Space conditioning systems serving multifamily dwelling units and common use areas shall comply with the applicable requirements of Sections 160.3(a) through 160.3(c).
EXCEPTION to Section 160.3(a)2: Heating or cooling systems exclusively serving dwelling units and common use areas providing shared provisions for living, eating, cooking, or sanitation to dwelling units that would otherwise lack these provisions may instead comply with Section 160.3(a)1.
EXCEPTION to Section 160.3(a)2A: An independent perimeter heating or cooling system may serve more than one zone without individual thermostatic controls if:
EXCEPTION to Section 160.3(a)2Biii: Systems with thermostats that require manual changeover between heating and cooling modes.
EXCEPTION to Section 160.3(a)2Biv: Package terminal air conditioners, package terminal heat pumps, room air conditioners, and room air-conditioner heat pumps.
EXCEPTION to Section 160.3(a)2Diia: Thermostat setback controls are not required in multifamily buildings in areas where the Winter Median of Extremes outdoor air temperature determined in accordance with Section 170.2(c)1C is greater than 32°F.
EXCEPTION to Section 160.3(a)2Diib: Thermostat setup controls are not required in multifamily buildings in areas where the Summer Design Dry Bulb 0.5 percent temperature determined in accordance with Section 170.2(c)1C is less than 100°F.
I. Automatically setup the operating cooling temperature set point by 2°F or more and setback the operating heating temperature set point by 2°F or more; or
II. For multiple zone systems with Direct Digital Controls (DDC) to the zone level, setup the operating cooling temperature setpoint by 0.5°F or more and setback the operating heating temperature setpoint by 0.5°F or more.
EXCEPTION to Section 160.3(a)2Diii: Zones that are only ventilated by a natural ventilation system in accordance with Section 120.1(c)2.
EXCEPTION 1 to Sections 160.3(a)2Di, ii, and iii: Where it can be demonstrated to the satisfaction of the enforcing agency that the system serves an area that must operate continuously.
Exception 2 to Sections 160.3(a)2Di, ii and iii: Systems with full load demands of 2 kW or less, if they have a readily accessible manual shut-off switch.
EXCEPTION 1 to Section 160.3(a)2E: Equipment that serves an area that must operate continuously.
EXCEPTION 2 to Section 160.3(a)2E: Gravity and other nonelectrical equipment that has readily accessible manual damper controls.
EXCEPTION 3 to Section 160.3(a)2E: At combustion air intakes and shaft vents.
EXCEPTION 4 to Section 160.3(a)2E: Where prohibited by other provisions of law.
EXCEPTION to Section 160.3(a)2F: Zones designed to be conditioned continuously.
I. On the thermostat, device, or an adjacent written sign, display instructions to contact appropriate building personnel or an HVAC technician; and
II. In buildings with multiple tenants, the annunciation shall either be within property management offices or in a common space accessible by the property or building manager.
EXCEPTION to Section 160.3(a)2Hviii: FDD algorithms based in Direct Digital Control systems are not required to be certified to the Energy Commission.
EXCEPTION to Section 160.3(a)2J: Systems that must operate continuously.
NOTE: Heating systems are required to have a minimum heating capacity adequate to meet the minimum requirements of the CBC.
EXCEPTION to Section 160.3(b)5Aiia: Portions of the duct system located in conditioned space below the ceiling separating the occupiable space from the attic are not required to be insulated if all of the following conditions are met:
i. The non-insulated portion of the duct system is located entirely inside the building’s thermal envelope as confirmed by visual inspection.
ii. At all locations where non-insulated portions of the duct system penetrate into unconditioned space, the penetration shall be draft stopped compliant with CFC sections 703.1 and 704.1 and air-sealed to the construction materials that are penetrated, using materials compliant with CMC section E502.4.2 to prevent air infiltration into the cavity. All connections in unconditioned space are insulated to a minimum of R-6.0 as confirmed by visual inspection.
EXCEPTION to Section 160.3(b)5A: Ducts and fans integral to a wood heater or fireplace.
For multifamily dwellings with the air-handling unit installed and the ducts connected directly to the air handler, regardless of duct system location:
EXCEPTION 1 to Section 160.3(b)5K: The HERS Rater field verification and HERS Provider data registry requirements of Reference Residential Appendix RA2 and RA3 are not required for multifamily dwelling units in buildings four habitable stories and greater. The installer shall certify that diagnostic testing was performed in accordance with the applicable procedures.
EXCEPTION 2 to Section 160.3(b)5K: Multifamily dwelling units in buildings four habitable stories and greater in Climate Zones 1, 3, 5, and 7.
EXCEPTION to Section 160.3(b)5Li: Systems that cannot conform to the specifications for hole location in Reference Residential Appendix Figure RA3.3-1 shall not be required to provide holes as described in Figure RA3.3-1.
EXCEPTION 1 to Section 160.3(b)5Lii: Standard ducted systems without zoning dampers may comply by meeting the applicable requirements in TABLE 160.3-A or 160.3-B as confirmed by field verification and diagnostic testing in accordance with the procedures in Reference Residential Appendix Sections RA3.1.4.4 and RA3.1.4.5. The design clean-filter pressure drop requirements specified by Section 160.2(b)1Div for the system air filter(s) shall conform to the requirements given in TABLE 160.3-A or 160.3-B.
EXCEPTION 2 to Section 160.3(b)5Lii: Multispeed compressor systems or variable speed compressor systems shall verify airflow (cfm/ton) and fan efficacy (Watt/cfm) for system operation at the maximum compressor speed and the maximum air handler fan speed.
EXCEPTION 3 to Section 160.3(b)5Lii: Gas furnace air-handling units manufactured prior to July 3, 2019 shall comply with a fan efficacy value less than or equal to 0.58 w/cfm as confirmed by field verification and diagnostic testing in accordance with the procedures given in Reference Residential Appendix RA3.3.
EXCEPTION 1 to Section 160.3(b)5Liii: Multispeed or variable speed compressor systems, or single speed compressor systems that utilize the performance compliance approach, shall demonstrate compliance with the airflow (cfm/ton) and fan efficacy (Watt/cfm) requirements of Section 160.3(b)5Liii by operating the system at maximum compressor capacity and system fan speed with all zones calling for conditioning, rather than in every zonal control mode.
EXCEPTION 2 to Section 160.3(b)5Liii: Gas furnace air-handling units manufactured prior to July 3, 2019 shall comply with a fan efficacy value less than or equal to 0.58 w/cfm as confirmed by field verification and diagnostic testing in accordance with the procedures given in Reference Residential Appendix RA3.3.
EXCEPTION 1 to Section 160.3(b)5Liv: Standard ducted systems without zoning dampers may comply by meeting the applicable requirements in TABLE 160.3-A or 160.3-B as confirmed by field verification and diagnostic testing in accordance with the procedures in Reference Residential Appendix Sections RA3.1.4.4 and RA3.1.4.5. The design clean-filter pressure drop requirements specified by Section 160.2(b)1Div for the system air filter(s) shall conform to the requirements given in TABLE 160.3-A or 160.3-B.
EXCEPTION 2 to Section 160.3(b)5Liv: Multispeed compressor systems or variable speed compressor systems shall verify airflow (cfm/ton) and fan efficacy (watt/cfm) for system operation at the maximum compressor speed and the maximum air handler fan speed.
EXCEPTION 1 to Section 160.3(b)5L: The HERS Rater field verification and HERS Provider data registry requirements of Reference Residential Appendix RA2 and RA3 are not required for multifamily dwelling units in buildings four habitable stories and greater. The installer shall certify that diagnostic testing was performed in accordance with the applicable procedures.
EXCEPTION 2 to Section 160.3(b)5L: Multifamily dwelling units in buildings four habitable stories and greater in Climate Zone 1.
Exception to Section 160.3(c)1Aii: Heat pumps refrigerant vapor line shall be installed with a minimum of 0.75 inch thick or R-6.0 insulation. No insulation is required on the refrigerant liquid line.
WHERE:
T = Minimum insulation thickness for material with conductivity K, inches.
PR = Pipe actual outside radius, inches.
t = Insulation thickness from Table 160.3-D, inches.
K = Conductivity of alternate material at the mean rating temperature indicated in Table 160.3-D for the applicable fluid temperature range, in Btu-inch per hour per square foot per °F.
k = The lower value of the conductivity range listed in Table 160.3-D for the applicable fluid temperature range, Btu-inch per hour per square foot per °F.
EXCEPTION 1 to Section 160.3(c)1: Factory-installed piping within space-conditioning equipment certified under Section 110.1 or 110.2.
EXCEPTION 2 to Section 160.3(c)1: Piping that conveys fluids with a design operating temperature range between 60°F and 105°F.
EXCEPTION 3 to Section 160.3(c)1: Where the heat gain or heat loss to or from piping without insulation will not increase building source energy use.
EXCEPTION 4 to Section 160.3(c)1: Piping that penetrates framing members shall not be required to have pipe insulation for the distance of the framing penetration. Metal piping that penetrates metal framing shall use grommets, plugs, wrapping or other insulating material to ensure that no contact is made with the metal framing.
Portions of supply-air ducts that are not in one of these spaces, including ducts buried in concrete slab, shall be insulated to a minimum installed level of R-4.2 or be enclosed in directly conditioned space.
EXCEPTION to Section 160.3(c)2Cid: Ductwork located in occupied space and exposed to view.
I. Outdoors; or
II. In a space directly under a roof that has a U-factor greater than the U-factor of the ceiling, or if the roof does not meet the requirements of Section 170.2(a)1; or
III. In a space directly under a roof that has fixed vents or openings to the outside or unconditioned spaces; or
IV. In an unconditioned crawlspace; or
V. In other unconditioned spaces.
EXCEPTION to Section 160.3(d)1D: Air economizers installed by the HVAC system manufacturer and certified to the Commission as being factory calibrated and tested are exempt from the Functional Testing section of the Air Economizer Controls acceptance test as described in NA7.5.4.2.
Return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend. If the total bending exceeds 90 degrees, one bend shall be a metal elbow. Return grille devices shall be labeled in accordance with the requirements in Section 160.2(b)1Biv to disclose the grille's design airflow rate and a maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in accordance with AHRI Standard 680 for the design airflow rate for the return grille. | ||
System Nominal Cooling Capacity (Ton) * | Return Duct Minimum Nominal Diameter (inch) | Minimum Total Return Filter Grille Nominal Area(inch 2 ) |
1.5 | 16 | 500 |
2.0 | 18 | 600 |
2.5 | 20 | 800 |
* Not applicable to systems with nominal cooling capacity greater than 2.5 tons or less than 1.5 ton. |
Each return duct length shall not exceed 30 feet and shall contain no more than 180 degrees of bend. If the total bending exceeds 90 degrees, one bend shall be a metal elbow. Return grille devices shall be labeled in accordance with the requirements in Section 160.2(b)1Biv to disclose the grille's design airflow rate and a maximum allowable clean-filter pressure drop of 25 Pa (0.1 inches water) for the air filter when tested using ASHRAE Standard 52.2, or as rated in accordance with AHRI Standard 680 for the design airflow rate for the return grille. | |||
System Nominal Cooling Capacity (Ton)* | Return Duct 1 Minimum Nominal Diameter (inch) | Return Duct 2 Minimum Nominal Diameter (inch) | Minimum Total Return Filter Grille Nominal Area (inch2 ) |
1.5 | 12 | 10 | 500 |
2.0 | 14 | 12 | 600 |
2.5 | 14 | 14 | 800 |
3.0 | 16 | 14 | 900 |
3.5 | 16 | 16 | 1000 |
4.0 | 18 | 18 | 1200 |
5.0 | 20 | 20 | 1500 |
* Not applicable to systems with nominal cooling capacity greater than 5.0 tons or less than 1.5 tons. |
Building Status | Applications | Qualifications |
Newly Constructed Buildings | Air handling system and all zones served by the system | Individual systems supplying more than three zones and with design heating or cooling capacity of 300 kBtu /h and larger |
Newly Constructed Buildings | Chilled water plant and all coils and terminal units served by the system | Individual plants supplying more than three zones and with design cooling capacity of 300 kBtu /h (87.9 kW) and larger |
Newly Constructed Buildings | Hot water plant and all coils and terminal units served by the system | Individual plants supplying more than three zones and with design heating capacity of 300 kBtu /h (87.9 kW) and larger |
Additions or Alterations | Zone terminal unit such as VAV box | Where existing zones served by the same air handling, chilled water, or hot water systems that have DDC |
Additions or Alterations | Air handling system or fan coil | Where existing air handling system(s) and fan coil(s) served by the same chilled or hot water plant have DDC |
Additions or Alterations | New air handling system and all new zones served by the system | Individual systems with design heating or cooling capacity of 300 kBtu /h and larger and supplying more than three zones and more than 75 percent of zones are new |
Additions or Alterations | New or upgraded chilled water plant | Where all chillers are new and plant design cooling capacity is 300 kBtu /h (87.9 kW) and larger |
Additions or Alterations | New or upgraded hot water plant | Where all boilers are new and plant design heating capacity is 300 kBtu /h (87.9 kW) and larger |
Fluid Operating Temperature Range (°F) | Insulation Conductivity | Nominal Pipe Diameter (in inches) | ||||||||
Conductivity (in Btu·in /h·ft2 ·°F) | Mean Rating Temperature (°F) | |||||||||
< 1 | 1 to <1.5 | 1.5 to < 4 | 4 to < 8 | 8 and larger | ||||||
Space heating (Steam, Steam Condensate, Refrigerant, Space Heating) | Minimum Pipe Insulation Required (Thickness in inches or R-value) | |||||||||
Above 350 | 0.32-0.34 | 250 | Inches | 4.5 | 5.0 | 5.0 | 5.0 | 5.0 | ||
R-value | R 37 | R 41 | R 37 | R 27 | R 23 | |||||
251-350 | 0.29-0.32 | 200 | Inches | 3.0 | 4.0 | 4.5 | 4.5 | 4.5 | ||
R-value | R 24 | R 34 | R 35 | R 26 | R 22 | |||||
201-250 | 0.27-0.30 | 150 | Inches | 2.5 | 2.5 | 2.5 | 3.0 | 3.0 | ||
R-value | R 21 | R 20 | R 17.5 | R 17 | R 14.5 | |||||
141-200 | 0.25-0.29 | 125 | Inches | 1.5 | 1.5 | 2.0 | 2.0 | 2.0 | ||
R-value | R 11.5 | R 11 | R 14 | R 11 | R 10 | |||||
105-140 | 0.22-0.28 | 100 | Inches | 1.0 | 1.5 | 1.5 | 1.5 | 1.5 | ||
R-value | R 7.7 | R 12.5 | R 11 | R 9 | R 8 | |||||
Fluid Operating Temperature Range (°F) | Insulation Conductivity | Nominal Pipe Diameter (in inches) | ||||||||
Conductivity (in Btu·in /h·ft2 ·°F) | Mean Rating Temperature (°F) | < 1 | 1 to <1.5 | 1.5 to < 4 | 4 to < 8 | 8 and larger | ||||
Space cooling systems (chilled water, refrigerant and brine) | Minimum Pipe Insulation Required (Thickness in inches or R-value)1 | |||||||||
40-60 | 0.21-0.27 | 75 | Inches | 0.75 | 0.75 | 1.0 | 1.0 | 1.0 | ||
R-value | R 6 | R 5 | R 7 | R 6 | R 5 | |||||
Below 40 | 0.20-0.26 | 50 | Inches | 1.0 | 1.5 | 1.5 | 1.5 | 1.5 | ||
R-value | R 8.5 | R 14 | R 12 | R 10 | R 9 | |||||
Footnote to TABLE 160.3-D: 1. These thicknesses are based on energy efficiency considerations only. Issues such as water vapor permeability or surface condensation sometimes require vapor retarders or additional insulation. |
NOTE: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.5, 25402.8, and 25943, Public Resources Code.