Appendix JA18 - Guideline 36 Programming Library Requirements
JA18.1 Purpose and Scope

Title 24, Part 6, Section 140.4(r) requires that HVAC control systems with DDC use programming originating from a certified programming library based on control sequences of operation described in ASHRAE Guideline 36. This section describes the requirements of the Guideline 36 programming library. 

HVAC Controls technology companies shall certify to the Energy Commission that the Guideline 36 Programming Library meets the requirements of Reference Joint Appendix JA18. 


JA18.2 Certification Submittal Requirements

Each company wishing to certify that their Guideline 36 programming library conforms to the Guideline 36 library requirements of Title 24, Part 6, may do so in a written declaration. This requires that a letter be sent to the California Energy Commission declaring that the Guideline 36 library is complete and conforms to the requirements listed in JA18.3. The declaration at the end of this section shall be used to submit to the California Energy Commission.

JA18.3 Information that shall be included with the Declaration

The certifying company shall provide evidence of compliance with these requirements, including the following at a minimum:

Evidence: List of hardwired points and control points used in the library. 

Evidence: Documentation of test plan and results, including inputs and outputs for each test.

Evidence: Documentation of programming, such as screenshots of programming function blocks or programming script. 


JA18.4 Programming Library Requirements

The programming library to be certified shall include complete control logic for all sections from ASHRAE Guideline 36 listed in Table JA18.4-1, and shall meet the minimum validation requirements listed.

Table JA18.4-1 Required Guideline 36 Logic for Certified Programming Library
Guideline 36 Logic Section Minimum Validation Requirements
Section 5.1
General Sections 5.1.14 and 5.1.17.3 only
Trim and Respond Setpoint Reset Logic, including Importance Multipliers, Request-Hours Accumulator, and Trim and Respond Variables per 5.1.14
Air Economizer High Limits based on device type and climate zone, per 5.1.17.3
Section 5.2
Generic Ventilation Zones (Section 5.2.1.3 is not required)
Zone minimum outdoor air setpoints and occupied minimum airflow calculations per 5.2.1.4
Time-averaged ventilation logic per 5.2.2

Section 5.3

Generic Thermal Zones

Independently adjustable zone heating and cooling setpoints, demand limit setpoint adjustments, and setbacks per 5.3.2
Heating Loop and Cooling Loop are separate control loops per 5.3.4
Section 5.4
Zone Groups
Separate schedules for each Zone Group per 5.4.2
All zones in a Zone Group are in the same Operating Mode per 5.4.3
Zone Group Operating Modes per 5.4.6
Section 5.5
VAV Terminal Unit— Cooling Only
Airflow endpoints determined by Zone Group Mode per 5.5.4
Airflow setpoint is reset by Heating Loop or Cooling Loop signals per 5.5.5
System Requests per 5.5.8
Section 5.6
VAV Terminal Unit with Reheat
Airflow endpoints determined by Zone Group Mode per 5.6.4
Airflow setpoint is reset by Heating Loop or Cooling Loop signals per 5.6.5 System Requests per 5.6.8
Section 5.15
Air-Handling Unit System Modes
All Operating Modes defined for Zone Groups (see Section 6.4) are also defined for air-handling units per 5.15.1
Section 5.16
Multiple-Zone VAV Air-Handling Unit(Sections 5.16.3.1, 5.16.4.1, 5.16.5.1, 5.16.6.1, and 5.16.11.2.a are not required)
Fan speed control and duct static pressure setpoint reset using trim and respond logic per 5.16.1
Supply air temperature control, temperature setpoint reset based on outdoor air temperature and trim and respond logic, and air economizer high limits per 5.16.2
System outdoor airflow requirements dynamically calculated for Zone Groups in Occupied Mode in accordance with Title 24 ventilation requirements, per 5.16.3.2
Minimum outdoor air control for multiple supported equipment configurations per 5.16.4, 5.16.5, and 5.16.6, using Title 24 ventilation logic.
Building relief per 5.16.8 and 5.16.9
Return fan control, per 5.16.10 and 5.16.11
Fan, filter, and pressure alarms per 5.16.13
Automatic FDD based on equipment operating state, including diagnostics based on fault conditions per 5.16.14
Plant Requests per 5.16.16
JA18.5 Declaration

Consistent with the requirements of Title 24, Part 6, Sections 100.0(h) and 140.4(r) companies wishing to certify to the California Energy Commission shall execute a declaration under penalty of perjury attesting that all information provided is true, complete, accurate, and in compliance with the applicable provisions of Part 6. Companies may fulfill this requirement by providing the information, signing the declaration below and submitting to the California Energy Commission as specified by the instructions in JA18.6. 


Company, Product Line, and Version Number of all Libraries Being Certified 

Company

Product Line

Guideline 36 Version

Library Version

 

 

 

 

 

 

 

 

 

 

 

 

When providing the information below, be sure to enter complete mailing addresses, including postal/zip codes.


Certifying Company

Contact Person Name *

Phone 1

Certifying Company Name **

Phone 2

Address

Fax

Address
E-mail
Address
Company Website (URL)

* If the contact person named above is NOT the person whose signature is on the Declaration, then the full contact information for the person whose signature is on the Declaration must also be provided on a separate page.

** If the company named above is: A) a parent entity filing on behalf of a subsidiary entity; B) a subsidiary entity filing on behalf of a parent entity; or C) an affiliate entity filing on behalf of an affiliate entity, the above contact information must be provided for any additional entities on a separate page.


Manufacturer (if different from Certifying Company)

Contact Person Name

Phone 1

Manufacturing Company Name

Phone 2

Address

Fax

(Address)

E-mail

(Address)

Company Website (URL)


Declaration

I declare under penalty of perjury under the laws of the State of California that:

(1)    All the information in this statement is true, complete, accurate, and in compliance with all applicable provisions of Section 140.4(r) of Title 24, Part 6 of the California Code of Regulations.

(2)    [If the party submitting this statement is a corporation, partnership, or other business entity] I am authorized to make this declaration, and to file this statement, on behalf of the company named below.

 

 

 

Certifying Company Name


 

Date

Name/Title (please print)


 

Signature




JA18.6 Certification

Send declarations and evidence of functionality or test reports to the addresses below. Electronic submittals are preferred.

Electronic submittal:

CertifiedtoCEC@energy.ca.gov

Attn: Guideline 36 programming library Certification


Mail:

Attn: Guideline 36 programming library Certification

Building Standards Development Branch

California Energy Commission

715 P Street, MS 37

Sacramento, CA 95814