Multifamily buildings shall comply with the applicable requirements of Sections 160.6(a) through 160.6(e).
Exception to Section 160.6(a): Service or feeder for which the utility company provides a metering system for the multifamily building that indicates instantaneous kW demand and kWh for a utility-defined period.
Metering Functionality | Electrical Services1 rated 50 kVA or less | Electrical Services1 rated more than 50kVA and less than or equal to 250 kVA | Electrical Services1 rated more than 250 kVA and less than or equal to 1000kVA | Electrical Services1 rated more than 1000kVA |
Instantaneous (at the time) kW demand | Required | Required | Required | Required |
Historical peak demand (kW) | Not required | Not required | Required | Required |
Tracking kWh for a user-definable period. | Required | Required | Required | Required |
kWh per rate period | Not required | Not required | Not required | Required |
1 “Electrical Services” applies to the building service-entrance rating or to the submetering service. For a building with submetering, this applies to the submetering service size to the common use areas.
Exception 1 to Section 160.6(b): For each separate load type, up to 10 percent of the connected load may be of any type.
Exception 2 to Section 160.6(b): Submetered electrical power distribution systems that provide power to dwelling units.
|
Electrical Load Type
|
Electrical Services1 rated 50 kVA or less
|
Electrical Services1 rated more than 50kVA and less than or equal to 250 kVA
|
Electrical Services1 rated more than 250 kVA and less than or equal to 1000kVA
|
Electrical Services1 rated more than 1000kVA
|
|
Lighting including exit and egress lighting and exterior lighting
|
Not required
|
All lighting in aggregate
|
All lighting disaggregated by floor, type or area
|
All lighting disaggregated by floor, type or area
|
|
HVAC systems and components including chillers, fans, heaters, furnaces, package units, cooling towers, and circulation pumps associated with HVAC
|
Not required
|
All HVAC in aggregate
|
All HVAC in aggregate and each HVAC load rated at least 50 kVA
|
All HVAC in aggregate and each HVAC load rated at least 50kVA
|
|
Domestic and service water system pumps and related systems and components
|
Not required
|
All loads in aggregate
|
All loads in aggregate
|
All loads in aggregate
|
|
Plug load including appliances rated less than 25 kVA
|
Not required
|
All plug load in aggregate Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf
|
All plug load separated by floor, type or area Groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf
|
All plug load separated by floor, type or area All groups of plug loads exceeding 25 kVA connected load in an area less than 5000 sf
|
|
Elevators, escalators, moving walks, and transit systems
|
Not required
|
All loads in aggregate
|
All loads in aggregate
|
All loads in aggregate
|
|
Renewable power source (net or total)
|
Each group
|
Each group
|
Each group
|
Each group
|
|
Loads associated with renewable power source
|
Not required
|
All loads in aggregate
|
All loads in aggregate
|
All loads in aggregate
|
|
Charging stations for electric vehicles
|
All loads in aggregate
|
All loads in aggregate
|
All loads in aggregate
|
All loads in aggregate
|
Exception to Section 160.6(c): Voltage drop permitted by California Electrical Code Sections 647.4, 695.6 and 695.7.
Exception 1 to Section 160.6(d): Receptacles that are only for the following purposes:
- Receptacles specifically for refrigerators and water dispensers in kitchen areas.
- Receptacles located a minimum of six feet above the floor that are specifically for clocks.
- Receptacles for network copiers, fax machines, A/V and data equipment other than personal computers in copy rooms.
- Receptacles on circuits rated more than 20 amperes.
- Receptacles connected to an uninterruptible power supply (UPS) that are intended to be in continuous use, 24 hours per day/365 days per year, and are marked to differentiate them from other uncontrolled receptacles or circuits.
Exception 2 to Section 160.6(d): Receptacles in common use areas providing shared provisions for living, eating, cooking, or sanitation to dwelling units that would otherwise lack these provisions.
Note: Definitions of terms and phrases in Section 160.6 are determined as specified in Section 100.1(b). Terms and phrases not found in Section 100.1(b) shall be defined as specified in Title 24, Part 3, Article 100 of the California Electrical Code.