9.8  Solar-Ready Overview

§110.10

This chapter of the nonresidential compliance manual addresses solar-ready requirements for hotels/motels, nonresidential, and high-rise multifamily buildings. These requirements are in §110.10|topic=SECTION 110.10 – MANDATORY REQUIREMENTS FOR SOLAR READINESS and §141.0 and are mandatory for newly constructed buildings and additions where the total roof area is increased by at least 2,000 square feet.

The solar-ready requirement is implemented when designing the building rooftop and associated equipment. The intent is to reserve a penetration-free and shade-free portion of the roof for the potential future installation of a solar energy system. There are no requirements to install panels, conduit, piping, or mounting hardware.

9.8.1      Overview

The solar-ready provisions are mandatory; “trade-offs” are not allowed. There are exceptions to the “solar zone” requirements, and these are described in the corresponding sections of this chapter. Because solar ready is mandatory, the NRCC-SRA-E compliance form must be submitted with the building permit application, even when using an allowable solar zone exception.

9.8.2      Covered Occupancies

§110.10(a)

The nonresidential solar-ready requirements apply to:

    Hotel/motel occupancies with 10 stories or fewer.

    All other nonresidential buildings with three stories or fewer.

    See Example 9-15

Mixed-Occupancy Buildings: The Energy Standards apply to mixed-occupancy buildings. Buildings with nonresidential space on the ground floor and multifamily residential floors above are common examples.

9.8.3      Solar Zone

§110.10(b)|topic=(b) Solar Zone.

The solar zone is a suitable place where solar panels can be installed at a future date if the owner chooses to do so. A solar zone area is designed with no penetrations, obstructions, or significant shade. The solar zone must comply with the access, pathway, smoke ventilation, and spacing requirements in Title 24, Part 9. Requirements from the other parts of Title 24 and those adopted by a local jurisdiction should also be incorporated in the solar zone design.

The solar zone can be located at any of the following locations:

    Roof of building

    Overhang of the building

    Covered parking installed with the building project

    Roof of another structure located within 250 feet (75 meters) of the primary building

    Overhang of another structure within 250 feet (75 meters) of the primary building

Other structures include, but are not limited to, trellises, arbors, patio covers, carports, gazebos, and similar accessory structures.

Multifamily Buildings: Solar-ready requirements for low-rise and high-rise multifamily buildings are in Chapter 11 of the Nonresidential Compliance Manual. In the 2022 Energy Standards, the solar zone requirements for low-rise multifamily buildings are grouped with high-rise multifamily, hotel/motel and nonresidential in §110.10(b)1B|topic=(b) Solar Zone..

9.8.4      Solar Zone Minimum Area and Exceptions

§110.10(b)1|topic=(b) Solar Zone.

Total Area: The solar zone must have a total area of at least 15 percent of the total roof area, after subtracting any skylights. See Example 9-16.

Multiple areas: The solar zone may be composed of multiple subareas if they meet the following minimum size specifications:

1.    Each subarea dimension must be at least 5 feet.

2.    If the total roof area is equal to or less than 10,000 square feet, each subarea must be at least 80 square feet.

3.    If the total roof area is greater than 10,000 square feet, each subarea must be at least 160 square feet.

Example 9-14:

Question:

A roof with no skylights has an area of 10,000 sq. ft. A neighboring building shades the roof, so 7,500 sq. ft of the roof has less than 70 percent annual solar access. How big does the solar zone have to be?

A roof with no skylights has an area of 10,000 sq. ft. A neighboring building shades the roof, so 7,500 sq. ft of the roof has less than 70 percent annual solar access.

Answer:

If the entire roof had an annual solar access of 70 percent or greater, the minimum solar zone would be 1,500 sq. ft, or 15 percent of the total roof area (10,000 sq. ft.). However, since the potential solar zone is 2,500 sq. ft, the minimum solar zone can be reduced to half the area of the potential solar zone, or 1,250 sq. ft.

Example 9-15:

Question:

The total roof area is less than 10,000 sq. ft., but the potential solar zone is less than the minimum size requirements for any subarea (less than 80 sq. ft. or narrower than 5 feet in the smallest dimension). Does the building still need to comply with the solar-ready requirements?

Answer:

No. If half the potential solar zone is less than 80 sq. ft. (if roof is less than or equal to 10,000 sq. ft) or 160 sq. ft. (if roof is greater than 10,000 sq. ft), then the building does not need to comply with the solar zone requirements.

Example 9-16:

Question:

A portion of an office building will have six stories, and a portion of the building will have two stories. Is the new building subject to the solar zone requirements?

Answer:

No, the solar-ready requirements do not apply to office buildings that have more than three stories. The solar-ready requirements apply only to hotel/motel occupancies and high-rise multifamily buildings with 10 or fewer stories and all other nonresidential buildings with 3 or fewer stories.

Example 9-17:

Question:

A new warehouse has a total roof area of 80,000 sq. ft. Skylights cover 2,560 sq. ft. of the total roof area. What is the minimum solar zone area?

An image of roof schematic  where the total roof area is 400 feet by 200 feet equaling 80,000 square feet. The total area covered by skylights.

Answer:

The minimum solar zone area would be 11,616 sq. ft

Example 9--18:

Question:

Does the solar zone have to be one contiguous area?

Answer:

No, the solar zone does not have to be one contiguous area. The total solar zone can be composed of multiple smaller areas. A subarea cannot be narrower than 5 feet in any dimension. If the total roof area is 10,000 sq. ft or less, each subarea must be at least 80 sq. ft. If the total roof area is greater than 10,000 sq. ft, each subarea must be at least 160 sq. ft.

The image below illustrates a solar zone layout that is composed of eight smaller subareas. The sum of all the smaller areas must equal the minimum total solar zone area. In this case, the sum of all areas must be at least 11,616 sq. ft. The solar zones must also comply with fire code requirements, including, but not limited to, setback and pathway requirements. Current fire code requirements can be found in Title 24 Part 2 § 3111, Title 24 Part 2.5 §R331, and Title 24 Part 9 § 903.3.

The image illustrates a solar zone layout that is composed of eight smaller subareas.

9.8.5      Solar Zone Exceptions

There are five exceptions to the solar zone area requirement described in §110.10(b)1B|topic=(b) Solar Zone.. Some exceptions are limited to certain buildings, as noted in the exception details below. Submit an NRCC-SRA-E, the "Solar Ready Areas" certificate of compliance to the enforcement agency for all building projects subject to solar ready, even if using a solar zone exception.

Exception 3 allows a reduced-size solar zone when solar access is limited by certain circumstances.

Exceptions 1, 2, and 4 allow alternate efficiency measures instead of a solar zone, so the requirements for zone shading, orientation, and design load; interconnection pathway; and owner documentation do not apply either. Any installations must be inspected and verified prior to final approval by the enforcement agency.

Exception 1: A compliant solar electric system is permanently installed on high-rise multifamily, hotel/motel, and nonresidential buildings. The system must have a nameplate direct current (DC) power rating of no less than 1 watt per sq. ft of roof area. The nameplate rating must be measured under standard test conditions. See Example 9-6. To verify compliance with this exception, submit NRCI-SPV-01-E Certificate of Installation: Solar Photovoltaic System.

Exception 2: A solar hot water system (SWH) is permanently installed on high-rise multifamily, hotel/motel, and nonresidential buildings. The SWH system must comply with §150.1(c)8Biii|topic=8. Domestic Water-Heating Systems., the prescriptive solar requirements for a system serving multiple dwelling units. To verify compliance with this exception, submit NRCI-STH-01-E Certificate of Installation: Solar Water Heating System.

Exception 3: Reduce the solar zone area when the roof is shaded by objects that are not part of the building project, and therefore beyond the designer’s control.  The designated solar zone may be reduced to ≥ 50 percent of the potential solar zone area when solar access is limited as described below. When the “potential” solar zone is smaller than the 250 sq. ft minimum, the solar zone can be reduced to half the area of the potential solar zone. The reduced-size solar zone is called the “designated” solar zone.

Exception for Reduced Solar Zone

Step 1: Determine the annual solar access: For the solar-ready requirements, solar access is the ratio of solar insolation including shading to the solar insolation without shading. Annual solar access is most easily determined using specialized software.

Solar access does not take into account shading from objects that are included in the building project because the designer has control of potential obstructions. Objects that are not part of the building project cannot be moved or modified as part of the project and include existing buildings, telephone poles, communication towers, trees, or other objects. Objects that are considered part of the building project are objects constructed as part of the building project and include the building itself, its HVAC equipment, outdoor lights, landscape features and other similar objects.

First, evaluate whether there are any objects outside the building project that will shade the rooftop (or other prospective solar zone areas such as overhangs or parking shade structures). If an existing object is located north of all potential solar zones, the object will not shade the solar zone. Similarly, if the horizontal distance (“D”) from the object to the solar zone is at least two times the height difference (“H”) between the highest point of the object and the horizontal projection of the nearest point of the solar zone, then the object will not shade the solar zone. (See Figure 9-2.)

Step 2: Determine the potential solar zone area: On low-sloped roofs, the potential solar zone is the area where annual solar access is ≥ 70 percent.

On steep-sloped roofs the potential solar zone is the area where the annual solar access is

≥ 70 percent on the portion oriented between 90 and 300 degrees of true north.

A “demand-responsive control” is defined in §100.1. as an “automatic control capable of receiving and automatically responding to a demand response signal.” The technical specifications for compliant demand responsive control thermostats are detailed in JA5.

In addition to the demand-responsive thermostats, choose Option A or Option B (below).

Each dwelling unit must have one of the following four measures (1 – 4):

a)    Install a dishwasher that meets or exceeds the ENERGY STAR® program requirements with either a refrigerator that meets or exceeds the ENERGY STAR program requirements or a whole-house fan driven by an electronically commutated motor.

b)    Install a home automation system that complies with §110.12(a)|topic=(a) Demand responsive controls. and capable of, at a minimum, controlling the appliances and lighting of the dwelling and responding to demand-response signals.

c)    Install alternative plumbing piping to permit the discharge from the clothes washer and all showers and bathtubs to be used for an irrigation system. It must comply with the California Plumbing Code and local ordinances.

d)    Install a rainwater catchment system that uses rainwater flowing from at least 65 percent of the available roof area. It must comply with the California Plumbing Code and local ordinances.

Meet the Title 24 Part 11, Section A4, 106.8.2 requirements for electric vehicle charging spaces.

Exception 5: Applies to multifamily, hotel/motel, and nonresidential buildings. If the roof is designed and approved to be a heliport, or used for vehicular traffic or parking, no solar zone is required. Therefore, interconnection pathway and documentation requirements do not apply.

9.8.5.1      Solar Zone Azimuth

150.1(c)8Biii

All sections of the solar zone on steep-sloped roofs (rise-to-run ratio greater than 2:12, or 10 degrees) must be oriented between azimuths of 90 degrees and 300 degrees of true north. This range of azimuths  ensures a reasonable solar exposure if a solar energy system is installed in the future. On a low-sloped roof (rise-to-run ratio equal to or less than 2:12, or 10 degrees), the azimuth requirement does not apply.

Figure 9-1: Azimuth of Roof If Solar Zone Is Located on Steep-Sloped Roof

Chart of the orientation of roof if the solar zone is located on a sloped roof. A 2 to 12 slope ratio is necessary, and the chart has north arrow point up at zero degrees, a right arrow at 90 degrees and the left arrow at 300 degrees.

Source: California Energy Commission

9.8.5.2      Solar Zone Shading

§110.10(b)3|topic=(b) Solar Zone. Obstructions such as vents, chimneys, architectural features, or roof-mounted equipment cannot be located in the solar zone. This requirement ensures the solar zone remains clear and open for the future installation of a solar energy system.

Any obstruction located on the roof or any other part of the building that projects above the solar zone must be located at a sufficient horizontal distance away from the solar zone such that the obstruction will not shade the solar zone. Equation 9-5 and Figure 9.2 describe the allowable distance between any obstruction and the solar zone. For each obstruction, the horizontal distance (“D”) from the obstruction to the solar zone has to be at least two times the height difference (“H”) between the highest point of the obstruction and the horizontal projection of the nearest point of the solar zone.