SECTION 140.10 – PRESCRIPTIVE REQUIREMENTS FOR PHOTOVOLTAIC AND BATTERY STORAGE SYSTEMS

(a)      Photovoltaic Requirements.

All newly constructed building types specified in Table 140.10-A, or mixed occupancy buildings where one or more of these building types constitute at least 80 percent of the floor area of the building, shall have a newly installed photovoltaic (PV) system meeting the minimum qualification requirements of Reference Joint Appendix JA11. The PV size in kWdc shall be not less than the smaller of the PV system size determined by Equation 140.10-A, or the total of all available Solar Access Roof Areas (SARA) multiplied by 14 W/ft². 

1.    SARA includes the area of the building’s roof space capable of structurally supporting a PV system, and the area of all roof space on covered parking areas, carports, and all other newly constructed structures on the site that are compatible with supporting a PV system per Title 24, Part 2, Section 1511.2.

2.    SARA does NOT include:

A.    Any area that has less than 70 percent annual solar access. Annual solar access is determined by dividing the total annual solar insolation (accounting for shading obstructions) by the total annual solar insolation if the same areas were unshaded by those obstructions. For all roofs, all obstructions including those that are external to the building, and obstructions that are part of the building design and elevation features may be considered for the annual solar access calculations.

B.    Occupied roofs as specified by CBC Section 503.1.4.

C.    Roof space that is otherwise not available due to compliance with other building code requirements if confirmed by the Executive Director.

 

EQUATION 140.10-A PHOTOVOLTAIC DIRECT CURRENT SIZE

kWPVdc = (CFA x A)/1000

WHERE:

kWPVdc        =             Size of the PV system in kW

CFA    =       Conditioned floor area in square feet

A =   PV capacity factor specified in Table 140.10-A for the building type

Where the building includes more than one of the space types listed in Table 140.10-A, the total PV system capacity for the building shall be determined by applying Equation 140.10-A to each of the listed space types and summing the capacities determined for each. 

EXCEPTION 1 to Section 140.10(a).  No PV system is required where the total of all available SARA is less than three percent of the conditioned floor area.

EXCEPTION 2 to Section 140.10(a).  No PV system is required where the required PV system size is less than 4 kWdc.

EXCEPTION 3 to Section 140.10(a). No PV system is required if the SARA contains less than 80 contiguous square feet.

EXCEPTION 4 to Section 140.10(a).  Buildings with enforcement-authority-approved roof designs, where the enforcement authority determines it is not possible for the PV system, including panels, modules, components, supports, and attachments to the roof structure, to meet  ASCE 7-16, Chapter 7, Snow Loads.

EXCEPTION 5 to Section 140.10(a). Multitenant buildings in areas where a load serving entity does not provide either a Virtual Net Metering (VNEM) or community solar program.

(b)      Battery Storage System Requirements.

All buildings that are required by Section 140.10(a) to have a PV system shall also have a battery storage system meeting the minimum qualification requirements of Reference Joint Appendix JA12.  The rated energy capacity and the rated power capacity shall be not less than the values determined by Equation 140.10-B and Equation 140.10-C.   Where the building includes more than one of the space types listed in Table 140.10-B, the total battery system capacity for the building shall be determined by applying Equations 140.10-B and 140.10-C to each of the listed space types and summing the capacities determined for each space type and equation.

EQUATION 140.10-B - BATTERY STORAGE RATED ENERGY CAPACITY

kWhbatt = kWPVdc x B / D0.5

WHERE:

kWhbatt =       Rated Useable Energy Capacity of the battery storage system in kWh

kWPVdc    =       PV system capacity required by section 140.10(a) in kWdc

B        =   Battery energy capacity factor specified in Table 140.10-B for the building type

D =   Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the battery storage system

 

EQUATION 140.10-C - BATTERY STORAGE RATED POWER CAPACITY

kWbatt = kWPVdc x C

WHERE:

kWbatt         =             Power capacity of the battery storage system in kWdc

kWPVdc        =             PV system capacity required by section 140.10(a) in kWdc

C         =       Battery power capacity factor specified in Table 140.10-B for the building type

 

EXCEPTION 1 to Section 140.10(b). No battery storage system is required if the installed PV system size is less than 15 percent of the size determined by Equation 140.10-A.

EXCEPTION 2 to Section 140.10(b). No battery storage system is required in buildings with battery storage system requirements with less than 10 kWh rated capacity.

EXCEPTION 3 to Section 140.10(b). For multi-tenant buildings, the energy capacity and power capacity of the battery storage system shall be based on the tenant spaces with more than 5,000 square feet of conditioned floor area. For single-tenant buildings with less than 5,000 square feet of conditioned floor area, no battery storage system is required.

EXCEPTION 4 to Section 140.10(b). In climate zone 1, no battery storage system is required for offices, schools, and warehouses.

 

Table 140.10-A – PV Capacity Factors

Factor A – Minimum PV Capacity (W/ft² of conditioned floor area)

Climate Zone

1, 3, 5, 16

2, 4, 6-14

15

Grocery

2.62

2.91

3.53

High-Rise Multifamily

1.82

2.21

2.77

Office, Financial Institutions, Unleased Tenant Space

2.59

3.13

3.80

Retail

2.62

2.91

3.53

School

1.27

1.63

2.46

Warehouse

 

0.39

0.44

0.58

Auditorium, Convention Center, Hotel/Motel, Library, Medical Office Building/Clinic, Restaurant, Theater

0.39

0.44

0.58

 

Table 140.10-B – Battery Storage Capacity Factors

Factor B – Energy Capacity

Factor C – Power Capacity

Storage-to-PV Ratio

Wh/W

W/W

Grocery

1.03

0.26

High-Rise Multifamily

1.03

0.26

Office, Financial Institutions, Unleased Tenant Space

1.68

0.42

Retail

1.03

0.26

School

1.87

0.46

Warehouse

 

0.93

0.23

Auditorium, Convention Center, Hotel/Motel, Library, Medical Office Building/Clinic, Restaurant, Theater

0.93

0.23

NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.