Welcome to the New & Improved Reference Ace Beta!

JA4.3 Walls

JA4.3.1 – U-factors of Wood Framed Walls with 1/2-inch Gypsum Board

Spacing
Cavity Insulation
Nominal Framing Size
Rated R-value of Continuous Insulation 2
R-0
R-2
R-4
R-5
R-6
R-7
R-8
R-10
R-12
R-15
A
B
C
D
E
F
G
H
I
J
16 in. OC
None
Any
1
0.356
0.209
0.146
0.127
0.113
0.101
0.092
0.078
0.067
0.056
R-11
2x4
2
0.110
0.088
0.074
0.068
0.064
0.060
0.056
0.050
0.045
0.040
R-13
2x4
3
0.102
0.082
0.069
0.064
0.060
0.056
0.053
0.047
0.043
0.038
R-15 1
2x4
4
0.095
0.077
0.065
0.060
0.056
0.053
0.050
0.045
0.041
0.036
R-19
2x6
5
0.074
0.063
0.055
0.051
0.049
0.046
0.044
0.040
0.037
0.033
R-20
2x6
6
0.071
0.060
0.052
0.049
0.047
0.044
0.042
0.039
0.036
0.032
R-21 1
2x6
7
0.069
0.059
0.051
0.048
0.046
0.043
0.041
0.038
0.035
0.031
R-22
2x6
8
0.072
0.062
0.054
0.051
0.048
0.045
0.043
0.037
0.036
0.033
R-23
2x6
9
0.067
0.057
0.049
0.047
0.044
0.042
0.040
0.037
0.034
0.030
R-25
2x6
10
0.065
0.055
0.048
0.045
0.043
0.040
0.039
0.035
0.036
0.032
R-19
2x8
11
0.065
0.057
0.051
0.048
0.045
0.043
0.041
0.038
0.035
0.032
R-22
2x8
12
0.061
0.053
0.047
0.045
0.043
0.041
0.039
0.036
0.033
0.030
R-25
2x8
13
0.057
0.050
0.044
0.042
0.040
0.038
0.037
0.034
0.032
0.029
R-30 1
2x8
14
0.056
0.049
0.044
0.041
0.040
0.038
0.036
0.033
0.031
0.028
24 in. OC
None
Any
15
0.362
0.211
0.148
0.128
0.114
0.102
0.092
0.078
0.067
0.056
R-11
2x4
16
0.106
0.086
0.072
0.067
0.062
0.059
0.055
0.050
0.045
0.039
R-13
2x4
17
0.098
0.079
0.067
0.062
0.058
0.055
0.052
0.047
0.043
0.038
R-15
2x4
18
0.091
0.074
0.063
0.059
0.055
0.052
0.049
0.044
0.040
0.036
R-19
2x6
19
0.071
0.061
0.053
0.050
0.048
0.045
0.043
0.040
0.036
0.033
R-20
2x6
20
0.068
0.058
0.051
0.048
0.045
0.043
0.041
0.038
0.035
0.031
R-21 1
2x6
21
0.066
0.057
0.050
0.047
0.045
0.042
0.040
0.037
0.034
0.031
R-22
2x6
22
0.069
0.060
0.052
0.049
0.047
0.044
0.042
0.036
0.036
0.033
R-23
2x6
23
0.064
0.054
0.048
0.045
0.043
0.041
0.039
0.036
0.033
0.030
R-25
2x6
24
0.061
0.052
0.046
0.043
0.041
0.039
0.037
0.034
0.035
0.031
R-19
2x8
25
0.063
0.055
0.049
0.047
0.045
0.043
0.041
0.037
0.035
0.031
R-22
2x8
26
0.058
0.051
0.046
0.044
0.042
0.040
0.038
0.035
0.033
0.030
R-25
2x8
27
0.055
0.048
0.043
0.041
0.039
0.037
0.036
0.033
0.031
0.028
R-30 1
2x8
28
0.054
0.047
0.042
0.040
0.038
0.037
0.035
0.033
0.030
0.028

Notes:
1. Higher density fiberglass batt is required in these cases.
2. Continuous insulation may be installed on either the inside or the exterior of the wall, or both.

This table contains U-factors for wood framed walls, which are typical of low-rise residential buildings and Type V nonresidential buildings. If continuous insulation is not used, then choices are made from Column A. In this case, the insulation is installed in the cavity between the framing members. When continuous insulation is used, this is typically installed on the exterior side of the wall, but can also be used on the inside. The continuous insulation is typically a rigid polystyrene or polyisocyanurate foam insulation.

When this table is used manually, the R-value of continuous insulation shall be equal to or greater than the R-value published in the continuous insulation columns. No interpolation is permitted when data from the table is used manually. Commission approved compliance software, however, may determine the U-factor for any amount of continuous insulation or for unusual construction assemblies using Equation 4-1 and Equation 4-2.

Table 4.3.1(a) – U-factors of Wood Framed Walls with 5/8-inch Gypsum Board1 (Only to be used when 5/8 inch gypsum is installed)

Spacing
Cavity Insulation
Nominal Framing Size
Rated R-value of Continuous Insulation3
R-0
R-2
R-4
R-5
R-6
R-7
R-8
R-10
A
B
C
D
E
F
G
H
16 in. OC
None
Any
1
0.343
0.208
0.145
0.126
0.112
0.100
0.091
0.077
R-11
2x4
2
0.109
0.087
0.073
0.067
0.063
0.059
0.055
0.050
R-13
2x4
3
0.101
0.081
0.068
0.063
0.059
0.056
0.052
0.047
R-15 2
2x4
4
0.094
0.076
0.064
0.059
0.055
0.052
0.049
0.045
R-19
2x6
5
0.073
0.062
0.054
0.050
0.048
0.045
0.043
0.040
R-21 2
2x6
6
0.068
0.058
0.050
0.047
0.045
0.041
0.040
0.038
R-22
2x6
7
0.071
0.061
0.053
0.050
0.047
0.044
0.042
0.039
R-19
2x8
8
0.064
0.056
0.050
0.047
0.044
0.042
0.040
0.038
R-22
2x8
9
0.060
0.052
0.046
0.044
0.042
0.040
0.038
0.036
R-25
2x8
10
0.056
0.049
0.043
0.041
0.039
0.037
0.036
0.034
R-30 2
2x8
11
0.055
0.048
0.043
0.040
0.039
0.037
0.035
0.033
24 in. OC
None
Any
12
0.361
0.210
0.147
0.127
0.113
0.101
0.091
0.077
R-11
2x4
13
0.105
0.085
0.071
0.066
0.061
0.058
0.055
0.049
R-13
2x4
14
0.097
0.078
0.066
0.061
0.057
0.054
0.052
0.046
R-15
2x4
22
0.090
0.073
0.062
0.058
0.054
0.051
0.049
0.04
R-19
2x6
15
0.070
0.060
0.052
0.049
0.047
0.044
0.043
0.039
R-21 2
2x6
16
0.065
0.056
0.049
0.046
0.044
0.041
0.040
0.037
R-22
2x6
17
0.068
0.059
0.051
0.048
0.046
0.043
0.042
0.038
R-19
2x8
18
0.062
0.054
0.048
0.046
0.044
0.042
0.041
0.037
R-22
2x8
19
0.057
0.050
0.045
0.043
0.041
0.039
0.038
0.035
R-25
2x8
20
0.054
0.047
0.042
0.040
0.038
0.036
0.036
0.033
R-30 1
2x8
21
0.053
0.046
0.041
0.039
0.037
0.036
0.035
0.033

Notes:
1. The 5/8 inch gypsum board must be verified by the enforcement agency. If 5/8 inch gypsum board is not installed use table 4.3.1.
2. Higher density fiberglass batt is required in these cases.
3. Continuous insulation may be installed on either the inside or the exterior of the wall, or both.

This table contains U-factors for wood framed walls, which are typical of low-rise residential buildings and Type V nonresidential buildings. If continuous insulation is not used, then choices are made from Column A. In this case, the insulation is installed in the cavity between the framing members. When continuous insulation is used, this is typically installed on the exterior side of the wall, but can also be used on the inside. The continuous insulation is typically a rigid polystyrene or polyisocyanurate foam insulation.

When this table is used manually, the R-value of continuous insulation shall be equal to or greater than the R-value published in the continuous insulation columns. No interpolation is permitted when data from the table is used manually. Commission approved compliance software, however, may determine the U-factor for any amount of continuous insulation or for unusual construction assemblies using Equation 4-1 and Equation 4-2.

P3949#yIS1

Figure 4.3.1 – Wood Framed Wall

Assumptions: Values in this table were calculated using the parallel heat flow calculation method, documented in the 2009 ASHRAE Handbook of Fundamentals. The construction assembly assumes an exterior air film of R-0.17, a 7/8 inch layer of stucco of R-0.18 (SC01), building paper of R-0.06 (BP01), continuous insulation (if any), the cavity insulation / framing layer, 1/2 inch gypsum board of R-0.45 (GP01) or 5/8 inch gypsum board of R-0.56, and an interior air film 0.68. The framing factor is assumed to be 25 percent for 16 inch stud spacing and 22 percent for 24 inch spacing. Actual cavity depth is 3.5 inch for 2x4, 5.5 inch for 2x6, 7.25 inch for 2x8, 9.25 inch for 2x10, and 11.25 inch for 2x12. High density R-30 insulation is assumed to be 8.5 inch thick batt and R-38 is assumed to be 10.5 inch thick. The thickness of the stucco is assumed to be reduced to 3/8 inch when continuous insulation is applied.

Table 4.3.2 – U-factors of Structurally Insulated Wall Panels (SIPS)

Wood Framing Connection Type (spline)
Insulation Core R-value1
Typical Panel Thickness
Rated R-value of Continuous Insulation5
None
R-2
R-4
R-5
R-6
R-8
A
B
C
D
E
F
OSB
R-14
4.5 in
1
0.061
0.055
0.049
0.047
0.045
0.041
Single 2x
R-14
4.5 in
2
0.071
0.061
0.054
0.051
0.048
0.044
Double 2x
R-14
4.5 in
3
0.077
0.065
0.057
0.054
0.050
0.046
I-joist
R-14
4.5 in
4
0.070
0.060
0.053
0.051
0.048
0.044
OSB
R-18 2
4.5 in
5
0.053
0.045
0.041
0.039
0.037
0.034
Single 2x
R-18 2
4.5 in
6
0.061
0.052
0.047
0.045
0.042
0.039
Double 2x
R-18 2
4.5 in
7
0.066
0.056
0.050
0.048
0.045
0.041
I-joist
R-18 2
4.5 in
8
0.059
0.051
0.046
0.044
0.042
0.038
OSB
R-22
6.5 in
9
0.041
0.038
0.036
0.035
0.033
0.031
Single 2x
R-22
6.5 in
10
0.050
0.044
0.040
0.039
0.037
0.034
Double 2x
R-22
6.5 in
11
0.054
0.048
0.043
0.041
0.039
0.036
I-joist
R-22
6.5 in
12
0.048
0.043
0.039
0.038
0.036
0.033
OSB
R-28
8.25 in
13
0.032
0.030
0.029
0.028
0.027
0.026
Single 2x
R-28
8.25 in
14
0.039
0.036
0.033
0.032
0.031
0.029
Double 2x
R-28
8.25 in
15
0.043
0.039
0.035
0.034
0.033
0.030
I-joist
R-28
8.25 in
16
0.037
0.034
0.032
0.031
0.030
0.028
OSB
R-33 3
6.5 in
17
0.032
0.029
0.027
0.026
0.025
0.023
Single 2x
R-33 3
6.5 in
18
0.038
0.034
0.031
0.030
0.029
0.027
Double 2x
R-33 3
6.5 in
19
0.043
0.038
0.034
0.033
0.031
0.029
I-joist
R-33 3
6.5 in
20
0.036
0.033
0.030
0.029
0.028
0.026
OSB
R-36
10.25 in
21
0.026
0.024
0.023
0.023
0.022
0.021
Single 2x
R-36
10.25 in
22
0.032
0.030
0.028
0.027
0.026
0.024
Double 2x
R-36
10.25 in
23
0.035
0.032
0.030
0.029
0.028
0.026
I-joist
R-36
10.25 in
24
0.030
0.028
0.026
0.026
0.025
0.023
OSB
R-44
12.25 in
25
0.022
0.021
0.020
0.020
0.019
0.018
Single 2x
R-44
12.25 in
26
0.027
0.025
0.024
0.023
0.022
0.021
Double 2x
R-44
12.25 in
27
0.028
0.027
0.025
0.025
0.024
0.023
I-joist
R-44
12.25 in
28
0.025
0.024
0.022
0.022
0.021
0.020
OSB
R-55 4
10.25 in
29
0.020
0.019
0.017
0.016
0.016
0.016
Single 2x
R-55 4
10.25 in
30
0.024
0.022
0.021
0.021
0.020
0.019
Double 2x
R-55 4
10.25 in
31
0.028
0.025
0.023
0.023
0.022
0.021
I-joist
R-55 4
10.25 in
32
0.022
0.021
0.019
0.019
0.018
0.018

Notes:
1. The insulation R-value must be at least R-14 in order to use this table. This table assumes moulded expanded polystyrene (EPS) unless noted otherwise. Although other insulation types are used by some SIP manufacturers, such as polyurethane and extruded expanded insulation (XPS), EPS is the most common insulation used in SIP construction.
2. R-18.1 is achievable using extruded expanded polystyrene (XPS) insulation in 4.5" thick panels.
3. R-33.2 is achievable using polyurethane insulation in 6.5" panels.
4. R-55.3 is achievable using polyurethane insulation in 10.25" panels.
5. Continuous insulation shall be at least R-2 and may be installed on either the inside or the exterior of the wall.

Structural insulated panels (SIPs) consist of a rigid insulation core, securely bonded between two structural facings, to form a structural sandwich panel. SIPs are considered a non-framed assembly usually with little or no structural framing that penetrates the insulation layer, resulting in less thermal bridging across the insulation when compared to a conventional framed assembly.

This table gives U-factors for structurally insulated panels used in wall construction. This is a construction system that consists of rigid foam insulation sandwiched between two layers of plywood or oriented strand board (OSB). Data is provided for four variations of connecting two panels together.

If continuous insulation is not used, then choices are made from Column A. When continuous insulation is also used, this is typically installed on the exterior side of the wall, but can also be used on the inside. The continuous insulation is typically a rigid polystyrene or polyisocyanurate foam insulation. Adding continuous insulation to a SIPS panel is highly unusual since the panel itself is mostly continuous insulation.

When this table is used manually, the R-value of continuous insulation shall be equal to or greater than the R-value published in the continuous insulation columns. No interpolation is permitted when data from the table is used manually. Commission approved software, however, may determine the U-factor for any amount of continuous insulation or for unusual construction assemblies using Equation 4-1 and Equation 4-2.

P4347#yIS1

Figure 4.3.2 – Structurally Insulated Wall Panels (SIPS)

This figure shows just one way that panels are connected. Other options exist.

Assumptions: These data are calculated using the parallel path method documented in the 2009 ASHRAE Handbook of Fundamentals.

These calculations assume an exterior air film of R-0.17, a 7/8 inch layer of stucco of R-0.18, building paper of R-0.06 (BP01), 7/16 inch of OSB of R-0.44, insulation at carrying R-values (as specified), 7/16 inch of OSB of R-0.44, ½ inch gypsum board of R-0.45 (GP01), and in interior air film of R-0.68. A framing factor of 13 percent is assumed for wood spacers and 7 percent for the OSB spline system. Framing includes the sill plate, the header and framing around windows and doors.

Table 4.3.3 – U-factors of Metal Framed Walls for Nonresidential Construction

Spacing
Cavity Insulation R-Value:
Nominal Framing Size
Rated R-value of Continuous Insulation 2
R-0
R-2
R-4
R-5
R-6
R-7
R-8
R-10
R-12
R-14
R-15
A
B
C
D
E
F
G
H
I
J
K
16 in. OC
None
Any
1
0.458
0.239
0.162
0.139
0.122
0.109
0.098
0.082
0.071
0.062
0.058
R-5
2x4
2
0.351
0.206
0.146
0.127
0.113
0.102
0.092
0.078
0.067
0.059
0.056
R-11
2x4
3
0.224
0.155
0.118
0.106
0.096
0.087
0.080
0.069
0.061
0.054
0.052
R-13
2x4
4
0.217
0.151
0.116
0.104
0.094
0.086
0.079
0.068
0.060
0.054
0.051
R-15
2x4
5
0.211
0.148
0.114
0.103
0.093
0.085
0.078
0.068
0.060
0.053
0.050
R-19
2x6
6
0.183
0.134
0.106
0.096
0.087
0.080
0.074
0.065
0.057
0.051
0.049
R-20
2x6
7
0.181
0.133
0.105
0.095
0.087
0.080
0.074
0.064
0.057
0.051
0.049
R-211
2x6
8
0.178
0.131
0.104
0.094
0.086
0.079
0.073
0.064
0.057
0.051
0.049
R-19
2x8
9
0.164
0.123
0.099
0.090
0.083
0.076
0.071
0.062
0.055
0.050
0.047
R-22
2x8
10
0.160
0.121
0.098
0.089
0.082
0.075
0.070
0.062
0.055
0.049
0.047
R-25
2x8
11
0.158
0.120
0.097
0.088
0.081
0.075
0.070
0.061
0.055
0.049
0.047
R-301
2x8
12
0.157
0.119
0.096
0.088
0.081
0.075
0.070
0.061
0.054
0.049
0.047
24 in. OC
None
Any
13
0.455
0.238
0.161
0.139
0.122
0.109
0.098
0.082
0.070
0.062
0.058
R-5
2x4
14
0.333
0.200
0.143
0.125
0.111
0.100
0.091
0.077
0.067
0.059
0.056
R-11
2x4
15
0.210
0.148
0.114
0.102
0.093
0.085
0.078
0.068
0.060
0.053
0.051
R-13
2x4
16
0.203
0.144
0.112
0.101
0.092
0.084
0.077
0.067
0.059
0.053
0.051
R-15
2x4
17
0.197
0.141
0.110
0.099
0.090
0.083
0.076
0.066
0.059
0.052
0.050
R-19
2x6
18
0.164
0.123
0.099
0.090
0.083
0.076
0.071
0.062
0.055
0.050
0.047
R-20
2x6
19
0.164
0.123
0.099
0.090
0.083
0.076
0.071
0.062
0.055
0.050
0.047
R-211
2x6
20
0.161
0.122
0.098
0.089
0.082
0.076
0.070
0.062
0.055
0.049
0.047
R-19
2x8
21
0.153
0.117
0.095
0.087
0.080
0.074
0.069
0.060
0.054
0.049
0.047
R-22
2x8
22
0.149
0.115
0.093
0.085
0.079
0.073
0.068
0.060
0.053
0.048
0.046
R-25
2x8
23
0.147
0.114
0.093
0.085
0.078
0.072
0.068
0.060
0.053
0.048
0.046
R-30 1
2x8
24
0.146
0.113
0.092
0.084
0.078
0.072
0.067
0.059
0.053
0.048
0.046

Notes:
1. Higher density fiberglass batt is required in these cases.
2. Continuous insulation may be installed on either the inside or the exterior of the wall, or both.

This table contains U-factors for steel or metal-framed walls, which are typical of nonresidential buildings. The table may be used for any construction assembly where the insulation is installed in the cavity of a metal-framed wall, or where continuous insulation is installed on the exterior or interior of the metal framing, or a combination of these two methods of insulating a metal-framed wall.

If continuous insulation is not used, then choices are made from Column A. In this case, the insulation is installed only in the cavity between the framing members. When continuous insulation is used, it is typically installed on the exterior side of the wall, but can also be used on the inside. The continuous insulation is typically a rigid polystyrene or polyisocyanurate foam insulation.

P4794#yIS1

Figure 4.3.3 – Metal Framed Wall

When this table is used manually, the R-value of continuous insulation shall be equal to or greater than the R-value published in the continuous insulation columns. No interpolation is permitted when data from the table is used manually. Commission approved compliance software programs, however, may determine the U-factor for any amount of continuous insulation or for unusual construction assemblies using Equation 4-1 and Equation 4-2.

Assumptions: Values in this table were calculated using the zone calculation method. The construction assembly assumes an exterior air film of R-0.17, a 7/8 inch layer of stucco of R-0.18, building paper of R-0.06 (BP01), continuous insulation (if any), the insulation / framing layer, 1/2 inch gypsum of R-0.45 gypsum board (GP01), and an interior air film 0.68. The steel framing is assumed to be 0.0747 inch thick with a 15 percent knock out. The framing factor is assumed to be 25 percent for 16 inch stud spacing and 22 percent for 24 inch spacing. The EZFrame internal default framing percentages are 15 percent for 16 inch stud spacing and 12 percent for 24 inch spacing. To account for the increased wall framing percentage the frame spacing input to the EZ Frame program is reduced to 13.218 inches for 16 inch stud spacing and 15.231 inches for 24 inch stud spacing. Actual cavity depth is 3.5 inch for 2x4, 5.5 inch for 2x6, 7.25 inch for 2x8, 9.25 inch for 2x10, and 11.25 inch for 2x12. High density R-30 insulation is assumed to be 8.5 inch thick batt and R-38 is assumed to be 10.5 inch thick. The thickness of the stucco is assumed to be reduced to 3/8 inch when continuous insulation is applied.

Table 4.3.4 – U-factors of Metal Framed Walls for Residential Construction

Rated R-value of Continuous Insulation2

Spacing
Cavity Insulation R-Value:
Nominal Framing Size
R-0
R-2
R-4
R-5
R-6
R-7
R-8
R-10
R-12
R-15
A
B
C
D
E
F
G
H
I
J
16 in. OC
None
Any
1
0.455
0.238
0.161
0.139
0.122
0.109
0.098
0.082
0.070
0.058
R-05
2x4
2
0.252
0.165
0.124
0.110
0.099
0.090
0.083
0.071
0.062
0.052
R-11
2x4
3
0.200
0.137
0.107
0.097
0.088
0.081
0.075
0.065
0.058
0.049
R-13
2x4
4
0.192
0.132
0.105
0.095
0.087
0.080
0.074
0.064
0.057
0.049
R-15
2x4
5
0.186
0.129
0.102
0.093
0.085
0.078
0.073
0.063
0.056
0.048
R-19
2x6
6
0.154
0.112
0.092
0.084
0.077
0.072
0.067
0.059
0.053
0.046
R-20
2x6
7
0.151
0.112
0.091
0.084
0.077
0.072
0.067
0.059
0.053
0.046
R-211
2x6
8
0.151
0.110
0.090
0.083
0.076
0.071
0.066
0.058
0.052
0.045
R-19
2x8
9
0.134
0.102
0.085
0.078
0.072
0.067
0.063
0.056
0.050
0.044
R-22
2x8
10
0.129
0.099
0.082
0.076
0.071
0.066
0.062
0.055
0.050
0.043
R-25
2x8
11
0.125
0.096
0.081
0.075
0.069
0.065
0.061
0.054
0.049
0.043
R-301
2x8
12
0.120
0.093
0.078
0.073
0.068
0.063
0.060
0.053
0.048
0.042
R-30
2x10
13
0.109
0.086
0.073
0.068
0.064
0.060
0.057
0.051
0.046
0.041
R-381
2x10
14
0.104
0.082
0.071
0.066
0.062
0.058
0.055
0.050
0.045
0.040
R-38
2 x 12
15
0.095
0.077
0.067
0.062
0.059
0.055
0.053
0.048
0.043
0.038
24 in. OC
None
Any
16
0.449
0.236
0.161
0.138
0.121
0.108
0.098
0.082
0.070
0.058
R-05
2x4
17
0.243
0.161
0.122
0.108
0.098
0.089
0.082
0.070
0.062
0.052
R-11
2x4
18
0.189
0.131
0.104
0.094
0.086
0.079
0.073
0.064
0.057
0.048
R-13
2x4
19
0.181
0.127
0.101
0.092
0.084
0.078
0.072
0.063
0.056
0.048
R-15
2x4
20
0.175
0.123
0.099
0.090
0.082
0.076
0.071
0.062
0.055
0.047
R-19
2x6
21
0.144
0.107
0.088
0.081
0.075
0.070
0.065
0.058
0.052
0.045
R-20
2x6
22
0.141
0.106
0.087
0.080
0.074
0.069
0.065
0.057
0.051
0.044
R-211
2x6
23
0.141
0.105
0.086
0.080
0.074
0.069
0.064
0.057
0.051
0.044
R-19
2x8
24
0.126
0.097
0.081
0.075
0.070
0.065
0.061
0.055
0.049
0.043
R-22
2x8
25
0.121
0.094
0.079
0.073
0.068
0.064
0.060
0.054
0.048
0.042
R-25
2x8
26
0.117
0.091
0.077
0.071
0.067
0.063
0.059
0.053
0.048
0.042
R-301
2x8
27
0.112
0.088
0.075
0.069
0.065
0.061
0.057
0.052
0.047
0.041
R-30
2x10
28
0.102
0.081
0.070
0.065
0.061
0.058
0.055
0.049
0.045
0.039
R-381
2x10
29
0.096
0.077
0.067
0063
0.059
0.056
0.053
0.048
0.044
0.039
R-38
2 x 12
30
0.088
0.072
0.063
0.059
0.056
0.053
0.050
0.046
0.042
0.037

Notes:
1. Higher density fiberglass batt is required in these cases.
2. Continuous insulation may be installed on either the inside or the exterior of the wall, or both.

This table contains U-factors for steel or metal framed walls in low-rise residential buildings where the thickness of the framing members is 18 gauge or thinner. Table 4.3.3 in Reference Joint Appendix JA4 must be used for steel-framed or metal-framed walls in nonresidential buildings (including high-rise residential buildings and hotels and motels) and in low rise residential buildings if the thickness of the framing members are thinner than 18 gauge.

If continuous insulation is not used, then choices are made from Column A. In this case, the insulation is installed only in the cavity between the framing members. When continuous insulation is used, it is typically installed on the exterior side of the wall, but can also be used on the inside. The continuous insulation is typically a rigid polystyrene or polyisocyanurate foam insulation.

P5285#yIS1

Figure 4.3.4 – Metal Framed Wall

When this table is used manually, the R-value of continuous insulation shall be equal to or greater than the R-value published in the continuous insulation columns. No interpolation is permitted when data from the table is used manually. Commission approved compliance software programs, however, may determine the U-factor for any amount of continuous insulation or for unusual construction assemblies using Equation 4-1 and Equation 4-2.

Assumptions: Values in this table were calculated using the zone calculation method. The construction assembly assumes an exterior air film of R-0.17, a 7/8 inch layer of siding or stucco averaging R-0.18, building paper of R-0.06 (BP01), continuous insulation (if any), the insulation / framing insulation layer, 1/2 inch gypsum of R-0.45 gypsum board (GP01), and an interior air film 0.68. The framing factor is assumed to be 25 percent for 16 inch stud spacing and 22 percent for 24 inch spacing. To account for the increased wall framing percentage, the frame spacing input to the EZ Frame program is reduced to 13.218 inches for 16 inch stud spacing and 15.231 inches for 24 inch stud spacing. The stud web thickness is assumed to be 0.038 inches, which is a 50/50 mix of 18 gauge and 20 gauge C-channel studs. This value was confirmed to be representative of low-rise residential construction by polling several California-based light-gauge steel structural engineers and light-gauge steel framers. Actual cavity depth is 3.5 inch for 2x4, 5.5 inch for 2x6, 8 inch for 2x8, 10 inch for 2x10, and 12 inches for 2x12. High density R-30 insulation is assumed to be 8.5 inch thick batt and R-38 is assumed to be 10.5 inches thick. The thickness of the stucco is assumed to be reduced to 3/8 inch when continuous insulation is applied.

Table 4.3.5 – Properties of Hollow Unit Masonry Walls

Thickness
Type
Partly Grouted with Ungrouted Cells
Solid Grout
Empty
Insulated
A
B
C
U-factor
C-factor
HC
U-factor
C-factor
HC
U-factor
C-factor
HC
12"
LW CMU
1
0.51
0.90
23
0.43
0.68
14.8
0.30
0.40
14.8
MW CMU
2
0.54
1.00
23.9
0.46
0.76
15.6
0.33
0.46
15.6
NW CMU
3
0.57
1.11
24.8
0.49
0.84
16.5
0.36
0.52
16.5
10"
LW CMU
4
0.55
1.03
18.9
0.46
0.76
12.6
0.34
0.48
12.6
MW CMU
5
0.59
1.18
19.7
0.49
0.84
13.4
0.37
0.54
13.4
NW CMU
6
0.62
1.31
20.5
0.52
0.93
14.2
0.41
0.63
14.2
8"
LW CMU
7
0.62
1.31
15.1
0.50
0.87
9.9
0.37
0.54
9.9
MW CMU
8
0.65
1.45
15.7
0.53
0.96
10.5
0.41
0.63
10.5
NW CMU
9
0.69
1.67
16.3
0.56
1.07
11.1
0.44
0.70
11.1
Clay Unit
10
0.57
1.11
15.1
0.47
0.78
11.4
0.39
0.58
11.4
6"
LW CMU
11
0.68
1.61
10.9
0.54
1.00
7.9
0.44
0.70
7.9
MW CMU
12
0.72
1.86
11.4
0.58
1.14
8.4
0.48
0.81
8.4
NW CMU
13
0.76
2.15
11.9
0.61
1.27
8.9
0.52
0.93
8.9
Clay Unit
14
0.65
1.45
11.1
0.52
0.93
8.6
0.45
0.73
8.6

The walls addressed in this table are rarely used in residential construction, but are common in some types of nonresidential construction. The tables include four types of hollow masonry units: lightweight concrete masonry units (CMU), medium weight CMU, normal weight CMU, and hollow clay masonry units. ASTM C-90 defines these masonry products in more detail.

Masonry used in California must be reinforced to withstand wind loads and earthquakes. This is achieved by installing reinforcing steel and grouting the cells in both a vertical and horizontal direction. Since grouting the cells affects thermal performance, data is provided for three cases: where every cell is grouted, where the cells are partially grouted and the remaining cells are left empty, and where the cells are partially grouted and the remaining cells are filled with perlite or some other insulating material.

P5524#yIS1

Figure 4.3.5 – Masonry Wall

For each of these conditions the U-factor, C-factor and heat capacity (HC) is published. There are other properties of mass materials that may be needed in compliance calculations, but these values can be determined from the published data using the procedures in Modeling Constructions in the Nonresidential compliance software and in Section 4.6 of this document.

Assumptions: Data is taken from Energy Calculations and Data, CMACN, 1986, Berkeley Solar Group; Concrete Masonry Association of California and Nevada. The density of the CMU material (not counting the grouted or hollow cells) is 105 lb/ft³ for lightweight, 115 lb/ft³ for medium weight and 125 lb/ft³ for normal weight. The density of the clay unit material is 130 lb/ft³. For all four types of masonry units, data is provided for thicknesses of 6 in., 8 in., 10 in., and 12 in. For the partially grouted cases, vertical cells are assumed to be grouted at 32 inch on center. Reinforcing in the horizontal direction is at 48 in. on center. Wall thicknesses given in the table are nominal; actual thicknesses are 3/8 in. less. Insulating material inside unit masonry hollow is assumed to be perlite.

Table 4.3.6 – Properties of Solid Unit Masonry and Solid Concrete Walls

Type
Property
Wall Thickness, inches
3
4
5
6
7
8
9
10
11
12
A
B
C
D
E
F
G
H
I
J
LW CMU
U-Factor
1
0.79
0.71
0.65
0.59
0.54
0.51
0.47
0.44
0.42
0.39
C-Factor
2.38
1.79
1.43
1.18
1.01
0.88
0.79
0.71
0.65
0.59
HC
5.3
7.00
8.80
10.50
12.30
14.00
15.80
17.50
19.30
21.00
MW CMU
U-Factor
2
0.84
0.77
0.70
0.65
0.61
0.57
0.53
0.50
0.48
0.45
C-Factor
2.94
2.22
1.75
1.47
1.25
1.10
0.98
0.88
0.80
0.74
HC
5.80
7.70
9.60
11.5
13.40
15.30
17.30
19.20
21.10
23.00
NW CMU
U-Factor
3
0.88
0.82
0.76
0.71
0.67
0.63
0.60
0.56
0.53
0.51
C-Factor
3.57
2.70
2.17
1.79
1.54
1.35
1.20
1.03
0.98
0.90
HC
6.30
8.30
10.40
12.50
14.6
16.70
18.80
20.80
22.90
25.00
Clay Brick
U-Factor
4
0.80
0.72
0.66
na
na
na
na
na
na
na
C-Factor
2.50
1.86
1.50
na
na
na
na
na
na
na
HC
6.30
8.40
10.43
na
na
na
na
na
na
na
Concrete
U-Factor
5
0.96
0.91
0.86
0.82
0.78
0.74
0.71
0.68
0.65
0.63
C-Factor
5.22
4.02
3.20
2.71
2.31
1.99
1.79
1.61
1.45
1.36
HC
7.20
9.60
12.00
14.40
16.80
19.20
21.60
24.00
26.40
28.80

This table provides thermal performance information for solid masonry units and solid concrete walls.

The walls addressed in this table are rarely used in residential construction, but are common in some types of nonresidential construction.

There are other properties of mass materials that may be needed in compliance calculations, but these values can be determined from the published data using the procedures in Modeling Constructions in the Nonresidential compliance software and in Section 4.6 of this document.

When insulation is added to the outside of masonry walls and/or when the inside is furred and insulated, the performance data in this table may be adjusted using Equation 4-4 and Equation 4-5 in coordination with Table 4.3.14.

P5776C1T23#yIS1

Figure 4.3.6(a) - Solid Unit Masonry Wall

P5778C2T23#yIS1

Figure 4.3.6(b) - Solid Concrete Wall

Assumptions: Data is taken from ASHRAE/IESNA Standard 90.1-2004. The density of the CMU material is 105 lb/ft³ for lightweight, 115 lb/ft³ for medium weight and 125 lb/ft³ for normal weight. The density of the clay unit material is 130 lb/ft³ and the density of the concrete is 144 lb/ft³. For all five types of masonry walls, the U-factor, C-factor and heat capacity (HC) is provided for thicknesses of 3 inch, 4 inch, and 5 inch ASTM C-90 provides more information on the classification of masonry walls.

Table 4.3.7 – Properties of Concrete Sandwich Panels

Percent
Concrete Web
Steel
Penetrates
Insulation
Performance
Factor
Insulation Thickness (R-value)
1.5 (7.0)
2.0 (9.3)
3.0 (14.0)
4.0 (18.6)
6.0 (27.9)
A
B
C
D
E
0%
No
U-factor
1
0.122
0.095
0.066
0.051
0.034
C-factor
0.136
0.104
0.070
0.053
0.035
HC
16.13
16.13
16.13
16.13
16.13
Yes
U-factor
2
0.164
0.128
0.091
0.070
0.048
C-factor
0.190
0.144
0.099
0.074
0.050
HC
16.13
16.13
16.13
16.13
16.13
10%
No
U-factor
3
0.476
0.435
0.345
0.286
0.217
C-factor
0.800
0.690
0.488
0.377
0.267
HC
16.53
16.66
16.93
17.20
17.74
Yes
U-factor
4
0.500
0.435
0.357
0.303
0.227
C-factor
0.870
0.690
0.513
0.408
0.282
HC
16.53
16.66
16.93
17.20
17.74
20%
No
U-factor
5
0.588
0.556
0.476
0.417
0.333
C-factor
1.176
1.053
0.800
0.645
0.465
HC
16.93
17.20
17.74
18.28
19.35
Yes
U-factor
6
0.588
0.556
0.476
0.417
0.333
C-factor
1.176
1.053
0.800
0.645
0.465
HC
16.93
17.20
17.74
18.28
19.35

This table provides U-factors, C-factors, and heat capacity (HC) data for concrete sandwich panels. Concrete sandwich panels, as the name suggests, consist of two layers of concrete that sandwich a layer of insulation. The wall system can be constructed in the field or in a factory. One method of field construction is where the wall panels are formed in a flat position using the concrete floor slab of the building as the bottom surface. After the panel has set, it is hoisted with a crane into its final vertical position.

Both the percent of concrete web and the percent steel are factors in determining the thermal performance of walls. The insulation layer in this type of concrete sandwich panel generally does not extend over the entire surface of the wall. To provide structural integrity, a certain portion of the wall is solid concrete, which ties together the two concrete layers. This portion is known as the concrete web. The thermal performance of concrete sandwich panels depends on the percent of the wall that is concrete web. Data is provided for concrete webs representing 0 percent, 10 percent and 20 percent of the opaque wall surface. In some cases, the concrete layers are tied together by structural steel that penetrates the insulation layer. Data is provided for the case where this steel is present and for cases where it is not.

P5999#yIS1

Figure 4.3.7 – Concrete Sandwich Panel

Other properties of mass materials such as density, conductivity, specific heat and wall weight may be needed in compliance calculations and these properties may be determined from the published data in Table 4.3.7 using the procedures in Modeling Constructions in the Nonresidential compliance software and in Section 4.6 of this document.

Values from this table may be combined with values from Table 4.3.14 when a furring layer is added to the inside of the wall and/or continuous insulation is added to the outside of the wall. Adjustments for additional layers shall follow the procedure of Equation 4-4 and Equation 4-5.

Assumptions: U-factors include an inside air film of 0.68 and an exterior air film of 0.17. Conductivity of the concrete is assumed to be 0.215 Btu/h-ºF-f, density is 150 lb/ft³, the thickness of each side of the sandwich panel is 0.5 ft. The data was calculated by Construction Technologies Laboratories, Inc. and published in the Thermal Mass Handbook, Concrete and Masonry Design Provisions Using ASHRAE/IESNA 90.1-1989, National Codes and Standards Council of the Concrete and Masonry Industries, 1994.

Table 4.3.8 – U-factors for Spandrel Panels and Curtain Walls

Frame Type
Spandrel Panel
Rated R-value of Insulation between Framing Members
None
R-4
R-7
R-10
R-15
R-20
R-25
R-30
A
B
C
D
E
F
G
H
Aluminum without Thermal Break
Single glass pane, stone, or metal panel
1
0.445
0.285
0.259
0.247
0.236
0.230
0.226
0.224
Double glass with no low-e coatings
2
0.356
0.273
0.254
0.244
0.234
0.229
0.226
0.223
Triple or low-e glass
3
0.313
0.263
0.249
0.241
0.233
0.228
0.225
0.223
Aluminum with Thermal Break
Single glass pane, stone, or metal panel
4
0.429
0.243
0.212
0.197
0.184
0.176
0.172
0.169
Double glass with no low-e coatings
5
0.328
0.228
0.205
0.193
0.182
0.175
0.171
0.168
Triple or low-e glass
6
0.277
0.217
0.199
0.189
0.180
0.174
0.170
0.167
Structural Glazing
Single glass pane, stone, or metal panel
7
0.428
0.217
0.180
0.161
0.145
0.136
0.130
0.126
Double glass with no low-e coatings
8
0.316
0.199
0.172
0.157
0.143
0.135
0.129
0.126
Triple or low-e glass
9
0.257
0.186
0.165
0.152
0.140
0.133
0.128
0.125
No framing or Insulation is Continuous
Single glass pane, stone, or metal panel
10
0.445
0.160
0.108
0.082
0.058
0.045
0.037
0.031
Double glass with no low-e coatings
11
0.356
0.147
0.102
0.078
0.056
0.044
0.036
0.030
Triple or low-e glass
12
0.313
0.139
0.098
0.076
0.055
0.043
0.035
0.030
Frame Type
Curtain Wall
Aluminum without Thermal Break
Single glass pane, stone, or metal panel
13
1.224
0.929
0.427
0.372
0.347
0.326
0.315
0.308
Double glass with no low-e coatings
14
0.727
0.611
0.400
0.361
0.341
0.323
0.313
0.307
Triple or low-e glass
15
0.567
0.494
0.380
0.351
0.335
0.320
0.311
0.306
Aluminum with Thermal Break
Single glass pane, stone, or metal panel
16
1.110
0.862
0.339
0.282
0.256
0.234
0.222
0.215
Double glass with no low-e coatings
17
0.617
0.531
0.311
0.270
0.249
0.230
0.220
0.214
Triple or low-e glass
18
0.458
0.409
0.290
0.260
0.243
0.227
0.218
0.212
Structural Glazing
Single glass pane, stone, or metal panel
19
1.106
0.859
0.290
0.228
0.199
0.175
0.162
0.154
Double glass with no low-e coatings
20
0.577
0.502
0.260
0.215
0.192
0.171
0.160
0.152
Triple or low-e glass
21
0.407
0.368
0.237
0.204
0.185
0.168
0.158
0.151
No framing or Insulation is Continuous
Single glass pane, stone, or metal panel
22
1.224
0.929
0.197
0.124
0.090
0.062
0.047
0.038
Double glass with no low-e coatings
23
0.727
0.611
0.177
0.116
0.086
0.060
0.046
0.038
Triple or low-e glass
24
0.567
0.494
0.166
0.111
0.083
0.059
0.045
0.037

This table has U-factors for the spandrel section of glass and other curtain wall systems. Design factors that affect performance are the type of framing, the type of spandrel panel and the R-value of insulation.

Four framing conditions are considered in the table. The first is the common case where standard aluminum mullions are used. Standard mullions provide a thermal bridge through the insulation, reducing its effectiveness. The second case is for metal framing members that have a thermal break. A thermal break frame uses a urethane or other non-metallic element to separate the metal exposed to outside conditions from the metal that is exposed to interior conditions. The third case is for structural glazing or systems where there is no exposed mullion on the interior. The fourth case is for the condition where there is no framing or the insulation is continuous and uninterrupted by framing. The columns in the table can be used for any specified level of insulation between framing members installed in framed curtain walls or spandrel panels.

P6332#yIS1

Figure 4.3.8 – Spandrel Panel

There are three cases considered in the table. To determine an appropriate thermal performance value the assumption used to differenciate between spandrel panels and curtain walls is that spandrel panels include an air gap and rigid backing, while curtain walls do not. The first is for a panel that provides little or no insulating value. This includes single pane glass, stone veneer, metal panels, or pre-case concrete less than 2 inches thick. The second case is for insulating glass. Sometimes insulating glass is used so that the spandrel panel looks similar to the vision glass. The third case is for triple glass or double glass that has a low-e coating.

Insulation levels are shown in the columns of the table. When the table is used manually, the R-value of insulation shall be equal to or greater than the R-value published in the columns. No interpolation is permitted when data from the table is selected manually. California Energy Commission approved compliance software programs, including those used for prescriptive compliance, may accurately account for any amount of continuous insulation or for unusual construction assemblies using Equation 4-1 and Equation 4-2. If the curtain wall has an insulated metal-framed wall on the inside, then values from this table may be combined with values from Table 4.3.4 or Table 4.3.14 using the procedures of Equation 4-2 or Equation 4-3.

Assumptions: The U-factors in Table 4.3.8 were derived from a regression analysis of the values for “Glass Only Center of Glass” and “Curtain Wall” in the 2009 ASHRAE Handbook of Fundamentals, Chapter 15, Table 4, with adaptions to update the values. The U-factors in Table 4.3.8 for curtain walls include an exterior air film with an R-value of 0.17 and an interior air film R-value of 0.68, which are accounted for in the values from the 2009 ASHRAE Handbook of Fundamentals. For spandrel panels the construction assembly includes an air gap with an R-value of 1.39 (3/4 inch gap, 50 ºF mean temperature and 30 ºF temperature difference), and includes 5/8 inch gypsum board with an R-value of 0.56 that provides the interior finish. The gypsum board is assumed to span between the window sill and a channel at the floor.

Table 4.3.9 – U-factors for Metal Building Walls

Insulation System
Rated R-Value of Insulation
Continuous Rigid Insulation
None
R-2
R-4
R-6
R-7
R-8
R-10
R-14
A
B
C
D
E
F
G
H
Single Layer of Batt Insulation
None
1
1.18
0.351
0.206
0.146
0.127
0.113
0.092
0.067
R-6
2
0.184
0.135
0.106
0.087
0.080
0.074
0.065
0.051
R-10
3
0.134
0.106
0.087
0.074
0.069
0.065
0.057
0.047
R-11
4
0.123
0.099
0.082
0.071
0.066
0.062
0.055
0.045
R-13
5
0.113
0.092
0.078
0.067
0.063
0.059
0.053
0.044
Double Layer of Batt Insulation
R-6 + R-13
6
0.07
0.061
0.055
0.049
0.047
0.045
0.041
0.035
R-10 + R-13
7
0.061
0.054
0.049
0.045
0.043
0.041
0.038
0.033
R-13 + R-13
8
0.057
0.051
0.046
0.042
0.041
0.039
0.036
0.032
R-19 + R-13
9
0.048
0.044
0.040
0.037
0.036
0.035
0.032
0.029

Double layer or batt insulation may not be able to have continuous rigid insulation added.

The U-factors in this table are intended for use with metal building walls. This type of construction is typical for manufacturing and warehouse facilities, but is used for other building types as well. The typical method of insulating this type of building is to stretch vinyl backed fiberglass insulation over the metal girts before the metal siding is attached with metal screws. With this method, the insulation is compressed at each girt, reducing its effectiveness. The first part of the table contains values for this insulation technique. The second section of the table has data for systems that have two layers of insulation. In this section layers are listed from inside to outside.

For the majority of cases, values will be selected from column A of this table. Builders or designers may increase thermal performance by adding a rigid continuous insulation layer between the metal siding and the structural supports. When this table is used manually, the R-value of continuous insulation shall be equal to or greater than the R-value published in the continuous insulation columns. No interpolation is permitted when data from the table is used manually. Energy Commission approved compliance software, however, may determine the U-factor for any amount of continuous insulation using Equation 4-1.

P6477#yIS1

Figure 4.3.9 – Metal Building Wall

Assumptions: Data in Column A of this table is taken from the ASHRAE/IESNA Standard 90.1-2004, Appendix A. The data in columns beyond A are calculated using Equation 4-1.

Table 4.3.10 – U-factors for Insulated Metal Panel Walls

Panel Thickness
U-factor
(Btu/0 F-ft2)
A
2”
1
0.078
2 ½”
2
0.063
3”
3
0.053
4”
4
0.041
5”
5
0.033
6”
6
0.027

This table contains thermal performance data (U-factors) for foamed-in-place, insulated metal panels consisting of liquid polyurethane or polyisocyanurate injected between metal skins in individual molds or on fully automated production lines. Metal building construction is the most common application for this product where the metal panel is fastened to the frame of the structure. This table can only be used for insulated panels that are factory built. This table does not apply to panels that utilize polystyrene, or to field applied products such as spray applied insulations.

P6515#yIS1

Figure 4.3.10 –Insulated Metal Panel Walls

Assumptions. These data are calculated using the parallel path method documented in the 2009 ASHRAE Handbook of Fundamentals. These calculations assume an exterior air film of R-0.17, light gauge metal exterior of 0.0747 inch thickness, continuous insulation R-5.9 per inch, light gauge metal interior of 0.0747 inch thickness, interior air film (heat flow horizontal) of R-0.68. The panels are assumed to be continuous with no framing penetration. The R-value of the metal is negligible.

Table 4.3.11 – Thermal Properties of Log Home Walls

Log Diameter
U-factor
Heat Capacity (HC)
A
6"
1
0.132
5.19
8”
2
0.102
6.92
10”
3
0.083
8.65
12”
4
0.070
10.37
14
5
0.060
12.10
16”
6
0.053
13.83

This table has U-factors and heat capacity data for log homes Data is provided for logs in six thicknesses ranging from 6 in. to 16 in. If other thermal properties are needed such as density, weight, conductivity, etc., use the procedures in Modeling Constructions in the Nonresidential compliance software and contained in Section 4.6 of this document. Energy Commission approved Compliance Software Programs may adjust the data for interior furring using data from Table 4.3.14 and the procedure from Equation 4-2.

P6559#yIS1

Figure 4.3.11 – Log Home Walls

Assumptions: Calculations are based on ASHRAE series method of calculation, 2009 ASHRAE Handbook of Fundamentals. Values assume a log R-value of R-1.25/inch, an average wall thickness of 90 percent of the log diameter, an interior air film of R-0.68 and an exterior air film of R-0.17. Values do not account for presence of windows or doors. Construction assumes no additional siding or insulation. Heat Capacity is based on a softwood density of 26.6 lb/ft³ and a specific heat of 0.39 Btu/lb-ºF. An exterior air film of R-0.17 and an interior film of R-0.68 are assumed.

Table 4.3.12 – Thermal and Mass Properties of Straw Bale Walls

A
R-value
1
30
U-factor
0.033
Heat Capacity [Btu/ft2 * °F]
6.34

This table has data that may be used for straw bale construction. This is an alternative construction technique used in some rural areas. The technique is not commonly used for production homes.

P6583#yIS1

Figure 4.3.12 – Straw Bale Wall

Assumptions: The construction consists of an exterior film of R-0.17, stucco and lath of R-0.18, the straw bale, interior plaster of R-0.47, and an interior air film of 0.68. Straw bale must have a minimum cross section of 22 inch by 16 inch, and shall have a thermal resistance of R-30, whether stacked so the walls are 22 inch wide or 16 inch wide. Due to the higher resistance to heat flow across the grain of the straws, a bale laid on edge with a nominal 16 inch horizontal thickness has the same R-value (R-30) as a bale laid flat. Framing is assumed to not penetrate more than 25 percent of the way through the straw bale.

Table 4.3.13 – Thermal Properties of Insulating Concrete Forms

Insulation Type
Insulation Thickness Per Side (Total R-Value)
Performance Factor
Flat1
Waffle Grid2
Screen Grid2
Concrete Core Thickness (inches)
4
6
8
10
12
6
8
6
A
B
C
D
E
F
G
H
EPS3
2.0
(15.4)
U-factor
HC
1
0.058 12.20
0.057 17.00
0.056 21.80
0.055 26.60
0.055 31.40
0.047 13.90
0.039 15.87
0.041 12.10
2.25
(18.9)
U-factor
HC
2
0.052 12.22
0.051 17.02
0.051 21.82
0.050 26.62
0.050 31.42
0.043 13.92
0.036 15.89
0.038 12.11
2.5
(19.25)
U-factor
HC
3
0.047 12.24
0.047 17.04
0.046 21.84
0.046 26.64
0.045 31.44
0.040 13.94
0.034 15.91
0.036 12.13
2.625
(20.2)
U-factor
HC
4
0.045 12.25
0.045 17.05
0.044 21.85
0.044 26.65
0.043 31.45
0.038 13.95
0.033 15.92
0.035 12.14
2.75
(21.2)
U-factor
HC
5
0.043 12.26
0.043 17.06
0.042 21.86
0.042 26.66
0.042 31.46
0.037 13.96
0.032 15.92
0.0323 12.15
3.0
(23.1)
U-factor
HC
6
0.040 12.27
0.040 17.07
0.039 21.87
0.039 26.67
0.039 31.47
0.0334 13.98
0.030 15.94
0.031 12.17
3.5
(27.0)
U-factor
HC
7
0.035 12.31
0.034 17.11
0.034 21.91
0.034 26.71
0.034 31.51
0.030 14.01
0.027 15.98
0.028 12.21
4.0
(30.8)
U-factor
HC
8
0.031 12.35
0.030 17.15
0.030 21.95
0.030 26.75
0.030 31.55
0.027 14.05
0.024 16.02
0.025 12.24
XPS
2.0
(20.0)
U-factor
HC
9
0.045 12.29
0.045 17.09
0.045 21.89
0.044 26.69
0.044 31.49
NA
NA
NA
NA
NA
NA
2.5
(25.0)
U-factor
HC
10
0.037 12.35
0.037 17.15
0.036 21.95
0.036 26.75
0.036 31.55
NA
NA
NA
NA
NA
NA
2.625
(26.3)
U-factor
HC
11
0.035 12.36
0.035 17.16
0.035 21.96
0.035 26.76
0.034 31.56
NA
NA
NA
NA
NA
NA
2.75
(27.5)
U-factor
HC
12
0.034 12.38
0.034 17.18
0.033 21.98
0.033 26.78
0.033 31.58
NA
NA
NA
NA
NA
NA
3.0
(30.0)
U-factor
HC
13
0.031 12.41
0.031 17.21
0.031 22.01
0.031 26.81
0.030 31.61
NA
NA
NA
NA
NA
NA
3.5
(35.0)
U-factor
HC
14
0.027 12.46
0.027 17.26
0.027 22.06
0.027 26.86
0.026 31.66
NA
NA
NA
NA
NA
NA
4.0
(40)
U-factor
HC
15
0.024 12.52
0.024 17.32
0.024 22.12
0.023 26.92
0.023 31.72
NA
NA
NA
NA
NA
NA
Polyurethane
1.5
(9.09)
U-factor
HC
16
0.050 12.23
0.049 17.03
0.049 21.83
0.048 26.63
0.048 31.43
NA
NA
NA
NA
NA
NA
2.0
(10.9)
U-factor
HC
17
0.042 12.41
0.042 17.21
0.041 22.01
0.041 26.81
0.041 31.61
NA
NA
NA
NA
NA
NA
4.5
(20.95)
U-factor
HC
18
0.023 12.58
0.023 17.38
0.023 22.18
0.022 26.98
0.022 31.78
NA
NA
NA
NA
NA
NA
Cement/EPS Compound
2.0
(12.0)
U-factor
HC
19
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
0.059 16.49
0.048 18.46
0.052 14.69
3.0
(18.0)

U-factor
HC
20
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
0.043 17.50
0.037 19.47
0.040 15.69
4.0
(24.0)
U-factor
HC
21
NA
NA
NA
NA
NA
NA
NA
NA
NA
NA
0.034 18.51
0.031 20.47
0.032 16.70

Notes:
1. Flat Insulated Concrete Forms utilizes rigid insulation as the form and do not use cement compound as the form.
2. Waffle and screen type Insulated Concrete Forms typically utilize either a cement/EPS compound or EPS insulation as the form. ICF's using the cement/EPS compound do not utilize rigid insulation added to the interior and exterior surfaces.
3. 1.5 lb density EPS insulation at R-3.85 per inch except for the 2.25” insulation thickness which uses 2.0 lb density EPS at R-4.2 per inch.

This table provides thermal performance information for insulating concrete forms.

Insulating Concrete Forms (ICFs) are concrete forming systems that use stay-in-place panels made from a variety of insulating materials for constructing cast-in-place solid concrete walls.  There are three basic types of ICFs: flat wall, waffle-grid and screen-grid. A flat wall system is a wall with uniform thickness just like a conventional poured wall made with plywood or metal forms. Waffle-grid wall systems have a solid concrete wall of varying thickness and look like a breakfast waffle. Screen grid wall systems also known as , “post and beam”, have a perforated concrete wall of varying thickness similar to the waffle type wall systems but with a solid form material between the horizontal and vertical members instead of concrete. The insulating panels for all three ICF types are most commonly made from expanded polystyrene (EPS) and extruded polystyrene (XPS) rigid insulation boards. Plastic or metal cross-ties separate the insulating panels and provide structural integrity during the pour. The ICF system is modular and stackable with interlocking edges. The materials can be delivered as pre-assembled blocks or as planks that require the flanges and web to be assembled during construction.

P7119#yIS1

Figure 4.3.13 – Insulating Concrete Forms

Assumptions: Values in this table were calculated using the one dimensional calculation method documented in 2009 ASHRAE Handbook of Fundamentals. The calculations assume an exterior air film of R-0.17, a 7/8 inch layer of stucco of R-0.18, building paper of R-0.06, an exterior insulating form of varying resistance, a concrete core of varying thickness at R-0.11 per inch, an interior insulating form of varying resistance, and an interior air film of R-0.68. The R-value of the cement/EPC compound is assumed to be R-3.0 per inch, the XPS insulation assumed to be R-5.0 per inch, and the polyurethane assumed to be aged and dried in 1.5 inch, 2.0 inch, and 4.5 inch thickness.

Table 4.3.14 – Effective R-values for Interior or Exterior Insulation Layers

Thickness
Frame Type
R-value of Insulation Installed in Furring Space
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
A
B
C
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
T
U
V
Any
None
1
0.5
1.5
2.5
3.5
4.5
5.5
6.5
7.5
8.5
9.5
10.5
11.5
12.5
13.5
14.5
15.5
16.5
17.5
18.5
19.5
20.5
21.5
0.5"
Wood
2
1.3
1.3
1.9
2.4
2.7
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
Metal
3
0.9
0.9
1.1
1.1
1.2
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
0.75"
Wood
4
1.4
1.4
2.1
2.7
3.1
3.5
3.8
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
Metal
5
1.0
1.0
1.3
1.4
1.5
1.5
1.6
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
1.0"
Wood
6
1.3
1.5
2.2
2.9
3.4
3.9
4.3
4.6
4.9
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
Metal
7
1.0
1.1
1.4
1.6
1.7
1.8
1.8
1.9
1.9
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
1.5"
Wood
8
1.3
1.5
2.4
3.1
3.8
4.4
4.9
5.4
5.8
6.2
6.5
6.8
7.1
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
Metal
9
1.1
1.2
1.6
1.9
2.1
2.2
2.3
2.4
2.5
2.5
2.6
2.6
2.7
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
n.a.
2"
Wood
10
1.4
1.5
2.5
3.3
4.0
4.7
5.3
5.9
6.4
6.9
7.3
7.7
8.1
8.4
8.7
9.0
9.3
n.a.
n.a.
n.a.
n.a.
n.a.
Metal
11
1.1
1.2
1.7
2.1
2.3
2.5
2.7
2.8
2.9
3.0
3.1
3.2
3.2
3.3
3.3
3.4
3.4
n.a.
n.a.
n.a.
n.a.
n.a.
2.5"
Wood
12
1.4
1.5
2.5
3.4
4.2
4.9
5.6
6.3
6.8
7.4
7.9
8.4
8.8
9.2
9.6
10.0
10.3
10.6
10.9
11.2
11.5
n.a.
Metal
13
1.2
1.3
1.8
2.3
2.6
2.8
3.0
3.2
3.3
3.5
3.6
3.6
3.7
3.8
3.9
3.9
4.0
4.0
4.1
4.1
4.1
n.a.
3"
Wood
14
1.4
1.5
2.5
3.5
4.3
5.1
5.8
6.5
7.2
7.8
8.3
8.9
9.4
9.9
10.3
10.7
11.1
11.5
11.9
12.2
12.5
12.9
Metal
15
1.2
1.3
1.9
2.4
2.8
3.1
3.3
3.5
3.7
3.8
4.0
4.1
4.2
4.3
4.4
4.4
4.5
4.6
4.6
4.7
4.7
4.8
3.5"
Wood
16
1.4
1.5
2.6
3.5
4.4
5.2
6.0
6.7
7.4
8.1
8.7
9.3
9.8
10.4
10.9
11.3
11.8
12.2
12.6
13.0
13.4
13.8
Metal
17
1.2
1.3
2.0
2.5
2.9
3.2
3.5
3.8
4.0
4.2
4.3
4.5
4.6
4.7
4.8
4.9
5.0
5.1
5.1
5.2
5.2
5.3
4"
Wood
18
1.4
1.6
2.6
3.6
4.5
5.3
6.1
6.9
7.6
8.3
9.0
9.6
10.2
10.8
11.3
11.9
12.4
12.8
13.3
13.7
14.2
14.6
Metal
19
1.2
1.3
2.0
2.6
3.0
3.4
3.7
4.0
4.2
4.5
4.6
4.8
5.0
5.1
5.2
5.3
5.4
5.5
5.6
5.7
5.8
5.8
4.5"
Wood
20
1.4
1.6
2.6
3.6
4.5
5.4
6.2
7.1
7.8
8.5
9.2
9.9
10.5
11.2
11.7
12.3
12.8
13.3
13.8
14.3
14.8
15.2
Metal
21
1.2
1.3
2.1
2.6
3.1
3.5
3.9
4.2
4.5
4.7
4.9
5.1
5.3
5.4
5.6
5.7
5.8
5.9
6.0
6.1
6.2
6.3
5"
Wood
22
1.4
1.6
2.6
3.6
4.6
5.5
6.3
7.2
8
8.7
9.4
10.1
10.8
11.5
12.1
12.7
13.2
13.8
14.3
14.8
15.3
15.8
Metal
23
1.2
1.4
2.1
2.7
3.2
3.7
4.1
4.4
4.7
5.0
5.2
5.4
5.6
5.8
5.9
6.1
6.2
6.3
6.5
6.6
6.7
6.8
5.5"
Wood
24
1.4
1.6
2.6
3.6
4.6
5.5
6.4
7.3
8.1
8.9
9.6
10.3
11.0
11.7
12.4
13.0
13.6
14.2
14.7
15.3
15.8
16.3
Metal
25
1.3
1.4
2.1
2.8
3.3
3.8
4.2
4.6
4.9
5.2
5.4
5.7
5.9
6.1
6.3
6.4
6.6
6.7
6.8
7.0
7.1
7.2
EIFS
26
0.0
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
10.0
11.0
12.0
13.0
14.0
15.0
16.0
17.0
18.0
19.0
20.0
21.0

Metal Clips

P7866#yIS1

Wood Framing

P7866#yIS2

Figure 4.3.14 – Interior or Exterior Insulation Layers

This table is used in combination with other tables and Equation 4-1 and Equation 4-2 to account for interior furring and continuous insulation added to other constructions.

Assumptions: Data is taken from ASHRAE/IESNA Standard 90.1-2004 All furring thickness values given are actual dimensions. All values include 0.5 inch gypsum board on the inner surface, interior surface resistances not included. The metal furring is 24 inch on center, 24 gauge, Z-type Metal Furring. The wood furring is 24 inch on center, Douglas-Fir Larch Wood Furring, density = 34.9 lb/ft³. Insulation assumed to fill the furring space.

This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2024 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.