Appendix JA8 Qualification Requirements for High Luminous Efficacy Light Sources
JA8.1 Purpose and Scope

Joint Appendix JA8 provides the qualification requirements for high luminous efficacy light sources installed to comply with Section 150(k). For the purposes of this Section, high luminous efficacy light sources include ballasts or LED drivers if needed for operation of the light source: light sources shall be certified together with a driver or ballast. If the light source is inseparable from the luminaire the entire luminaire shall meet the requirements of this section. All qualifying light sources shall be certified to the Energy Commission according to all of the requirements in this Appendix.

JA8.2 Certification of Test Labs

The light source under test shall be tested at a testing laboratory accredited to ISO/IEC 17025:2017, by the National Voluntary Laboratory Accreditation Program (NVLAP) or other laboratory accreditation body operating in accordance with ISO/IEC 17011 and produced under an ongoing inspection program carried out by a Type A inspection body in accordance with ISO/IEC 17020.

JA8.3 Tests to be performed

Compliance with the requirements of this Appendix shall be determined by performance of the following test procedures, as applicable to the type of light source.

Sample group size shall be as specified in the referenced test procedures. Where a sample group is not specified for a test, a single unit shall be tested.

JA8.3.1 Luminous Efficacy Test

For federally regulated light sources, luminous efficacy shall be determined by the test procedures specified in 10 CFR 429 Subpart B and 10 CFR 430.23(gg).

   For non-federally-regulated light sources, luminous efficacy at full light output shall be determined by the following test procedures, as applicable to the type of light source:    

  1. For LED light sources, IES LM-79.    
  2. For high intensity discharge lamps, IES LM-51.
  3. For induction lamps, IES LM-66.

The reported value shall be the minimum luminous efficacy of the tested units and be rounded to the nearest tenth.

JA8.3.2 Power Factor Test

Power factor shall be measured at full light output in accordance with ANSI C82.77, Section 6 and 7.

For lamps, the reported value shall be the average measured values of the tested units rounded to be the nearest tenth.

For all other sources, the reported value shall be the minimum power factor of the tested units rounded to the nearest tenth.

JA8.3.3 Start Time Test

Start time shall be measured in accordance with the Start Time Test Method as specified in Section JA8.7, subject to the following modifications:

For lamps the reported value shall be the average start time of the tested units rounded to the nearest millisecond.

For all other light sources the reported value shall be the maximum start time of the tested units rounded to the nearest millisecond.

For light sources that provide a fade-in feature, the initial plateau shall be the point specified in JA8.7.1.

For light sources with a standby mode consuming no more than 0.2 watts of power, the start time test may be performed with the product receiving power and in this mode. In this case, the start time shall be the time between the sending of an on signal to the device via an appropriate control and the initial plateau.

JA8.3.4 Color Characteristics Tests

Correlated Color Temperature (CCT) and Color Rendering Index of federally-regulated light sources shall be determined by the test procedures specified in 10 CFR 429 Subpart B and 10 CFR 430.23(gg).

   Correlated Color Temperature (CCT) and Color Rendering Index of non-federally-regulated light sources shall be determined by the following test procedures, as applicable to the type of light source:    

       
  1. Induction lamps: IES LM-66.
  2.    
  3. LED light sources: IES LM 79.
  4.    
  5. High intensity discharge lamps: IES LM-51.
  6.    
  7. Other equipment: other applicable test procedure approved by the Executive Director

Nominal Correlated Color Temperature (CCT) shall be calculated in accordance with CIE 15 (reference document ANSI C78.377). Color Rendering Index (CRI) shall be calculated in accordance with CIE 13.3.

The reported value shall be the average measured values of units tested rounded to be the nearest whole number for CRI.

JA8.3.5 RESERVED
JA8.3.6 RESERVED
JA8.3.7 Tests for Minimum Dimming Level, Flicker, and Audible Noise

Light sources shall be tested for flicker using Joint Appendix 10.

The audible noise test shall be performed as specified in the Noise Test Method as specified in Section JA8.8.

Minimum dimming level is measured by comparing the stabilized light output of the light source with the dimming control set to full light output with the dimming control being set to the manufacturer’s minimum rated output. Full light output and minimum light output is measured after the light output has stabilized according to the test procedures specific to light source type in Section JA8.3.1.

In addition to the reporting of flicker results as described in Section JA8.6, flicker test data for each combination of light source, ballast or driver (if applicable), transformer type and dimmer type claiming compliance with JA8 shall be submitted to the California Energy Commission.

Testing for minimum dimming level, flicker, and audible noise is required for each combination of light source, ballast or driver (if applicable), transformer type and dimmer type as follows:

  1. Low voltage light sources shall be tested with a representative transformer for each transformer type that the light source is claiming compatibility.
  2. Light sources claimed as compatible with forward phase-cut dimmers shall be tested in combination with a NEMA SSL 7A compliant dimmer.
  3. Light sources claimed as compatible with dimmers other than forward phase-cut dimmers, dimmability, low noise and low flicker operation shall be tested for each ballast or driver combination (if applicable) with at least one representative dimmer for each dimmer type for which compatibility is claimed.
JA8.4 Qualification Requirements

The following qualification requirements must be met for the light source to be considered High Luminous Efficacy as specified in Section 150(k).

JA8.4.1 Luminous Efficacy

The light source shall meet the following requirements when measured in accordance with the test method of Section JA8.3.1:

The luminous efficacy of the light source shall be equal to or greater than either the applicable State or federal appliance efficiency standard or 45 lumens/Watt, whichever is higher, when tested at its full light output.

JA8.4.2 Power Factor

The light source shall meet the following requirements when measured in accordance with the test method of Section JA8.3.2:

The light source shall have a power factor equal to or greater than 0.90 when tested at its full light output.

JA8.4.3 Start Time

The light source shall meet the following requirements when measured in accordance with the test method of Section JA8.3.3:

The light source shall have a start time no greater than 0.5 seconds.

JA8.4.4 Color Characteristics

The light source shall meet the following CCT and color rendering requirements when measured in accordance with the test method of Section JA8.3.4:

  1. LED lamps regulated by the Title 20 Appliance Efficiency Regulations and subject to Color Rendering Index requirements under Title 20 shall comply with the Color Rendering Index requirements in Title 20.
  2. All other light sources shall provide a Color Rendering Index (CRI) of 90 or higher and color rendering R9 value of 50 or higher.
  3. All light sources shall be capable of providing a nominal Correlated Color Temperature (CCT) of 4000 Kelvin or less.
JA8.4.5 RESERVED
JA8.4.6 Dimming, Reduced Flicker Operation and Audible Noise

The light source shall meet the following dimming, reduced flicker operation, and audible noise requirements when measured in accordance with the test method of Section JA8.3.7:

  1. The light source shall be dimmable down to 10 percent light output where 100 percent full light output is defined as operating the light source at the maximum setting provided by the control.
  2. LED-based light sources designed to be connected with or dimmed by forward phase cut dimmers shall meet the requirements of NEMA standard SSL 7A.
  3. Light source in combination with specified control shall provide “reduced flicker operation” when tested at full light output as specified in JA10, where reduced flicker operation is defined as having percent amplitude modulation (percent flicker) less than 30 percent at frequencies less than 200Hz.
  4. Light source shall not emit audible noise above 24dBA measured at 1 meter from the light source when tested at full light output.
  5. Light sources shall also be tested and shown to comply with (c) and (d) while at 20% light output.
JA8.5 Marking

Light sources meeting the requirements of this Appendix shall be marked with “JA8-2025” to indicate their compliance with the criteria of this Appendix. Light sources that have passed the “time to failure ” portion of the federal test procedures specified in Appendix BB to Subpart B of 10 C.F.R. Part 430 (2018) with a rated life of 15,000 hours or greater and that the ambient temperature for the test is maintained at 45 °C ± 5°C tolerance or at a manufacturer-selected temperature higher than 45 °C with ± 5°C tolerance shall instead be marked with “JA8-2025-E” to indicate that they comply with this Appendix and may additionally be installed in elevated temperature applications such as enclosed fixtures. Light sources that do not comply with this Appendix shall not be marked with “JA8-2025” or “JA8-2025-E”.

JA8.6 Data Reporting

The following test data shall be submitted to the California Energy Commission in the format specified in Table JA-8. The entity submitting the filing shall keep all test data and documentation required for compliance for at least two years from the date of certification and shall provide copies of this documentation to the Energy Commission within 10 days of written request received from the Energy Commission.


TABLE JA-8. DATA TO BE RECORDED AND SUBMITTED TO THE CALIFORNIA ENERGY COMMISSION

Required Information

Permissible Answers

Compliance Threshold

Manufacturer, Model number, Description

NA

NA

Light Source Type

LED, OLED, HID, Other

NA

Product type

Omnidirectional lamp, Directional lamp, Decorative lamp, LED light engine, inseparable SSL luminaire, T20 lamp, other

NA

Lab accredited by NVLAP or accreditation body operating in accordance with ISO/IEC 17011

Yes/No

Yes

Initial Luminous Efficacy

Value (lumens/Watt)

≥ 45 lumens/Watt

Power Factor at Full Rated Power

0 – 1 Fraction

≥ 0.90

Start time

Value (seconds)

≤ 0.5 sec

Correlated Color Temperature (CCT)

Number Kelvin

≤4000 Kelvin.

Color Rendering Index (CRI)

0-100 

≥ 90 for all products other than T20 lamps, ≥ 82 for T20 lamps

Color Rendering R9 (red)

0-100 or below 0

≥ 50 for all products other than T20 lamps

Ambient or elevated temperature 

Ambient or Elevated

NA

Minimum dimming level

Value (percent)

≤ 10%

Dimming control compatibility

Forward Phase cut control, reverse phase cut, powerline carrier, digital, 0-10 VDC, other.

At least one type must be listed

NEMA SSL 7A compatible?

Yes/No, NA

If compatible with forward phase cut dimmer control, “Yes”. If not, “NA”.

Flicker: See JA10 Table 10-1 for flicker data requirements and permissible answers

NA

<30% for frequencies of 200 Hz or below, at 100% light output

<30% for frequencies of 200 Hz or below, at 20% light output

Audible Noise:

100% light output: Audible Noise

20% light output: Audible Noise

Value (dBA)

≤ 24 dBA

Marking: Marked in accordance with JA8.5

Yes/No

Yes

TABLE JA-8 DATA TO BE RECORDED AND SUBMITTED TO THE CALIFORNIA ENERGY COMMISSION
JA8.7 Start Time Test Method



JA8.7.1 Definitions

Device Under Test (DUT): the integrated LED lamp, LED light engine, or LED luminaire which is undergoing the start time test.

Start Time: the time between the application of power to the DUT and the point where the light source is continuously illuminated, and the light output is either constant or increasing. DUTs with integral controls (e.g., motion sensors, photosensors, wireless control, standby mode, or connected functionality) may have these controls disabled or bypassed for this testing.

Initial Plateau: the point at which the average increase in the light output over time levels out (reduces in slope). This can be determined mathematically or visually based on the output trace.


JA8.7.2 Methods Of Measurement and Reference Documents

IES LM-79.

JA8.7.3 Test Setup

A.    Test Setup and Instrumentation

 1.    Regulated AC or DC power supply (as applicable to the DUT)

 2.    Multichannel oscilloscope with data storage capability

 3.    Appropriate attenuator probes

 4.    Photodetector

   B.    Seasoning and Preburning: SSL sources shall not be seasoned.

   C.    Input Power for Start Time Measurements: The power requirements shall be per IES LM-79 as applicable. When selecting a power supply for use with integrated lamps and luminaires, it is necessary to apply an appropriate power factor when specifying the Volt-Amp capacity of the power supply.

   D.    Storage: Lamps and luminaires shall be stored at 25°C ± 5°C for a minimum of 16 hours prior to the test, after which the temperature range shall be 25°C ± 1°C for at least two hours immediately prior to the test.

   E.    Ambient Temperature: Testing shall take place in an ambient temperature of 25°C ± 1°C. Drafts shall be minimized.

   F.    Power Meter: Power meters shall be capable of measuring to the appropriate requirements of IES LM-79 as applicable.

  G.    Environmental Conditions: The test environment shall be clean and free from large amounts of dust and moisture.

   H.    Orientation: Test samples in orientation(s) as specified by the ENERGY STAR specification or manufacturer specified position if different. 

   I.    Sample Selection: Samples shall be representative of the manufacturer’s typical product. The samples shall be clean and thoroughly inspected before testing. Any flaws or inconsistencies in the DUT samples shall be noted.


JA8.7.4 Test Conduct

Photometric Measurements:

A.    For integrating sphere measurements, refer to IES-LM-79 as applicable.

B.    For non-integrating sphere measurements, the photodetector used for photometric measurements shall be a silicon detector corrected to closely fit the Commission Internationale de l’Eclairage (CIE) spectral luminous efficiency curve (Vil).


JA8.7.5 Test Procedure

A.    Install the DUT in the test environment. The driver may be external to the test environment, if applicable.

B.    For non-integrating sphere measurements, position the photocell so it sees the main body of the discharge tube or array (as applicable). Shield from extraneous light as needed.

C.    For integrating sphere measurements, see test conduct section JA8.7.4.

D.    When testing DUTs with sensors (e.g. motion sensors, photosensors) the sensors may be disabled or bypassed for this testing.

E.    Connect oscilloscope probe to measure the input voltage to the sample, and light output.

F.    Set the scope to trigger off the input voltage signal. Set trigger level at 10V.

G.    Set power supply to rated voltage and frequency of the DUT. If a range is specified, test sample at the midpoint of the range.

H.    Use an exemplar sample to determine the proper voltage and time base settings. Suggested initial time base is 200 ms/div.

I.    Apply rated voltage/frequency to the DUT.

J.    Record the input voltage and light output waveform on which the starting time was based.

K.    Record Start Time.


JA8.8 Noise Test Method
JA8.8.1 Definitions

Unit Under Test: The unit under test (UUT) refers the specific lamp sample being tested.

Baseline Light Output: The baseline light output (BLO) refers to the stabilized light output of the unit under test (UUT) is operating without a dimmer in the circuit.

Maximum Control Position: The setting on the dimmer or control device intended to achieve the maximum light output during operation.

Maximum Light Output: The maximum light output (MaxLO) refers to the light output of the UUT when operating with a dimmer in the circuit at the Maximum Control Position.

Minimum Dimming Level Claimed: The minimum light output level of a UUT when operated with a dimmer in the circuit, as declared by the lamp manufacturer. Typically expressed as a percentage.

Minimum Light Output: The minimum light output (MinLO) refers to the minimum light output when the UUT is operating with a dimmer in the circuit.

Peak Noise: The highest time-averaged sound value recorded at a measurement point during stable operation of the UUT.


JA8.8.2 Methods Of Measurement and Reference Documents

A.    IES LM-79.

B.    ISO 7574-4 B.2.1: 1985. Statistical methods for determining and verifying stated noise emission values of machinery and equipment, International Organization for Standardization, Geneva, Swizerland.

C.    ASA S12.55-2006/ISO3745:2003: 2006. Acoustical Society of America, New York.


JA8.8.3 Recommended Practice Test Setup

A.    Test Setup and Instrumentation: The test can be performed using a single microphone and rotating the product, or by using multiple microphones. Equipment required for measurement is as follows:

  1.    Regulated AC or DC power supply (as applicable to the UUT or transformer).

  2.    Multichannel oscilloscope with data storage capability or similar equipment for comparing output readings from a photodetector.

  3.    Appropriate attenuator probe(s), if applicable.

  4.    Photodetector capable of measuring relative light output.

  5.    Noise level measurement equipment.

  6.    Microphone(s).

  7.    Isolated sound chamber (e.g., anechoic chamber).

B.    Lamp Seasoning and Preburning: LED lamps shall not be seasoned. 

C.    Input Power for Measurements: The power requirements shall be per IES LM-79 as applicable. Note: When selecting a power supply, it is necessary to apply an appropriate power factor when specifying the Volt-Amp rating of the power supply.

D.    Ambient Temperature: testing of the UUT shall take place in an ambient temperature of 25°C ± 5°C. Drafts shall be minimized.

E.    Power Meter: Power meters shall be capable of measuring to the appropriate requirements of IES LM-79 as applicable.

F.    Environmental Conditions: The test environment shall be clean and free from large amounts of dust and moisture.

G.    Sample Selection: Samples shall be representative of the manufacturer’s typical product. The samples shall be clean and thoroughly inspected before testing. Any flaws or inconsistencies in the samples shall be noted. The samples used for noise testing shall be the same sample(s) used for testing for meeting Joint Appendix JA10, if applicable, and can be the same sample(s) used for other testing.


JA8.8.4 Test Conduct - Guidance for Noise Test Procedure

A.    Photometric Measurements:

  1.    For absolute measurements, refer to IES LM-79 as applicable with the exception of the guidance for stabilization.

  2.    The photodetector used for photometric measurements shall be a silicon detector corrected to closely fit the Commission Internationale de l’Eclairage (CIE) spectral luminous efficiency curve (Vil).

Ensure that the measurement equipment receives the appropriate voltage range from the photodetector, using an amplifier if necessary.

B.    Measurement Equipment:

  1.    The sound chamber shall provide an environment suitable for the sound testing of the UUT. External sources of noise shall be minimized.

  2.    The sound measurement equipment shall be capable of measuring A-weighted decibels.

  3.    The microphone(s) shall be placed at a distance of one (1) meter or less from the UUT to be measured.

    i)    If multiple microphones are used, 6 microphones shall be placed about the UUT spaced 90° apart and aimed at the UUT.

    ii)    If a single microphone is used, the microphone shall be aimed at the UUT and the UUT holding device shall be capable of moving and holding the UUT so that six measurements about the UUT can be made 90° apart.

  4.    The sound level of the UUT shall be calculated from the measurement taken.

   i)    The baseline level may be corrected for in accordance with ISO 7574-4:1985, B.2.1.

 

   ii)    ANSI standard S12.55-2006/ISO3745:2003 may be used as a reference document for other aspects of the measurements (calibration, etc.).

C.    Reserved

D.    Low Voltage UUTs

  1.    UUTs designed for operation on low voltage transformers shall be operated on a compatible transformer specified or supplied by the lamp manufacturer.

  2.    Electrical measurements shall include characteristics of the UUT.

E.    Measurements:

  1.    The following data shall be collected at each measurement point:

    i)    Light output.

    ii)    Peak Noise Reading.

    iii)    Microphone Position at which the Peak Noise Reading occurs (e.g., 0 degrees / opposite lamp base).


JA8.8.5 Test Procedure for Products Claiming Dimmability
JA8.8.5.1 General Test Procedures for Noise at Baseline output:

A.    Install the UUT in the test environment without a dimmer in the circuit.

B.    Set power supply to rated voltage and frequency of the device. If a range is specified, test sample at the midpoint of the range.

C.    Record noise readings from measurement equipment to determine sound level in dBA. This is the control noise level.

D.    Apply rated voltage/frequency to the device.

E.    Allow UUT to stabilize per IES LM-79 as applicable. If lamp has been stabilized for measurements previously and the stabilization time recorded, the lamp may be considered stabilized after operating for this period of time.

F.    Record noise readings as specified in Section 8.8.4.E from measurement equipment about the UUT to determine the peak sound level in dBA. This is the noise at the Baseline Light Output (BLO).

G.    If using a single microphone, note the position with the highest sound level (if applicable).

H.    Remove power from UUT.


JA8.8.5.2 General Test Procedures for Noise on a Dimmer

A.    Install dimmer into the UUT test circuit. The dimmer shall be located outside of the sound chamber.

B.    Apply rated voltage/frequency to the dimmer or control device.

C.    Adjust dimmer to the maximum control position. 

D.    Allow UUT to stabilize and verify by taking light output measurements every minute until consecutive measurements are no more than 0.5% apart, utilizing previously recorded UUT stabilization time or verify by mathematical means that the lamp is stabilized.

E.    Record noise readings as specified in Section 8.8.4.E from measurement equipment about the UUT to determine the peak sound level in dBA. This is the noise at the MaxLO.

F.    Adjust dimmer so that the light output is the lower of:

  1.    20% of the MaxLO ± 5%; or

  2.    The minimum dimming level claimed as a percentage of the MaxLO ± 5%.

G.    Allow UUT to stabilize and verify by taking light output measurements every minute until consecutive measurements are no more than 0.5% apart, utilizing previously recorded UUT stabilization time or verify by mathematical means that the lamp is stabilized.

H.    Verify that the UUT light output is still within the range in F).

  1.    If not, repeat step A) and G).

  2.    If light output is within range, record noise readings as specified in Section 8.8.4.E from measurement equipment about the UUT to determine the peak sound level in dBA. This is the noise at MinLO.

I.    Repeat step A thru H as specified in JA8.8.5.2 for each dimmer to be tested. A test setup that includes a device that allows hot switching between dimmers may be utilized to bypass stabilization time.