airflow. For additions with 1,000 ft2 or less of added conditioned floor area, no IAQ requirements shall apply.

Table 33: Standard Design for Space Conditioning Systems

Proposed Design Space-Conditioning System Type

Addition

 

Altered

Verified Altered

Heating System Efficiency

See Section 2.10.4 Addition-Alone Approach and 2015 Federal Appliance Standards. based on fuel source and equipment type

Existing heating fuel type and equipment type/efficiency. If the existing equipment is electric resistance and none of the exceptions to Section150.2(b)1G are met, the Standard Design system shall be a heat pump meeting the requirements of Section 2.10.4 Addition-Alone ApproachSame as Addition.

Same as altered

Cooling System Efficiency

See Section 2.10.4 Addition-Alone Approach and 2015 Federal Appliance Standards based on fuel source and equipment type

Same as Addition

Existing cooling equipment type/efficiency

Refrigerant Charge

CZ 2, 8-15: Yes
CZ 1, 3-7: No

Same as Addition

Existing

Whole-House Fan (WHF) applies only if addition > 1,000 ft2

CZ 8-14; 1.5 CFM/ft2

N/A

Existing condition. To count as Existing the WHF must be > 1.5 CFM/ft2 and be CEC-rated

Indoor Air Quality applies only if addition > 1,000 ft2 or if addition is a dwelling unit

Meet mandatory ventilation for entire dwelling

Same as Addition

Existing

Source: California Energy Commission

Duct System

Proposed Design

Duct insulation shall be based on the new or replacement R-value input by the user. Duct leakage shall be based on the tested duct leakage rate entered by the user or a default rate of 30 percent.

Standard Design

Table 34: Standard Design for Duct Systems

Proposed Design Duct System Type

No Verification of Existing Conditions

Verified Existing Conditions

Altered or Extended Ducts >25 ft

CZ 1-2, 4, 8-16: Duct insulation R-8 and total leakage of 10%

CZ 3, 5-7: Duct insulation R-6 and total leakage of 10%

Existing duct R-value and total leakage the lesser of 30% or the existing leakage rate

New Ducts

CZ 1-2, 4, 8-16: Duct insulation R-8 and total leakage of 7%

CZ 3, 5-7: Duct insulation R-6 and total leakage of 7%

N/A

Based on Table 150.2-A

Note 1: Refer to Section 150.2(b)1Diia for definition of an “Entirely New or Complete Replacement Duct System.”

Source: California Energy Commission

Water Heating System

Standard Design

Table 35: Standard Design for Water Heater Systems

Proposed Design Water Heating System Type

Addition (adding water heater)

Altered

Verified Altered

Single-Family Residential Buildings

Prescriptive water heating system per Section 2.10.4 Addition-Alone Approach

Proposed fuel type, proposed tank type, mandatory requirements (with no solar)

Existing water heater type(s), efficiency, distribution system.

Source: California Energy Commission