Single-family residential buildings shall comply with the applicable requirements of Sections 150(a) through 150.0(v).
NOTE: The requirements of Sections 150.0(a) through 150.0(v) apply to newly constructed buildings. Sections 150.2(a) and 150.2(b) specify which requirements of Sections 150.0(a) through 150.0(v) also apply to additions or alterations
Exception to Section 150.0(a)1:
iii. The space-conditioning system is a ductless system.
Exception 2 to Section 150.0(a)1: Space-conditioning duct systems buried within insulation in an attic that complies using Section 150.1(b) and is verified according to RA 3.1.4.1.
Exception to Section 150.0(c)1: Existing walls already insulated to a U-factor not exceeding U-0.110 or already insulated between framing members with insulation having an installed thermal resistance of R-11 or greater.
Exception to Section 150.0(e)2: An outside combustion-air intake is not required if the fireplace will be installed over concrete slab flooring and the fireplace will not be located on an exterior wall.
Exception to Section 150.0(e)3: When a gas log, log lighter, or decorative gas appliance is installed in a fireplace, the flue damper shall be blocked open if required by the CMC or the manufacturer's installation instructions.
Exception 1 to Section 150.0(h)1: Block loads (the total load for all rooms combined are served by the central equipment,) may be used for the purpose of system sizing for additions.
- Equipment sizing and selection shall meet the cooling and heating loads of Section 150.0(h)1 and 2.
- Systems shall be sized based on ACCA Manual S-2023 in accordance with these requirements:
- Cooling Capacity: There is no limit on the minimum capacity.
- Furnaces: Heating capacity shall be sized based on ACCA Manual S-2023, Table N2.5.
- Heat Pump Heating Capacity:
- Minimum: Heating systems are required to have a heating capacity meeting the minimum requirements of the CBC not including any supplementary heating.
- Maximum: There is no limit on the maximum heating capacity.
- If a heat pump is equipped with an installer adjustable defrost delay timer, the delay timer shall be set to greater than or equal to 90 minutes.
- The installer shall certify on the Certificate of Installation (CF2R) that the control configuration has been tested in accordance with the testing procedure in the CF2R.
Exception 1 to Section 150.0(h)6. Dwelling units in Climate Zones 6 and 7.
Exception 2 to Section 150.0(h)6. Dwelling units with a conditioned floor area of 500 square feet or less in Climate Zones 3, 5 through 10, and 15.
Exception 1 to Section 150.0(h)7: For buildings with a conditioned floor area less than 500 square feet, and for buildings of any size in climate zones 7 and 15, heat pumps with supplementary heaters shall have controls that meet i or ii.
i. Option A:
1. That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and
2. In which the cut-on temperature for heat pump heating is higher than the cut- on temperature for supplementary heating, and the cut-off temperature for heat pump heating is higher than the cut-off temperature for supplementary heating.
ii. Option B: The controls may allow supplementary heater operation during defrost mode and transient periods, such as specified in Section 110.2(c).start-ups and following a room thermostat setpoint advance, if the controls prevent the unnecessary operation of supplementary heating.
Exception 2 to Section 150.0(h)7: Room air-conditioner heat pumps.
9. Capacity variation with third-party thermostats. Variable or multi-speed systems shall comply with the following requirements:
- The space conditioning system and thermostat together shall be capable of responding to heating and cooling loads by modulating system compressor speed, and meet thermostat requirements in section 150.0(i)2.
- The installer shall certify on the Certificate of Installation that the control configuration has been tested in accordance with the testing procedure found in the CF2R.
2. Thermostats that are Applied to Heat Pumps with Supplemental Heating. Thermostats that are applied to heat pumps with supplemental heating. In addition to the requirements in Section 150.0(i)1, thermostats controlling heat pumps with electric resistance supplementary heat or gas furnace supplementary heat shall comply with the following requirements:
- The thermostat shall receive outdoor air temperature from an outdoor air temperature sensor or from an internet weather service.
- The thermostat shall display the outdoor air temperature.
- As described in 150.0(h)7, the thermostat and heat pump shall lock out supplementary heat when the outdoor air temperature is above 35°F.
- The thermostat shall have an indicator to notify when supplementary heat or emergency heat is in use.
- During defrost or when the user selects emergency heating, supplementary heat operation is permitted above 35°F.
- The installer shall certify on the Certificate of Installation that the system has been tested in accordance with the testing procedure found in the CF2R.
Exception to Section 150.0(i)2A, B, and C: Where supplementary heat is locked out above 35°F by another control device in accordance with Section 150.0(h)7.
Exception 1 to Section 150.0(i)2: Systems compliant with Exception 1 to Section 150.0(h)7.
Exception 2 to Section 150.0(i)2: Room air-conditioner heat pumps.
Exception 1 to Section 150.0(k)1A: Integrated device lighting. Lighting integral to exhaust fans, kitchen range hoods, bath vanity mirrors, garage door openers, and ceiling fan kits that are subject to DOE's Appliance and Equipment Standards Program.
Exception 2 to Section 150.0(k)1A: Navigation lighting rated less than five watts such as night lights, step lights, and path lights.
Exception 3 to Section 150.0(k)1A: Lighting with an efficacy of 45 lumens per watt or greater and located internal to drawers, cabinetry, and linen closets.
Exception 4 to Section 150.0(k)1A: Light sources as follows:
i. LED light sources installed outdoors;
ii. inseparable solid state lighting (SSL) luminaires containing colored light sources that are installed to provide decorative lighting;
iii. High intensity discharge (HID) light sources including pulse start metal halide and high pressure sodium light sources; and
iv. Luminaires with hardwired high frequency generator and induction lamp.
Exception to Sections 150.0(k)1Cii and iii: Recessed luminaires marked for use in fire-rated installations extruded into ceiling space and recessed luminaires installed in noninsulated ceilings.
A. Lighting shall have readily accessible wall-mounted controls that allow the lighting to be manually turned ON and OFF.
Exception to Section 150.0(k)2A: Ceiling fans may provide control of integrated lighting via a remote control.
Exception 1 to Section 150.0(k)2F: Ceiling fans may provide control of integrated lighting via a remote control. Lighting integral to kitchen range hoods and bathroom exhaust fans.
Exception 2 to Section 150.0(k)2F: Luminaires connected to a circuit with controlled lighting power less than 20 watts or controlled by an occupancy or vacancy sensor providing automatic-off functionality.
Exception 3 to Section 150.0(k)2F: Navigation lighting rated less than five watts, such as night lights, step lights, and path lights. Lighting controlled by automatic-off controls and located internal to drawers, cabinetry with opaque fronts, or cabinetry with doors.
a. a photocell and a motion sensor; or
b. a photocell and an automatic time switch control; or
c. Controlled by an astronomical time clock control.
B. Controls that override to ON shall not be allowed unless the override automatically returns the automatic control to its normal operation within 6 hours.
C. An energy management control system (EMCS) or other controls that provides the specified lighting control functionality and complies with all requirements applicable to the specified controls may be used to meet these requirements.
5. Residential garages for eight or more vehicles.
Exception to Section 150.0(m)1Bi: Portions of the duct system located in conditioned space below the ceiling separating the occupiable space from the attic are not required to be insulated if all of the following conditions are met:
- The non-insulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection.
- At all locations where non-insulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC Sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC Section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection.
Exception 2 to Section 150.0(m)1Bi: Ducts located in an unvented attic shall have a minimum insulation value of R-4.2, verified by visual inspection when:
a. The attic has at least R-30 insulation between the roof rafters in contact with the roof deck,
b. The gable ends meet the wall insulation requirements of Section 150.1(c)1B, and
c. The dwelling unit achieves a whole building leakage rate of 3.0 ACH50 or less, as confirmed by field verification and diagnostic testing in accordance with Reference Residential Appendix RA3.8.
ii. Ducts do not require insulation when the duct system is located entirely within conditioned space as confirmed through field verification and diagnostic testing in accordance with the requirements of Reference Residential Appendix RA3.1.4.3.8. For dwelling units with attics, the duct system shall be located below the ceiling separating the occupiable space from the attic.
Exception 1 to Section 150.0(m)12Bi: For heat recovery ventilators and energy recovery ventilators the location of the filters required by Section 150.0(m)12 may be downstream of a system thermal conditioning component, provided the system is equipped with ancillary filtration upstream of the system’s thermal conditioning component.
Systems specified in Section 150.0(m)12Ai shall be equipped with air filters that meet either Subsection a or b below.
Aface = Qfilter / Vface
where
Aface = air filter face area, the product of air filter nominal length × nominal width, ft2
Qfilter = design airflow rate for the air filter, ft3/min
Vface = air filter face velocity ≤150 ft/min
Exception to 150.0(m)13A: Systems that cannot conform to the specifications for hole location in Reference Residential Appendix Figure RA3.3-1 shall not be required to provide holes as described in Figure RA3.3-1.
Single-family dwellings shall have mechanical ventilation as specified in Subsections i, and iv. Single- family detached dwelling units, and attached dwelling units not sharing ceilings or floors with other dwelling units, occupiable spaces, public garages, or commercial spaces may reduce their required mechanical ventilation rates in accordance with subsections ii, and iii. Vertically attached dwelling units shall not reduce their minimum ventilation rates in accordance with subsections ii and iii below.
Qtot = 0.03Afloor + 7.5(Nbr + 1)
where
Qtot = total required ventilation rate, cfm
Afloor = dwelling-unit floor area, ft2
Nbr = number of bedrooms (not to be less than 1)
Q50 = Vdu × 2 ACH50 / 60 min
where
Q50 = leakage rate at 50 Pa
Vdu = dwelling unit conditioned volume, ft3
ACH50 = air changes per hour at 50 Pa (0.2 inch water)
Q50 = Vdu × Verified ACH50 / 60 min
where
Q50 = leakage rate at 50 Pa
Vdu = dwelling unit conditioned volume, ft3
ACH50 = air changes per hour at 50 Pa (0.2 inch water)
Qinf = 0.052 × Q50 × wsf × [H/Hr]z
where
Qinf = effective annual infiltration rate, cfm (L/s)
Q50 = leakage rate at 50 Pa from equation 150.0-C, or equation 150.0-D
wsf = weather and shielding factor from Table 150.0-D
H = vertical distance between the lowest and highest above-grade points within the pressure boundary, ft (m)
Hr = reference height, 8.2 ft (2.5 m)
z = 0.4 for the purpose of calculating the Effective Annual Average Infiltration Rate
The Required Mechanical Ventilation Rate (Qfan) shall be calculated using Equation 150.0-F
Qfan = Qtot – ΦF (Qinf × Aext)
where
Qfan = required mechanical ventilation rate, cfm (L/s)
Qtot = total required ventilation rate, cfm (L/s) from Equation 150.0-B
Qinf = effective annual average infiltration rate, cfm (L/s) from Equation 150.0-E
Aext = 1 for single-family detached homes, or the ratio of exterior envelope surface area that is not attached to garages or other dwelling units to total envelope surface area for attached dwelling units not sharing ceilings or floors with other dwelling units, occupiable spaces, public garages, or commercial spaces.ΦF = 1 for balanced ventilation systems and Qinf/Qtot otherwise
iv. Requirements for balanced and supply only ventilation systems.
a. IAQ filter and HRV/ERV accessibility. System air filters and HRV/ERV heat/energy recovery cores shall be located such that they are accessible for service from within occupiable spaces, basements, garages, balconies, and mechanical closets. Filters and heat/energy cores behind access panels, access doors, or grilles located no more than 10 feet above a walking surface inside a space specified above comply with this requirement.
Exception to Section 150.0(o)1Civa: Systems that require servicing from inside the attic shall have the following:
1. A Fault Indicator Display (FID) meeting the requirements of Reference Appendix JA17; and
2. An attic access door located in a wall or, where attic access is provided through a ceiling, an attic access hatch that includes an integrated ladder; and
3. A walkway from the attic access door to the HRV/ERV.
b. IAQ System component accessibility: Fans, motors, heat exchangers, filters and recovery cores shall meet all applicable requirements of California Mechanical Code Section 304.0 accessibility for service.
c. Outdoor air intake design: Outdoor air intakes shall comply with California Mechanical Code Section 402.4.1.
d. Outdoor air intake location and accessibility: To provide access for cleaning, outdoor air intakes shall be accessible. Air intakes located not more than 10 feet above a walking surface comply with this requirement. If located on roofs, they shall meet the requirements of California Mechanical Code Section 304.3.1.
Exception to Section 150.0(o)1Civd: Outdoor air intake serving equipment with an FID meeting requirements of Reference Appendix JA 17.
- A readily accessible occupant-controlled ON-OFF control.
- An automatic control that does not impede occupant ON control.
When using Table 150.0-H for demonstrating compliance, the airflow rating shall be greater than or equal to the value required by Section 150.0(o)1G at a static pressure greater than or equal to 0.25 in. of water (62.5 Pa). When a vented range hood utilizes a capture efficiency rating to demonstrate compliance with Section 150.0(o)1Giiib, a static pressure greater than or equal to 0.25 in. of water at the rating point shall not be required, and the airflow listed in the approved directory corresponding to the compliant capture efficiency rating point shall be applied to Table 150.0-H for determining compliance.
Use of Table 150.0-H is limited to ventilation systems that conform to all of the following three specifications:
- Total duct length is less than or equal to 25 ft (8 m),
- Duct system has no more than three (3) elbows, and
- Duct system has exterior termination fitting with a hydraulic diameter greater than or equal to the minimum duct diameter and not less than the hydraulic diameter of the fan outlet.
Exception to Section 150.0(o)1Gvi: Kitchen range hoods may be rated for sound at no less than 100 cfm at a static pressure determined at working speed as specified in HVI 916 section 7.2.
H = C × F2
where:
H is the total system head in feet of water.
F is the flow rate in gallons per minute (gpm).
C is a coefficient based on the volume of the pool:
0.0167 for pools less than or equal to 17,000 gallons.
0.0082 for pools greater than 17,000 gallons.
E. For dedicated-purpose pool pumps with more than one speed, the controls shall default to the filtration flow rate setting within 24 hours and shall have an override capability for servicing.
Exception to Section 150.0(s): Buildings which have a BESS installed.
Systems using gas or propane cooktop to serve individual dwelling units shall include the following:Return duct length shall not exceed 30 feet and shall contain no more than 180° of bend. If the total bending exceeds 90°, one bend shall be a metal elbow. Return grille devices shall be labeled in accordance with the requirements in Section 150.0(m)12Biv to disclose the grille's design airflow rate and a maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in accordance with AHRI Standard 680 for the design airflow rate for the return grille. | ||
SYSTEM NOMINAL COOLING CAPACITY (Ton)* | RETURN DUCT MINIMUM NOMINAL DIAMETER (inch) | MINIMUM TOTAL RETURN FILTER GRILLE NOMINAL AREA (square inches) |
1.5 | 16 | 500 |
2.0 | 18 | 600 |
2.5 | 20 | 800 |
* Not applicable to systems with nominal cooling capacity greater than 2.5 tons or less than 1.5 ton |
Each return duct length shall not exceed 30 feet and shall contain no more than 180° of bend. If the total bending exceeds 90°, one bend shall be a metal elbow. Return grille devices shall be labeled in accordance with the requirements in Section 150.0(m)12Biv to disclose the grille's design airflow rate and a maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in accordance with AHRI Standard 680 for the design airflow rate for the return grille. | |||
System Nominal Cooling Capacity (Ton)* | Return Duct 1 Minimum Nominal Diameter (inch) | Return Duct 2 Minimum Nominal Diameter (inch) | Minimum Total Return Filter Grille Nominal Area (square inch) |
1.5 | 12 | 10 | 500 |
2.0 | 14 | 12 | 600 |
2.5 | 14 | 14 | 800 |
3.0 | 16 | 14 | 900 |
3.5 | 16 | 16 | 1000 |
4.0 | 18 | 18 | 1200 |
5.0 | 20 | 20 | 1500 |
* Not applicable to systems with nominal cooling capacity greater than 5.0 tons or less than 1.5 tons. |
TMY3 | Wrf | Weather Station | Latitude | Longitude | State |
690150 | 0.50 | Twentynine Palms | 34.30 | -116.17 | California |
722860 | 0.43 | March AFB | 33.90 | -117.25 | California |
722868 | 0.45 | Palm Springs Intl | 33.83 | -116.50 | California |
722869 | 0.42 | Riverside Muni | 33.95 | -117.45 | California |
722880 | 0.39 | Burbank-Glendale-Pasadena | 34.20 | -118.35 | California |
722885 | 0.39 | Santa Monica Muni | 34.02 | -118.45 | California |
722886 | 0.39 | Van Nuys Airport | 34.22 | -118.48 | California |
722895 | 0.55 | Lompoc (AWOS) | 34.67 | -120.47 | California |
722897 | 0.51 | San Luis Co Rgnl | 35.23 | -120.63 | California |
722899 | 0.45 | Chino Airport | 33.97 | -117.63 | California |
722900 | 0.38 | San Diego Lindbergh Field | 32.73 | -117.17 | California |
722903 | 0.39 | San Diego/Montgomery | 32.82 | -117.13 | California |
722904 | 0.40 | Chula Vista Brown Field NAAS | 32.58 | -116.98 | California |
722906 | 0.39 | San Diego North Island NAS | 32.70 | -117.20 | California |
(CONTINUED) TABLE 150.0-D: Infiltration Effectiveness Weather and Shielding Factors [ASHRAE 62.2:Table B1]
TMT3 | Wuf | Weather Station | Latitude | Longitude | State |
723920 | 0.40 | Oakland/Metropolitan/OAS | 37.72 | -122.22 | California |
722927 | 0.38 | Carlsbad/Palomar | 33.13 | -117.28 | California |
722900 | 0.35 | San Diego Miramar NAS | 32.87 | -117.13 | California |
722950 | 0.42 | Long Beach Daugherty | 33.82 | -118.35 | California |
722956 | 0.38 | Jack Northrop Fld H | 33.92 | -118.33 | California |
722970 | 0.38 | Long Beach Daugherty Fld | 33.83 | -118.17 | California |
722976 | 0.34 | Fullerton Municipal | 33.87 | -117.98 | California |
722977 | 0.36 | Santa Ana John Wayne AP | 33.68 | -117.87 | California |
723805 | 0.51 | Needles Airport | 34.77 | -114.62 | California |
723810 | 0.59 | Edwards AFB | 34.90 | -117.87 | California |
723815 | 0.58 | Daggett Barstow-Daggett AP | 34.85 | -116.80 | California |
723816 | 0.62 | Lancaster Gen Wm Fox Field | 34.73 | -118.22 | California |
723820 | 0.57 | Palmdale Airport | 34.63 | -118.08 | California |
723830 | 0.68 | Sandberg | 34.75 | -118.72 | California |
723840 | 0.43 | Bakersfield Meadows Field | 35.43 | -119.05 | California |
723890 | 0.45 | Fresno Yosemite Intl AP | 36.78 | -119.72 | California |
723895 | 0.42 | Porterville (AWS) | 36.03 | -119.07 | California |
723896 | 0.43 | Visalia Muni (AWS) | 36.32 | -119.40 | California |
723910 | 0.45 | Point Mugu NF | 34.12 | -119.12 | California |
723925 | 0.44 | Santa Barbara Municipal AP | 34.43 | -119.85 | California |
723926 | 0.43 | Camarillo (AWS) | 34.22 | -119.08 | California |
723927 | 0.45 | Oxnard Airport | 34.20 | -119.20 | California |
723940 | 0.52 | Santa Maria Public Arpt | 34.92 | -120.47 | California |
723965 | 0.53 | Paso Robles Municipal Arpt | 35.67 | -120.63 | California |
724800 | 0.55 | Bishop Airport | 37.37 | -118.35 | California |
724815 | 0.46 | Merced Castle Arb Fld | 37.28 | -120.52 | California |
724830 | 0.51 | Sacramento Executive Arpt | 38.50 | -121.50 | California |
724837 | 0.45 | Beale AFB | 39.13 | -121.43 | California |
724838 | 0.50 | Yuba Co | 39.10 | -121.57 | California |
724839 | 0.51 | Sacramento Metropolitan AP | 38.70 | -121.58 | California |
724915 | 0.49 | Monterey Naf | 36.60 | -121.87 | California |
724917 | 0.54 | Salinas Municipal AP | 36.67 | -121.60 | California |
724920 | 0.50 | Stockton Metropolitan Arpt | 37.90 | -121.23 | California |
724926 | 0.47 | Modesto City—County AP | 37.63 | -120.95 | California |
724927 | 0.53 | Livermore Municipal | 37.70 | -121.82 | California |
724930 | 0.54 | Oakland Metropolitan Arpt | 37.72 | -122.22 | California |
724935 | 0.47 | Hayward Air Term | 37.67 | -122.12 | California |
724936 | 0.53 | Concord—Buchanan Field | 38.00 | -122.05 | California |
724940 | 0.60 | San Francisco Intl AP | 37.62 | -122.40 | California |
(CONTINUED) TABLE 150.0-D: Infiltration Effectiveness Weather and Shielding Factors [ASHRAE 62.2:Table B1]
TMY3 | Wef | Weather Station | Latitude | Longitude | State |
724945 | 0.43 | San Jose Int'l AP | 37.37 | -121.93 | California |
724955 | 0.55 | Napa Co Airport | 38.22 | -122.28 | California |
724957 | 0.43 | Santa Rosa (AWOS) | 38.52 | -122.82 | California |
724926 | 0.51 | Blue Canyon AP | 39.30 | -120.72 | California |
725846 | 0.66 | Truckee-Tahoe | 39.32 | -120.13 | California |
725847 | 0.63 | South Lake Tahoe | 38.90 | -120.00 | California |
725905 | 0.47 | Ukiah Municipal AP | 39.13 | -123.20 | California |
725910 | 0.50 | Red Bluff Municipal AP | 40.15 | -122.25 | California |
725920 | 0.47 | Redding Municipal Arpt | 40.52 | -122.32 | California |
725945 | 0.56 | Arcata Airport | 40.98 | -124.10 | California |
725946 | 0.60 | Crescent City FAAPA | 41.78 | -124.23 | California |
725955 | 0.51 | Montague Siskiyou County AP | 41.78 | -122.47 | California |
725958 | 0.59 | Alturas | 41.50 | -120.53 | California |
745090 | 0.45 | Mountain View Moffett FLD NAS | 37.40 | -122.05 | California |
746160 | 0.60 | China Lake NAF | 38.27 | -121.93 | California |
746120 | 0.52 | China Lake NAF | 35.68 | -117.68 | California |
747040 | 0.47 | Lemoore Reeves NAS | 36.33 | -119.95 | California |
747185 | 0.46 | Imperial | 32.83 | -115.58 | California |
747187 | 0.44 | Palm Springs Thermal AP | 33.63 | -116.17 | California |
747188 | 0.48 | Blythe Riverside Co Arpt | 33.62 | 114.72 | California |
Application |
Compliance Criteria |
Enclosed Kitchen or Nonenclosed Kitchen |
Vented range hood, including appliance-range hood combinations shall meet either the capture efficiency (CE) or the airflow rate specified in Table 150.0-G as applicable. |
Enclosed Kitchen or Nonenclosed Kitchen |
Other kitchen exhaust fans, including downdraft: 300 cfm (150 L/s) |
Bathroom |
50 cfm (25 L/s) |
Application | Airflow |
Enclosed kitchen | 5 ach, based on kitchen volume |
Bathroom | 20 cfm (10 L/s) |
Dwelling Unit Floor Area (ft2) | Hood Over Electric Range | Hood Over Natural Gas Range |
>1500 | 50% CE or 110 cfm | 70% CE or 180 cfm |
>1000 - 1500 | 50% CE or 110 cfm | 80% CE or 250 cfm |
750 - 1000 | 55% CE or 130 cfm | 85% CE or 280 cfm |
<750 | 65% CE or 160 cfm | 85% CE or 280 cfm |
Table 150.0-H Prescriptive Ventilation System Duct Sizing [ASHRAE 62.2:Table 5-3]
Fan Airflow Rating, cfm at minimum static pressuref, 0.25 in. water (L/s at minimum 62.5 Pa) | Minimum Duct Diameter for Rigid Duct, in.(mm) a,b | Minimum Duct Diameter for Flex Ductc, in. (mm)a,b |
≤50 (25) | 4e (100) | 4 (100) |
≤80 (40) | 5 (125) | 5 (125) |
≤100 (50) | 5 (125) | 6 (150) |
≤125 (60) | 6 (150) | 6 (150) |
≤150 (70) | 6 (150) | 7 (150) |
≤175 (85) | 7 (180) | 7 (180) |
≤200 (95) | 7 (180) | 8 (205) |
≤250 (120) | 8 (205) | 8 (205) |
≤350 (165) | 9 (230) | 9 (230) |
≤400 (190) | 10 (255) | 10 (255) |
≤450 (210) | 10 (255) | NP |
≤700 (330) | 12 (305) | NP |
≤800 (380) | 12d (305) | NP |
Footnotes for Table 150.0-H: a. For noncircular ducts, calculate the diameter as four times the cross-sectional area divided by the perimeter. b. NP = application of the prescriptive table is not permitted for this scenario. c. Use of this table for verification of flex duct systems requires flex duct to be fully extended and any flex duct elbows to have a minimum bend radius to duct diameter ratio of 1.0. d. For this scenario, use of elbows is not permitted. e. For this scenario, 4 in. (100 mm) oval duct shall be permitted, provided the minor axis of the oval is greater than or equal to 3 in. (75 mm) f. When a vented range hood utilizes a capture efficiency rating to demonstrate compliance with 150.0(o)1Giiib, a static pressure greater than or equal to 0.25 in. of water at the rating point shall not be required, and the airflow listed in the approved directory corresponding to the compliant capture efficiency rating point shall be applied to Table 150.0-H for determining compliance. |
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.