Section 160.6 - Mandatory Requirements for Electric Power Distribution Systems

Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).

(a) Service electrical metering. Each electrical service or feeder that provides power to the common use areas (interior and exterior) shall have a permanently installed metering system that measures electrical energy use in accordance with TABLE 160.6-A.

EXCEPTION to Section 160.6(a): Service or feeder for which the utility company provides a metering system for the multifamily building that indicates instantaneous kW demand and kWh for a utility-defined period.

TABLE 160.6-A MINIMUM REQUIREMENTS FOR METERING OR SUBMETERING OF ELECTRICAL LOAD

Metering Functionality
Electrical Services1
rated 50 kVA or less
Electrical Services1
rated more than 50kVA and less than or equal to 250 kVA
Electrical Services1 rated more than 250 kVA and less than or equal to 1000kVA
Electrical Services1 rated more than 1000kVA
Instantaneous (at the time) kW demand
Required
Required
Required
Required
Historical peak demand (kW)
Not required
Not required
Required
Required
Tracking kWh for a user-definable period.
Required
Required
Required
Required
kWh per rate period
Not required
Not required
Not required
Required
1 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use areas.

(b) Separation of electrical circuits for electrical energy monitoring. Electrical power distribution systems shall be designed so that measurement devices can monitor the electrical energy usage of load types according to TABLE 160.6-B.

EXCEPTION 1 to Section 160.6(b): For each separate load type, up to 10 percent of the connected load may be of any type.

EXCEPTION 2 to Section 160.6(b): Submetered electrical power distribution systems that provide power to dwelling units.

TABLE 160.6-B MINIMUM REQUIREMENTS FOR SEPARATION OF ELECTRICAL LOAD

Electrical Load Type
Electrical Services1 rated 50 kVA or less
Electrical Services1 rated more than 50kVA and less than or equal to 250 kVA
Electrical Services1 rated more than 250 kVA and less than or equal to 1000kVA
Electrical Services1 rated more than 1000kVA
Lighting including exit and egress lighting and exterior lighting
Not required
All lighting in aggregate
lighting disaggregated by floor, type or area
All lighting disaggregated by floor, type or area
HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers, and circulation pumps associated with HVAC
Not required
All HVAC in aggregate
All HVAC in aggregate and each HVAC load rated at least 50 kVA
All HVAC in aggregate and each HVAC load rated at least 50kVA
Domestic and service water system pumps and related systems and components
Not required
All loads in aggregate
All loads in aggregate
All loads in aggregate
Plug load including appliances rated less than 25 kVA
Not required
All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf
All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf
All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf
Elevators, escalators, moving walks, and transit systems
Not required
All loads in aggregate
All loads in aggregate
All loads in aggregate
Renewable power source (net or total)
Each group
Each group
Each group
Each group
Loads associated with renewable power source
Not required
All loads in aggregate
All loads in aggregate
All loads in aggregate
Charging stations for electric vehicles
All loads in aggregate
All loads in aggregate
All loads in aggregate
All loads in aggregate
1 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use area.

(c) Voltage drop. The maximum combined voltage drop on both installed feeder conductors and branch circuit conductors to the farthest connected load or outlet shall not exceed 5 percent.

EXCEPTION to Section 160.6(c): Voltage drop permitted by California Electrical Code Sections 647.4, 695.6 and 695.7.

(d) Circuit controls for 120-Volt receptacles and controlled receptacles. In all common areas, both controlled and uncontrolled 120 volt receptacles shall be provided in office areas, lobbies, conference rooms, kitchen areas in office spaces, and copy rooms. Controlled receptacles shall meet the following requirements, as applicable:

1. Install a control capable of automatically shutting OFF the controlled receptacles when the space is typically unoccupied, either at the receptacle or circuit level. When an automatic time switch control is installed it shall incorporate an override control that allows the controlled receptacle to remain ON for no more than 2 hours when an override is initiated and an automatic holiday “shut-OFF” feature that turns OFF all loads for at least 24 hours and then resumes the normally scheduled operation. Countdown timer switches shall not be used to comply with the automatic time switch control requirements; and

2. Install at least one controlled receptacle within 6 feet from each uncontrolled receptacle, or install a splitwired receptacle with at least one controlled and one uncontrolled receptacle. Where receptacles are installed in modular furniture in open office areas, at least one controlled receptacle shall be installed at each workstation; and

3. Provide a permanent and durable marking for controlled receptacles or circuits to differentiate them from uncontrolled receptacles or circuits; and

NOTE: A hardwired power strip controlled by an occupant sensing control may be used to comply with Section 160.6(d). Plug-in strips and other plug-in devices shall not be used to comply with the requirements of this Section.

EXCEPTION 1 to Section 160.6(d): Receptacles that are only for the following purposes:

  1. Receptacles specifically for refrigerators and water dispensers in kitchen areas.
  2. Receptacles located a minimum of six feet above the floor that are specifically for clocks.
  3. Receptacles for network copiers, fax machines, A/V and data equipment other than personal computers in copy rooms.
  4. Receptacles on circuits rated more than 20 amperes.
  5. Receptacles connected to an uninterruptible power supply (UPS) that are intended to be in continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.

EXCEPTION 2 to Section 160.6(d): Receptacles in common use areas providing shared provisions for living, eating, cooking, or sanitation to dwelling units that would otherwise lack these provisions.

(e) Demand responsive controls and equipment. See Section 110.12 for requirements for demand responsive controls and equipment.

NOTE: Definitions of terms and phrases in Section 160.6 are determined as specified in Section 100.1(b). Terms and phrases not found in Section 100.1(b) shall be defined as specified in Title 24, Part 3, Article 100 of the California Electrical Code.

NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.

This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2024 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.