Welcome to the New & Improved Reference Ace Beta!

SECTION 110.2 - MANDATORY REQUIREMENTS FOR SPACE-CONDITIONING EQUIPMENT

Certification by Manufacturers. Any space-conditioning equipment listed in this section may be installed only if the manufacturer has certified to the Commission that the equipment complies with all the applicable requirements of this section.

(a) Efficiency. Equipment shall meet the applicable efficiency requirements in TABLE 110.2-A through TABLE 110.2-N subject to the following:

1. If more than one efficiency standard is listed for any equipment in TABLE 110.2-A through TABLE 110.2-N, the equipment shall meet all the applicable standards that are listed; and

2. If more than one test method is listed in TABLE 110.2-A through TABLE 110.2-N, the equipment shall comply with the applicable efficiency standard when tested with each listed test method; and

3. Where equipment serves more than one function, it shall comply with the efficiency standards applicable to each function; and

4. Where a requirement is for equipment rated at its "maximum rated capacity" or "minimum rated capacity," the capacity shall be as provided for and allowed by the controls, during steady-state operation.

EXCEPTION 1 to Section 110.2(a):

EXCEPTION 2 to Section 110.2(a): Positive displacement (air-cooled and water-cooled) chillers with a leaving evaporator fluid temperature higher than 32°F shall show compliance with TABLE 110.2-D when tested or certified with water at standard rating conditions, per the referenced test procedure.

EXCEPTION 3 to Section 110.2(a): Equipment primarily serving refrigerated warehouses or commercial refrigeration.

(b) Controls for Heat Pumps with Supplementary Electric Resistance Heaters.

Heat pumps with supplementary electric resistance heaters shall have controls:

1. That prevent supplementary heater operation when the heating load can be met by the heat pump alone; and

2. In which the cut-on temperature for compression heating is higher than the cut-on temperature for supplementary heating, and the cut-off temperature for compression heating is higher than the cut-off temperature for supplementary heating.

EXCEPTION 1 to Section 110.2(b): The controls may allow supplementary heater operation during:

A. Defrost; and

B. Transient periods such as start-ups and following room thermostat setpoint advance, if the controls provide preferential rate control, intelligent recovery, staging, ramping or another control mechanism designed to preclude the unnecessary operation of supplementary heating.

EXCEPTION 2 to Section 110.2(b): Room air-conditioner heat pumps.

(c) Thermostats.

All heating or cooling systems not controlled by a central energy management control system (EMCS) shall have a setback thermostat.

1. Setback Capabilities. All thermostats shall have a clock mechanism that allows the building occupant to program the temperature setpoints for at least four periods within 24 hours. Thermostats for heat pumps shall meet the requirements of Section 110.2(b).

EXCEPTION to Section 110.2(c) Gravity gas wall heaters, gravity floor heaters, gravity room heaters, noncentral electric heaters, fireplaces or decorative gas appliances, wood stoves, room air conditioners, and room air-conditioner heat pumps.

(d) Gas-Fired and Oil-Fired Furnace Standby Loss Controls.

Gas-fired and oil-fired forced air furnaces with input ratings ≥ 225,000 Btu/hr shall also have an intermittent ignition or interrupted device (IID), and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for furnaces where combustion air is drawn from the conditioned space. All furnaces with input ratings ≥ 225,000 Btu/hr, including electric furnaces, that are not located within the conditioned space shall have jacket losses not exceeding 0.75 percent of the input rating.

(e) Open and Closed -Circuit Cooling Towers.

All open and closed cooling tower installations shall comply with the following:

1. Be equipped with Conductivity or Flow-based Controls that maximize cycles of concentration based on local water quality conditions. Controls shall automate system bleed and chemical feed based on conductivity, or in proportion to metered makeup volume, metered bleed volume, recirculating pump run time, or bleed time. Conductivity controllers shall be installed in accordance with manufacturer’s specifications in order to maximize accuracy.

2. Documentation of Maximum Achievable Cycles of Concentration. Building owners shall document the maximum cycles of concentration based on local water supply as reported annually by the local water supplier, and using the calculator approved by the Energy Commission. The calculator is intended to determine maximum cycles based on a Langelier Saturation Index (LSI) of 2.5 or less. Building owner shall document maximum cycles of concentration on the mechanical compliance form which shall be reviewed and signed by the Professional Engineer (P.E.) of Record.

3. Be equipped with a Flow Meter with an analog output for flow either hardwired or available through a gateway on the makeup water line.

4.  Be equipped with an Overflow Alarm to prevent overflow of the sump in case of makeup water valve failure. Overflow alarm shall send an audible signal or provide an alert via the Energy Management Control System to the tower operator in case of sump overflow.

5. Be equipped with Efficient Drift Eliminators that achieve drift reduction to 0.002 percent of the circulated water volume for counter-flow towers and 0.005 percent for cross-flow towers.

EXCEPTION to Section 110.2(e): Open and closed circuit cooling towers with rated capacity < 150 tons.

(f) Low leakage air-handling units. To qualify as a low leakage air-handling unit for use for meeting the requirements for applicable low leakage air-handling unit compliance credit(s) available in the performance standards set forth in Sections 150.1(b) and 140.1, the manufacturer shall certify to the Energy Commission that the air-handling unit meets the specifications in Reference Joint Appendix JA9.

TABLE 110.2-A AIR CONDITIONERS AND CONDENSING UNITS - MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type
Size Category
Efficiency
Test Procedureb
Air conditioners, air cooled both split system and single package
≥ 65,000 Btu/h and < 135,000 Btu/h
11.2 EERa
14.8 IEERa
AHRI 340/360
Air conditioners, air cooled both split system and single package
≥ 135,000 Btu/h and < 240,000 Btu/h
11.0 EERa
14.2 IEERa
AHRI 340/360
Air conditioners, air cooled both split system and single package
≥ 240,000 Btu/h and < 760,000 Btu/h
10.0 EERa
13.2 IEERa
AHRI 340/360
Air conditioners, air cooled both split system and single package
≥ 760,000 Btu/h
9.7 EERa
12.5 IEERa
AHRI 340/360
Air conditioners, water cooled
≥ 65,000 Btu/h and < 135,000 Btu/h
12.1 EERa
13.9 IEERa
AHRI 340/360
Air conditioners, water cooled
≥135,000 Btu/h and < 240,000 Btu/h
12.5 EERa
13.9 IEERa
AHRI 340/360
Air conditioners, water cooled
≥240,000 Btu/h and < 760,000 Btu/h
12.4 EERa
13.6 IEERa
AHRI 340/360
Air conditioners, water cooled
≥ 760,000 Btu/h
12.2EERa
13.5 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled
≥65,000 Btu/h and < 135,000 Btu/h
12.1 EERa
12.3 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled
≥ 135,000 Btu/h and < 240,000 Btu/h
12.0 EERa
12.2 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled
≥240,000 Btu/h and < 760,000 Btu/h
11.9 EERa
12.1 IEERa
AHRI 340/360
Air conditioners, evaporatively cooled
≥ 760,000 Btu/h
11.7 EERa
11.9 IEERa
AHRI 340/360
Condensing units, air cooled
≥ 135,000 Btu/h
10.5 EER
11.8 IEER
AHRI 365
Condensing units, water cooled
≥ 135,000 Btu/h
13.5 EER
14.0 IEER
AHRI 365
Condensing units, evaporatively cooled
≥ 135,000 Btu/h
13.5 EER
14.0 IEER
AHRI 365
a Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat.
b Applicable test procedure and reference year are provided under the definitions.

TABLE 110.2-B HEAT PUMPS, MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type
Size Category
Rating Condition
Efficiencya
Test Procedureb
Air Cooled (Cooling Mode), both split system and single package
≥ 65,000 Btu/h and
< 135,000 Btu/h
11.0 EER
14.1 IEER
AHRI 340/360
Air Cooled (Cooling Mode), both split system and single package
≥ 135,000 Btu/h and < 240,000 Btu/h
10.6 EER
13.5 IEER
AHRI 340/360
Air Cooled (Cooling Mode), both split system and single package
≥ 240,000 Btu/h
9.5 EER
12.5 IEER
AHRI 340/360
Water source (cooling mode)
≥ 65,000 Btu/h and
< 135,000 Btu/h
86ºF entering water
13.0 EER
ISO-13256-1
Groundwater source (cooling mode)
< 135,000 Btu/h
59ºF entering water
18.0 EER
ISO-13256-1
Ground source (cooling mode)
< 135,000 Btu/h
77ºF entering water
14.1 EER
ISO-13256-1
Water source water-to-water (cooling mode)
< 135,000 Btu/h
86ºF entering water
10.6 EER
ISO-13256-2
Groundwater source water-to-water (cooling mode)
< 135,000 Btu/h
59ºF entering water
16.3 EER
ISO-13256-2
Ground source brine-to-water (cooling mode)
< 135,000 Btu/h
77ºF entering water
12.1 EER
ISO-13256-2
Air Cooled (Heating Mode) Split system and single package
≥ 65,000 Btu/h and
< 135,000 Btu/h
(cooling capacity)
47° F db/43° F wb
outdoor air
3.4 COP
AHRI 340/360
Air Cooled (Heating Mode) Split system and single package
≥ 65,000 Btu/h and
< 135,000 Btu/h
(cooling capacity)
17° F db/15° F wb
outdoor air
2.25 COP
AHRI 340/360
Air Cooled (Heating Mode) Split system and single package
≥ 135,000 Btu/h and < 240,000 Btu/h
47° F db/43° F wb
outdoor air
3.3 COP
AHRI 340/360
Air Cooled (Heating Mode) Split system and single package
≥ 240,000 Btu/h and < 760,000 Btu/h
47° F db/43° F wb outdoor air
3.2 COP
AHRI 340/360
Air Cooled (Heating Mode) Split system and single package
≥ 135,000 Btu/h (cooling capacity)
17° F db/15° F wb
outdoor air
2.05 COP
AHRI 340/360
Water source (heating mode)
< 135,000 Btu/h (cooling capacity)
68ºF entering water
4.3 COP
ISO-13256-1
Water source (heating mode)
≥ 135,000 Btu/h and < 240,000 Btu/h
68ºF entering water
2.90 COP
ISO-13256-1
Groundwater source (heating mode)
< 135,000 Btu/h
(cooling capacity)
50ºF entering water
3.7 COP
ISO-13256-1
Ground source (heating mode)
< 135,000 Btu/h
(cooling capacity)
32ºF entering water
3.2 COP
ISO-13256-1
Water source water-to-water (heating mode)
< 135,000 Btu/h
(cooling capacity)
68ºF entering water
3.7 COP
ISO-13256-2
Groundwater source water-to-water (heating mode)
< 135,000 Btu/h
(cooling capacity)
50ºF entering water
3.1 COP
ISO-13256-2
Ground source brine-to-water (heating mode)
< 135,000 Btu/h
(cooling capacity)
32ºF entering water
2.5 COP
ISO-13256-2
a Deduct 0.2 from the required EERs and IEERs for units with a heating section other than electric resistance heat.
b Applicable test procedure and reference year are provided under the definitions.

TABLE 110.2-C AIR-COOLED GAS-ENGINE HEAT PUMPS

Equipment Type
Size Category
Subcategory or Rating Condition
Efficiency
Test Procedure a
Air-Cooled Gas-Engine Heat Pump (Cooling Mode)
All Capacities
95° F db
Outdoor Air
0.60 COP
ANSI Z21.40.4A
Air-Cooled Gas-Engine Heat Pump (Heating Mode)
All Capacities
47° F db/43° F wb
Outdoor Air
0.72 COP
ANSI Z21.40.4A
a Applicable test procedure and reference year are provided under the definitions.





TABLE 110.2-D WATER CHILLING PACKAGES – MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type
Size Category
Path A Efficiencya,b
Path B Efficiencya,b
Test Procedurec
Air Cooled, With Condenser Electrically Operated
< 150 Tons
≥ 10.100 EER
≥ 13.700 IPLV
≥ 9.700 EER
≥15.800 IPLV
AHRI 550/590
Air Cooled, With Condenser Electrically Operated
≥ 150 Tons
≥ 10.100 EER
≥ 14.000 IPLV
≥ 9.700 EER
≥16.100 IPLV
AHRI 50/590
Air Cooled, Without Condenser Electrically Operated
All Capacities
Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements.
Air-cooled chillers without condensers must be rated with matching condensers and comply with the air-cooled chiller efficiency requirements.
AHRI 550/590
Water Cooled, Electrically Operated, Reciprocating
All Capacities
Reciprocating units must comply with the water-cooled positive displacement efficiency requirements.
Reciprocating units must comply with the water-cooled positive displacement efficiency requirements.
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement
< 75 Tons
≤0.750kW/ton
≤ 0.600 IPLV
≤ 0.780 kW/ton
≤ 0.500 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement
≥ 75 tons and < 150 tons
≤ 0.720 kW/ton
≤ 0.560 IPLV
≤ 0.750 kW/ton
≤ 0.490 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement
≥ 150 tons and < 300 tons
≤ 0.660 kW/ton
≤ 0.540 IPLV
≤ 0.680 kW/ton
≤ 0.440 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement
≥ 300 Tons and < 600 tons
≤ 0.610kW/ton
≤ 0.520 IPLV
≤ 0.625 kW/ton
≤ 0.410 IPLV
AHRI 550/590
Water Cooled, Electrically Operated Positive Displacement
≥ 600 tons
≤ 0.560 kW/ton
≤ 0.500 IPLV
≤ 0.585 kW/ton
≤ 0.380 IPLV
AHRI 550/590
Water Cooled, Electrically Operated, Centrifugal
< 150 Tons
≤ 0.610 kW/ton
≤ 0.550IPLV
≤ 0.695 kW/ton
≤ 0.440 IPLV
AHRI 550/590
Water Cooled, Electrically Operated, Centrifugal
≥ 150 tons and < 300 tons
≤ 0.610 kW/ton
≤ 0.550 IPLV
≤ 0.635 kW/ton
≤ 0.400 IPLV
AHRI 550/590
Water Cooled, Electrically Operated, Centrifugal
≥ 300 tons and < 400 tons
≤ 0.560 kW/ton
≤ 0.520 IPLV
≤ 0.595 kW/ton
≤ 0.390 IPLV
AHRI 550/590
Water Cooled, Electrically Operated, Centrifugal
≥ 400 tons and < 600 tons
≤ 0.560 kW/ton
≤ 0.500 IPLV
≤ 0.585 kW/ton
≤ 0.380 IPLV
AHRI 550/590
Water Cooled, Electrically Operated, Centrifugal
≥ 600 tons
≤ 0.560 kW/ton
≤ 0.500 IPLV
≤ 0.585 kW/ton
≤ 0.380 IPLV
AHRI 550/590
Air Cooled Absorption, Single Effect
All Capacities
≥0.600 COP
N.A.d
AHRI 560
Water Cooled Absorption, Single Effect
All Capacities
≥ 0.700 COP
N.A.d
AHRI 560
Absorption Double Effect, Indirect-Fired
All Capacities
≥ 1.000 COP
≥ 1.050 IPLV
N.A.d
AHRI 560
Absorption Double Effect, Direct-Fired
All Capacities
≥ 1.000 COP
≥1.000 IPLV
N.A.d
AHRI 560
Water Cooled Gas Engine Driven Chiller
All Capacities
≥ 1.2 COP
≥ 2.0 IPLV
N.A.d
ANSI Z21.40.4A
a No requirements for:
• Centrifugal chillers with design leaving evaporator temperature < 36°F; or
• Positive displacement chillers with design leaving fluid temperature ≤ 32°F; or
• Absorption chillers with design leaving fluid temperature < 40°F.
b Must meet the minimum requirements of Path A or Path B. However, both the full load (COP) and IPLV must be met to fulfill the requirements of the applicable Path.
c See Section 100.1 for definitions.
d N.A. means not applicable.

TABLE 110.2-E PACKAGED TERMINAL AIR CONDITIONERS AND PACKAGED TERMINAL HEAT PUMPS –MINIMUM EFFICIENCY REQUIREMENTS

Equipment Type
Size Category (Input)
Subcategory or Rating Condition
Efficiency
Test Procedurec
PTAC (Cooling mode) Newly constructed or newly conditioned buildings or additions
All Capacities
95°F db Outdoor Air
14.0 - (0.300 × Cap/1000)a EER
AHRI 310/380
PTAC (Cooling mode) Replacements b
All Capacities
95°F db Outdoor Air
10.9 - (0.213 × Cap/1000)a EER
AHRI 310/380
PTHP (Cooling mode) Newly constructed or newly conditioned buildings or additions
All Capacities
95°F db Outdoor Air
14.0 - (0.300 × Cap/1000)a EER
AHRI 310/380
PTHP (Cooling mode) Replacements b
All Capacities
95°F db Outdoor Air
10.8 - (0.213 × Cap/1000)a EER
AHRI 310/380
PTHP (Heating Mode) Newly constructed or newly conditioned buildings or additions
All Capacities
-
3.7 - (0.052 × Cap/1000)a COP
AHRI 310/380
PTHP (Heating mode) Replacements b
All Capacities
-
2.9 - (0.026 × Cap/1000)a COP
AHRI 310/380
SPVAC (Cooling Mode)
<65,000 Btu/h
95°F db / 75°F wb
Outdoor Air
11.0 EER
AHRI 390
SPVAC (Cooling Mode)
≥65,000 Btu/h and
<135,000 Btu/h
95°F db / 75°F wb
Outdoor Air
10.0 EER
AHRI 390
SPVAC (Cooling Mode)
≥135,000 Btu/h and
<240,000 Btu/h
95°F db / 75°F wb
Outdoor Air
10.0 EER
AHRI 390
SPVHP (Cooling Mode)
<65,000 Btu/h
95°F db / 75°F wb
Outdoor Air
11.0 EER
AHRI 390
SPVHP (Cooling Mode)
≥65,000 Btu/h and
<135,000 Btu/h
95°F db / 75°F wb
Outdoor Air
10.0 EER
AHRI 390
SPVHP (Cooling Mode)
≥135,000 Btu/h and
<240,000 Btu/h
95°F db / 75°F wb
Outdoor Air
10.0 EER
AHRI 390
SPVHP (Heating Mode)
<65,000 Btu/h
47°F db / 43°F wb
Outdoor Air
3.3 COP
AHRI 390
SPVHP (Heating Mode)
≥65,000 Btu/h and
<135,000 Btu/h
47°F db / 43°F wb
Outdoor Air
3.0 COP
AHRI 390
SPVHP (Heating Mode)
≥135,000 Btu/h and
<240,000 Btu/h
47°F db / 43°F wb
Outdoor Air
3.0 COP
AHRI 390
aCap means the rated cooling capacity of the product in Btu/h. If the unit’s capacity is less than 7000 Btu/h, use 7000 Btu/h in the calculation. If the unit’s capacity is greater than 15,000 Btu/h, use 15,000 Btu/h in the calculation.
bReplacement units must be factory labeled as follows: "MANUFACTURED FOR REPLACEMENT APPLICATIONS ONLY; NOT TO BE INSTALLED IN NEWLY CONSTRUCTED BUILDINGS." Replacement efficiencies apply only to units with existing sleeves less than 16 inches high or less than 42 inch wide and having a cross-sectional area less than 670 square inches.
cApplicable test procedure and reference year are provided under the definitions.

TABLE 110.2-F PERFORMANCE REQUIREMENTS FOR HEAT REJECTION EQUIPMENT

Equipment Type
Total System Heat Rejection Capacity at Rated Conditions
Subcategory or Rating Condition
Performance Required ,a ,b, c, d
Test Proceduree
Propeller or axial fan Open-circuit cooling towers
All
95°F entering water 85°F leaving water 75°F entering air wb
≥ 42.1 gpm /hp
CTI ATC-105 and
CTI STD-201 RS
Centrifugal fan Open-circuit cooling towers
All
95°F entering water
85°F leaving water
75°F entering air wb
≥ 20.0 gpm /hp
CTI ATC-105 and
CTI STD-201 RS
Propeller or axial fan closed-circuit cooling towers
All
102°F entering water
90°F leaving water
75°F entering air wb
≥ 16.1 gpm /hp
CTI ATC-105S and
CTI STD-201 RS
Centrifugal fan closed-circuit cooling towers
All
102°F entering water
90°F leaving water
75°F entering air wb
≥ 7.0 gpm /hp
CTI ATC-105S and
CTI STD-201 RS
Propeller or axial fan evaporative condensers
All
R-448A test fluid 165⁰F entering gas temp
105⁰F condensing temp
75⁰F entering air wb
≥ 157,000 Btu/h • hp
CTI ATC-106
Propeller or axial fan evaporative condensers
All
Ammonia test fluid
140⁰F entering gas temp
96.3⁰F condensing temp
75⁰F entering air wb
≥ 134,000 Btu/h • hp
CTI ATC-106
Centrifugal fan evaporative condensers
All
R-448A test fluid
165⁰F entering gas temp
105⁰F condensing temp
75⁰F entering air wb
≥ 135,000 Btu/h • hp
CTI ATC-106
Centrifugal fan evaporative condensers
All
Ammonia test fluid
140⁰F entering gas temp
96.3⁰F condensing temp
75⁰F entering air wb
≥ 110,000 Btu/h • hp
CTI ATC-106
Air cooled condensers
All
125°F condensing temperature
190°F entering gas temperature
15°F subcooling
95°F entering drybulb
≥ 176,000 Btu/h · hp
AHRI 460
Propeller or axial fan dry coolers (air-cooled fluid coolers)
All
115°F entering water
105°F leaving water
95°F entering air db
> 4.5 gpm /hp
CTI ATC-105DS
a For purposes of this table, open-circuit cooling tower performance is defined as the water flow rating of the tower at the given rated conditions divided by the fan motor nameplate power.
b For purposes of this table, closed-circuit cooling tower performance is defined as the process water flow rating of the tower at the given rated conditions divided by the sum of the fan motor nameplate rated power and the integral spray pump motor nameplate power.
c For purposes of this table dry cooler performance is defined as the process water flow rating of the unit at the given thermal rating condition divided by the total fan motor nameplate power of the unit and air-cooled condenser performance is defined as the heat rejected from the refrigerant divided by the fan motor nameplate power of the unit.
d Open cooling towers shall be tested using the test procedures in CTI ATC-105. Performance of factory assembled open cooling towers shall be either certified as base models as specified in CTI STD-201 or verified by testing in the field by a CTI approved testing agency. Open factory assembled cooling towers with custom options added to a CTI certified base model for the purpose of safe maintenance or to reduce environmental or noise impact shall be rated at 90 percent of the CTI certified performance of the associated base model or at the manufacturer’s stated performance, whichever is less. Base models of open factory assembled cooling towers are open cooling towers configured in exact accordance with the Data of Record submitted to CTI as specified by CTI STD-201. There are no certification requirements for field erected cooling towers.
e Applicable test procedure and reference year are provided under the definitions. For refrigerated warehouses or commercial refrigeration applications, condensers shall comply with requirements specified by Section 120.6(a) or Section 120.6(b) .

TABLE 110.2-G Electrically Operated Variable Refrigerant Flow (VRF) Air Conditioners Minimum Efficiency Requirements

Equipment Type
Size Category
Heating Section Type
Sub-Category or Rating Condition
Minimum Efficiency
Test Procedure a
VRF Air Conditioners,
Air Cooled
<65,000 Btu/h
All
VRF Multi-split System
13.0 SEER
AHRI 1230
VRF Air Conditioners,
Air Cooled
≥65,000 Btu/h and <135,000 Btu/h
Electric Resistance (or none)
VRF Multi-split System
11.2 EER 15.5 IEERb
AHRI 1230
VRF Air Conditioners,
Air Cooled
≥135,000 Btu/h and <240,000 Btu/h
Electric Resistance (or none)
VRF Multi-split System
11.0 EER 14.9 IEERb
AHRI 1230
VRF Air Conditioners,
Air Cooled
≥240,000 Btu/h
Electric Resistance (or none)
VRF Multi-split System
10.0 EER 13.9 IEERb
AHRI 1230
a Applicable test procedure and reference year are provided under the definitions.
b IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures.

TABLE 110.2-H Electrically Operated Variable Refrigerant Flow Air-to-Air and Applied Heat Pumps - Minimum Efficiency Requirements

Equipment Type
Size Category
Heating Section Type
Sub-Category or Rating Condition
Minimum Efficiency
Test Procedure b
VRF Air Cooled, (cooling mode)
<65,000 Btu/h
All
VRF Multi-split System
13.0 SEER
AHRI 1230
VRF Air Cooled, (cooling mode)
≥65,000 Btu/h and <135,000 Btu/h
Electric Resistance (or none)
VRF Multi-split Systema
11.0 EER 14.6 IEERc
AHRI 1230
VRF Air Cooled, (cooling mode)
≥135,000 Btu/h and <240,000 Btu/h
Electric Resistance (or none)
VRF Multi-split Systema
10.6 EER 13.9 IEERc
AHRI 1230
VRF Air Cooled, (cooling mode)
≥240,000 Btu/h
Electric Resistance (or none)
VRF Multi-split Systema
9.5 EER 12.7 IEER c
AHRI 1230
VRF Water source (cooling mode)
<65,000 Btu/h
All
VRF Multi-split systemsa
86ºF entering water
12.0 EER 16.0 IEER c
AHRI 1230
VRF Water source (cooling mode)
≥65,000 Btu/h and <135,000 Btu/h
All
VRF Multi-split Systema
86ºF entering water
12.0 EER 16.0 IEER c
AHRI 1230
VRF Water source (cooling mode)
≥135,000 Btu/h and < 240,000
All
VRF Multi-split Systema
86ºF entering water
10.0 EER 14.0 IEER c
AHRI 1230
VRF Water source (cooling mode)
≥ 240,000 Btu/h
All
VRF Multi-split Systema
86 o F entering water
10.0 EER 12.0 IEER
AHRI 1230
VRF Groundwater source (cooling mode)
<135,000 Btu/h
All
VRF Multi-split Systema
59ºF entering water
16.2 EER
AHRI 1230
VRF Groundwater source (cooling mode)
≥ 135,000 Btu/h
All
VRF Multi-split Systema
59ºF entering water
13.8 EER
AHRI 1230
VRF Ground source (cooling mode)
<135,000 Btu/h
All
VRF Multi-split Systema
77ºF entering water
13.4 EER
AHRI 1230
VRF Ground source (cooling mode)
≥ 135,000 Btu/h
All
VRF Multi-split Systema
77ºF entering water
11.0 EER
AHRI 1230
VRF Air Cooled (heating mode)
<65,000 Btu/h (cooling capacity)
---
VRF Multi-split System
7.7 HSPF
AHRI 1230
VRF Air Cooled (heating mode)
≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)
---
VRF Multi-split system 47ºF db/ 43ºF wb outdoor air
3.3 COP
AHRI 1230
VRF Air Cooled (heating mode)
≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)
---
VRF Multi-split system 17ºF db/15ºF wb outdoor air
2.25 COP
AHRI 1230
VRF Air Cooled (heating mode)
≥135,000 Btu/h (cooling capacity)
---
VRF Multi-split system 47ºF db/43ºF wb outdoor air
3.2 COP
AHRI 1230
VRF Air Cooled (heating mode)
≥135,000 Btu/h (cooling capacity)
---
VRF Multi-split system 17ºF db /15ºF wb outdoor air
2.05 COP
AHRI 1230
VRF Water source (heating mode)
< 65,000 Btu/h (cooling capacity)
---
VRF Multi-split System 68 o F entering water
4.3 COP
AHRI 1230
VRF Water source (heating mode)
≥65,000 Btu/h and <135,000 Btu/h (cooling capacity)
---
VRF Multi-split System 68ºF entering water
4.3 COP
AHRI 1230
VRF Water source (heating mode)
≥135,000 Btu/h and < 240,000 Btu/h (cooling capacity)
---
VRF Multi-split System 68ºF entering water
4.0 COP
AHRI 1230
VRF Water source (heating mode)
≥ 240,000 Btu/h (cooling capacity)
---
VRF Multi-split System 68 o F entering water
3.9 COP
AHRI 1230
VRF Groundwater source (heating mode)
<135,000 Btu/h (cooling capacity)
---
VRF Multi-split System 50ºF entering water
3.6 COP
AHRI 1230
VRF Groundwater source (heating mode)
≥135,000 Btu/h (cooling capacity)
---
VRF Multi-split System 50ºF entering water
3.3 COP
AHRI 1230
VRF Ground source (heating mode)
<135,000 Btu/h (cooling capacity)
---
VRF Multi-split System 32ºF entering water
3.1 COP
AHRI 1230
VRF Ground source (heating mode)
≥135,000 Btu/h (cooling capacity)
---
VRF Multi-split System 32ºF entering water
2.8 COP
AHRI 1230
Footnote for Table 110.2H
a Deduct 0.2 from the required EERs and IEERs for Variable Refrigerant Flow (VRF) Multi-split system units with a heating recovery section.
b Applicable test procedure and reference year are provided under the definitions.
c IEERs are only applicable to equipment with capacity control as specified by AHRI 1230 test procedures

TABLE 110.2-I Warm-Air Furnaces and Combination Warm-Air Furnaces/Air-Conditioning Units, Warm-Air Duct Furnaces, and Unit Heaters

Equipment Type
Size Category (Input)
Subcategory or Rating Conditionb
Minimum Efficiencyd,e
Test Procedurea
Warm-Air Furnace, Gas-Fired
≥ 225,000 Btu/h
Maximum Capacityb
81% Et
Section 2.39, Thermal Efficiency, ANSI Z21.47
Warm-Air Furnace, oil-Fired
≥ 225,000 Btu/h
Maximum Capacityb
82% Et
Section 42, Combustion, UL 727
Warm-Air Duct Furnaces, Gas-Fired
All Capacities
Maximum Capacityb
80% Ec
Section 2.10, Efficiency, ANSI Z83.8
Warm-Air Unit Heaters, Gas-Fired
All Capacities
Maximum Capacityb
80% Ec
Section 2.10, Efficiency, ANSI Z83.8
Warm-Air Unit Heaters, Oil-Fired
All Capacities
Maximum Capacityb
81% Ec
Section 40, Combustion, UL 731
a Applicable test procedure and reference year are provided under the definitions.
b Compliance of multiple firing rate units shall be at maximum firing rate.
c Combustion units not covered by the U.S. Department of Energy Code of Federal Regulations 10 CFR 430 (3-phase power or cooling capacity greater than or equal to 19 kW) may comply with either rating.
d Et= thermal efficiency. Units must also include an interrupted or intermittent ignition device (IID), have jacket losses not exceeding 0.75% of the input rating, and have either power venting or a flue damper. A vent damper is an acceptable alternative to a flue damper for those furnaces where combustion air is drawn from the conditioned space.
e Ec = combustion efficiency (100% less flue losses). See test procedure for detailed discussion.
f As of August 8, 2008, according to the Energy Policy Act of 2005, units must also include interrupted or intermittent ignition device (IID) and have either power venting or an automatic flue damper.

TABLE 110.2-J Gas- and Oil-Fired Boilers, Minimum Efficiency Requirements

Equipment Type
Sub Category
Size Category (Input)
Minimum Efficiency b,c Before 1/10/2023
Minimum Efficiency b,c On or After 1/10/2023
Test Procedure a
Boiler, hot water
Gas-Fired
< 300,000 Btu/h
82% AFUE
82% AFUE
DOE 10 CFR Part 430
Boiler, hot water
Gas-Fired
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h d
80% Et
84% Et
DOE 10 CFR Part 431
Boiler, hot water
Gas-Fired
> 2,500,000 Btu/h and
<10,000,000 Btu/h
82% Ec
85% Ec
DOE 10 CFR Part 431
Boiler, hot water
Gas-Fired
>10,000,000 Btu/h
82% Ec
82% Ec
DOE 10 CFR Part 431
Boiler, hot water
Oil-Fired e
< 300,000 Btu/h
84% AFUE
84% AFUE
DOE 10 CFR Part 430
Boiler, hot water
Oil-Fired e
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h d
82% Et
87% Et
DOE 10 CFR Part 431
Boiler, hot water
Oil-Fired e
> 2,500,000 Btu/h and
<10,000,000 Btu/h
84% Ec
88% Ec
DOE 10 CFR Part 431
Boiler, hot water
Oil-Fired e
>10,000,000 Btu/h
84% Ec
84% Ec
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired
< 300,000 Btu/h
80% AFUE
80% AFUE
DOE 10 CFR Part 430
Boiler, steam
Gas-Fired
>300,000 Btu/h and
<2,500,000 Btu/h
81% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired
>2,500,000 Btu/h and
<10,000,000 Btu /h
82% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired
>10,000,000 Btu/h
79% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired all, except natural draft f
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h d
79% Et
81% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired all, except natural draft f
> 2,500,000 Btu/h and
<10,000,000 Btu/h
79% Et
82% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired all, except natural draft f
>10,000,000 Btu/h
79% Et
79% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired, natural draft f
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h d
77% Et
81% Et
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired, natural draft f
> 2,500,000 Btu/h and
<10,000,000 Btu/h
77% Et
82% t
DOE 10 CFR Part 431
Boiler, steam
Gas-Fired, natural draft f
>10,000,000 Btu/h
77% Et
79% Et
DOE 10 CFR Part 431
Boiler, steam
Oil-Fired e
< 300,000 Btu/h
82% AFUE
82% AFUE
DOE 10 CFR Part 430
Boiler, steam
Oil-Fired e
≥ 300,000 Btu/h and
≤ 2,500,000 Btu/h d
81% Et
84% Et
DOE 10 CFR Part 431
Boiler, steam
Oil-Fired e
> 2,500,000 Btu/h and
<10,000,000 Btu/h
81% Et
85% Et
DOE 10 CFR Part 431
Boiler, steam
Oil-Fired e
10,000,000 Btu/h
81% Et
81% Et
DOE 10 CFR Part 431
Footnote for Table -110-2J:
a Applicable test procedure and reference year are provided under the definitions.
b Ec = combustion efficiency (100% less flue losses).See test procedure for detailed information.
c Et= thermal efficiency. See test procedure for detailed information.
d Maximum capacity - maximum rating per the certified unit capacity.
e Included oil-fired (residual).
f Federal efficiency standards do not distinguish between natural draft gas-fired steam boilers and other gas-fired steam boilers on or after January 10, 2023.

TABLE 110.2-K DX-DOAS Units, Single-Package and Remote Condenser – Minimum Efficiency Requirements

Equipment Type
Energy Recovery
Subcategory or Rating Condition
Minimum Efficiency
Test Procedure a
Air cooled
(dehumidification mode)
Without energy recovery
4.0 ISMRE
AHRI 920
Air source heat pumps
(dehumidification mode)
Without energy recovery
4.0 ISMRE
AHRI 920
Water cooled
(dehumidification mode)
Without energy recovery
Cooling Tower Condenser Water
4.9 ISMRE
AHRI 920
Water cooled
(dehumidification mode)
Without energy recovery
Chilled Water
6.0 ISMRE
AHRI 920
Water source heat pump
(dehumidification mode)
Without energy recovery
Ground source, closed loop
4.8 ISMRE
AHRI 920
Water source heat pump
(dehumidification mode)
Without energy recovery
Ground-water source
5.0 ISMRE
AHRI 920
Water source heat pump
(dehumidification mode)
Without energy recovery
Water source
4.0 ISMRE
AHRI 920
Air source heat pumps
(heating mode)
Without energy recovery
2.7 ISCOP
AHRI 920
Water source heat pump
(heating mode)
Without energy recovery
Ground source, closed loop
2.0 ISCOP
AHRI 920
Water source heat pump
(heating mode)
Without energy recovery
Ground-water source
3.2 ISCOP
AHRI 920
Water source heat pump
(heating mode)
Without energy recovery
Water source
3.5 ISCOP
AHRI 920
Air cooled
(dehumidification mode)
With energy recovery
5.2 ISMRE
AHRI 920
Air source heat pumps
(dehumidification mode)
With energy recovery
5.2 ISMRE
AHRI 920
Water cooled
(dehumidification mode)
With energy recovery
Cooling Tower Condenser Water
5.3 ISMRE
AHRI 920
Water cooled
(dehumidification mode)
With energy recovery
Chilled Water
6.6 ISMRE
AHRI 920
Water source heat pump
(dehumidification mode)
With energy recovery
Ground source, closed loop
5.2 ISMRE
AHRI 920
Water source heat pump
(dehumidification mode)
With energy recovery
Ground-water source
5.8 ISMRE
AHRI 920
Water source heat pump
(dehumidification mode)
With energy recovery
Water source
4.8 ISMRE
AHRI 920
Air source heat pumps
(heating mode)
With energy recovery
3.3 ISCOP
AHRI 920
Water source heat pump
(heating mode)
With energy recovery
Ground source, closed loop
3.8 ISCOP
AHRI 920
Water source heat pump
(heating mode)
With energy recovery
Ground-water source
4.0 ISCOP
AHRI 920
Water source heat pump
(heating mode)
With energy recovery
Water source
4.8 ISCOP
AHRI 920
Footnote to TABLE 110.2-K:
a Applicable test procedure and reference year are provided under the definitions.

TABLE 110.2-L Floor-Mounted Air Conditioners and Condensing Units Serving Computer Rooms – Minimum Efficiency Requirements

Equipment TypeStandard ModelNet Sensible Cooling CapacityMinimum Net Sensible COPRating Conditions Return air (dry bulb/dew point)Test Procedurea
Air CooledDownflow< 80,000 Btu/h2.7085°F / 52°F (Class 2)AHRI 1360
Air CooledDownflow≥ 80,000 Btu/h and
< 295,000 Btu/h
2.5885°F / 52°F (Class 2)AHRI 1360
Air CooledDownflow≥ 295,000 Btu/h2.3685°F / 52°F (Class 2)AHRI 1360
Air CooledUpflow - ducted< 80,000 Btu/h2.6785°F / 52°F (Class 2)AHRI 1360
Air CooledUpflow - ducted≥ 80,000 Btu/h and
< 295,000 Btu/h
2.5585°F / 52°F (Class 2)AHRI 1360
Air CooledUpflow - ducted≥ 295,000 Btu/h2.3385°F / 52°F (Class 2)AHRI 1360
Air CooledUpflow - nonducted< 65,000 Btu/h2.1675°F / 52°F (Class 1)AHRI 1360
Air CooledUpflow - nonducted≥ 65,000 Btu/h and
< 240,000 Btu/h
2.0475°F / 52°F (Class 1)AHRI 1360
Air CooledUpflow - nonducted≥ 240,000 Btu/h1.8975°F / 52°F (Class 1)AHRI 1360
Air CooledHorizontal< 65,000 Btu/h2.6595°F / 52°F (Class 3)AHRI 1360
Air CooledHorizontal≥ 65,000 Btu/h and
< 240,000 Btu/h
2.5595°F / 52°F (Class 3)AHRI 1360
Air CooledHorizontal≥ 240,000 Btu/h2.4795°F / 52°F (Class 3)AHRI 1360
Air cooled with fluid economizerDownflow< 80,000 Btu/h2.7085°F / 52°F (Class 2)AHRI 1360
Air cooled with fluid economizerDownflow≥ 80,000 Btu/h and
< 295,000 Btu/h
2.5885°F / 52°F (Class 2)AHRI 1360
Air cooled with fluid economizerDownflow≥ 295,000 Btu/h2.3685°F / 52°F (Class 2)AHRI 1360
Air cooled with fluid economizerUpflow - ducted< 80,000 Btu/h2.6785°F / 52°F (Class 2)AHRI 1360
Air cooled with fluid economizerUpflow - ducted≥ 80,000 Btu/h and
< 295,000 Btu/h
2.5585°F / 52°F (Class 2)AHRI 1360
Air cooled with fluid economizerUpflow - ducted≥ 295,000 Btu/h2.3385°F / 52°F (Class 2)AHRI 1360
Air cooled with fluid economizerUpflow - nonducted< 65,000 Btu/h2.0975°F / 52°F (Class 1)AHRI 1360
Air cooled with fluid economizerUpflow - nonducted≥ 65,000 Btu/h and
< 240,000 Btu/h
1.9975°F / 52°F (Class 1)AHRI 1360
Air cooled with fluid economizerUpflow - nonducted≥ 240,000 Btu/h1.8175°F / 52°F (Class 1)AHRI 1360
Air cooled with fluid economizerHorizontal< 65,000 Btu/h2.6595°F / 52°F (Class 3)AHRI 1360
Air cooled with fluid economizerHorizontal≥ 65,000 Btu/h and
< 240,000 Btu/h
2.5595°F / 52°F (Class 3)AHRI 1360
Air cooled with fluid economizerHorizontal≥ 240,000 Btu/h2.4795°F / 52°F (Class 3)AHRI 1360
Water cooledDownflow< 80,000 Btu/h2.8285°F / 52°F (Class 2)AHRI 1360
Water cooledDownflow≥ 80,000 Btu/h and
< 295,000 Btu/h
2.7385°F / 52°F (Class 2)AHRI 1360
Water cooledDownflow≥ 295,000 Btu/h2.6785°F / 52°F (Class 2)AHRI 1360
Water cooledUpflow - ducted< 80,000 Btu/h2.7985°F / 52°F (Class 2)AHRI 1360
Water cooledUpflow - ducted≥ 80,000 Btu/h and
< 295,000 Btu/h
2.7085°F / 52°F (Class 2)AHRI 1360
Water cooledUpflow - ducted≥ 295,000 Btu/h2.6485°F / 52°F (Class 2)AHRI 1360
Water cooledUpflow - nonducted< 65,000 Btu/h2.4375°F / 52°F (Class 1)AHRI 1360
Water cooledUpflow - nonducted≥ 65,000 Btu/h and
< 240,000 Btu/h
2.3275°F / 52°F (Class 1)AHRI 1360
Water cooledUpflow - nonducted≥ 240,000 Btu/h2.2075°F / 52°F (Class 1)AHRI 1360
Water cooledHorizontal< 65,000 Btu/h2.7995°F / 52°F (Class 3)AHRI 1360
Water cooledHorizontal≥ 65,000 Btu/h and
< 240,000 Btu/h
2.6895°F / 52°F (Class 3)AHRI 1360
Water cooledHorizontal≥ 240,000 Btu/h2.6095°F / 52°F (Class 3)AHRI 1360
Water cooled with fluid economizerDownflow< 80,000 Btu/h2.7785°F / 52°F (Class 2)AHRI 1360
Water cooled with fluid economizerDownflow≥ 80,000 Btu/h and
< 295,000 Btu/h
2.6885°F / 52°F (Class 2)AHRI 1360
Water cooled with fluid economizerDownflow≥ 295,000 Btu/h2.6185°F / 52°F (Class 2)AHRI 1360
Water cooled with fluid economizerUpflow - ducted< 80,000 Btu/h2.7485°F / 52°F (Class 2)AHRI 1360
Water cooled with fluid economizerUpflow - ducted≥ 80,000 Btu/h and
< 295,000 Btu/h
2.6585°F / 52°F (Class 2)AHRI 1360
Water cooled with fluid economizerUpflow - ducted≥ 295,000 Btu/h2.5885°F / 52°F (Class 2)AHRI 1360
Water cooled with fluid economizerUpflow - nonducted< 65,000 Btu/h2.3575°F / 52°F (Class 1)AHRI 1360
Water cooled with fluid economizerUpflow - nonducted≥ 65,000 Btu/h and
< 240,000 Btu/h
2.2475°F / 52°F (Class 1)AHRI 1360
Water cooled with fluid economizerUpflow - nonducted≥ 240,000 Btu/h2.1275°F / 52°F (Class 1)AHRI 1360
Water cooled with fluid economizerHorizontal< 65,000 Btu/h2.7195°F / 52°F (Class 3)AHRI 1360
Water cooled with fluid economizerHorizontal≥ 65,000 Btu/h and
< 240,000 Btu/h
2.6095°F / 52°F (Class 3)AHRI 1360
Water cooled with fluid economizerHorizontal≥ 240,000 Btu/h2.5495°F / 52°F (Class 3)AHRI 1360
Glycol cooledDownflow< 80,000 Btu/h2.5685°F / 52°F (Class 2)AHRI 1360
Glycol cooledDownflow≥ 80,000 Btu/h and
< 295,000 Btu/h
2.2485°F / 52°F (Class 2)AHRI 1360
Glycol cooledDownflow≥ 295,000 Btu/h2.2185°F / 52°F (Class 2)AHRI 1360
Glycol cooledUpflow - ducted< 80,000 Btu/h2.5385°F / 52°F (Class 2)AHRI 1360
Glycol cooledUpflow - ducted≥ 80,000 Btu/h and
< 295,000 Btu/h
2.2185°F / 52°F (Class 2)AHRI 1360
Glycol cooledUpflow - ducted≥ 295,000 Btu/h2.1885°F / 52°F (Class 2)AHRI 1360
Glycol cooledUpflow - nonducted< 65,000 Btu/h2.0875°F / 52°F (Class 1)AHRI 1360
Glycol cooledUpflow - nonducted≥ 65,000 Btu/h and
< 240,000 Btu/h
1.9075°F / 52°F (Class 1)AHRI 1360
Glycol cooledUpflow - nonducted≥ 240,000 Btu/h1.8175°F / 52°F (Class 1)AHRI 1360
Glycol cooled with fluid economizerHorizontal< 65,000 Btu/h2.4895°F / 52°F (Class 3)AHRI 1360
Glycol cooled with fluid economizerHorizontal≥ 65,000 Btu/h and
< 240,000 Btu/h
2.1895°F / 52°F (Class 3)AHRI 1360
Glycol cooled with fluid economizerHorizontal≥ 240,000 Btu/h2.1895°F / 52°F (Class 3)AHRI 1360
Glycol cooled with fluid economizerDownflow< 80,000 Btu/h2.5185°F / 52°F (Class 2)AHRI 1360
Glycol cooled with fluid economizerDownflow≥ 80,000 Btu/h and
< 295,000 Btu/h
2.1985°F / 52°F (Class 2)AHRI 1360
Glycol cooled with fluid economizerDownflow≥ 295,000 Btu/h2.1585°F / 52°F (Class 2)AHRI 1360
Glycol cooled with fluid economizerUpflow - ducted< 80,000 Btu/h2.4885°F / 52°F (Class 2)AHRI 1360
Glycol cooled with fluid economizerUpflow - ducted≥ 80,000 Btu/h and
< 295,000 Btu/h
2.1685°F / 52°F (Class 2)AHRI 1360
Glycol cooled with fluid economizerUpflow - ducted≥ 295,000 Btu/h2.1285°F / 52°F (Class 2)AHRI 1360
Glycol cooled with fluid economizerUpflow - nonducted< 65,000 Btu/h2.0075°F / 52°F (Class 1)AHRI 1360
Glycol cooled with fluid economizerUpflow - nonducted≥ 65,000 Btu/h and
< 240,000 Btu/h
1.8275°F / 52°F (Class 1)AHRI 1360
Glycol cooled with fluid economizerUpflow - nonducted≥ 240,000 Btu/h1.7375°F / 52°F (Class 1)AHRI 1360
Glycol cooled with fluid economizerHorizontal< 65,000 Btu/h2.4495°F / 52°F (Class 3)AHRI 1360
Glycol cooled with fluid economizerHorizontal≥ 65,000 Btu/h and
< 240,000 Btu/h
2.1095°F / 52°F (Class 3)AHRI 1360
Glycol cooled with fluid economizerHorizontal≥ 240,000 Btu/h2.1095°F / 52°F (Class 3)AHRI 1360
a Applicable test procedure and reference year are provided under the definitions

TABLE 110.2-M Ceiling-Mounted Air Conditioners and Condensing Units Serving Computer Rooms – Minimum Efficiency Requirements

Equipment Type
Standard Model
Net Sensible Cooling Capacity
Minimum Net Sensible COP
Rating Conditions Return air
(dry bulb/dew point)
Test Procedure a
Air Cooled with free air discharge condenser
Ducted
< 29,000 Btu/h
2.05
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.02
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser
Ducted
≥ 65,000 Btu/h
1.92
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser
Nonducted
< 29,000 Btu/h
2.08
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.05
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser
Nonducted
≥ 65,000 Btu/h
1.94
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser with fluid economizer
Ducted
< 29,000 Btu/h
2.01
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser with fluid economizer
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.97
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser with fluid economizer
Ducted
≥ 65,000 Btu/h
1.87
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser with fluid economizer
Nonducted
< 29,000 Btu/h
2.04
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser with fluid economizer
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.00
75°F / 52°F (Class 1)
AHRI 1360
Air Cooled with free air discharge condenser with fluid economizer
Nonducted
≥ 65,000 Btu/h
1.89
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with ducted condenser
Ducted
< 29,000 Btu/h
1.86
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with ducted condenser
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.83
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with ducted condenser
Ducted
≥ 65,000 Btu/h
1.73
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with ducted condenser
Nonducted
< 29,000 Btu/h
1.89
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with ducted condenser
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.86
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with ducted condenser
Nonducted
≥ 65,000 Btu/h
1.75
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with fluid economizer and ducted condenser
Ducted
< 29,000 Btu/h
1.82
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with fluid economizer and ducted condenser
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.78
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with fluid economizer and ducted condenser
Ducted
≥ 65,000 Btu/h
1.68
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with fluid economizer and ducted condenser
Nonducted
< 29,000 Btu/h
1.85
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with fluid economizer and ducted condenser
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.81
75°F / 52°F (Class 1)
AHRI 1360
Air cooled with fluid economizer and ducted condenser
Nonducted
≥ 65,000 Btu/h
1.70
75°F / 52°F (Class 1)
AHRI 1360
Water cooled
Ducted
< 29,000 Btu/h
2.38
75°F / 52°F (Class 1)
AHRI 1360
Water cooled
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.38
75°F / 52°F (Class 1)
AHRI 1360
Water cooled
Ducted
≥ 65,000 Btu/h
2.18
75°F / 52°F (Class 1)
AHRI 1360
Water cooled
Nonducted
< 29,000 Btu/h
2.41
75°F / 52°F (Class 1)
AHRI 1360
Water cooled
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.31
75°F / 52°F (Class 1)
AHRI 1360
Water cooled
Nonducted
≥ 65,000 Btu/h
2.20
75°F / 52°F (Class 1)
AHRI 1360
Water cooled with fluid economizer
Ducted
< 29,000 Btu/h
2.33
75°F / 52°F (Class 1)
AHRI 1360
Water cooled with fluid economizer
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.23
75°F / 52°F (Class 1)
AHRI 1360
Water cooled with fluid economizer
Ducted
≥ 65,000 Btu/h
2.13
75°F / 52°F (Class 1)
AHRI 1360
Water cooled with fluid economizer
Nonducted
< 29,000 Btu/h
2.36
75°F / 52°F (Class 1)
AHRI 1360
Water cooled with fluid economizer
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
2.26
75°F / 52°F (Class 1)
AHRI 1360
Water cooled with fluid economizer
Nonducted
≥ 65,000 Btu/h
2.16
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled
Ducted
< 29,000 Btu/h
1.97
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.93
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled
Ducted
≥ 65,000 Btu/h
1.78
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled
Nonducted
< 29,000 Btu/h
2.00
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.98
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled
Nonducted
≥ 65,000 Btu/h
1.81
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled with fluid economizer
Ducted
< 29,000 Btu/h
1.92
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled with fluid economizer
Ducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.88
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled with fluid economizer
Ducted
≥ 65,000 Btu/h
1.73
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled with fluid economizer
Nonducted
< 29,000 Btu/h
1.95
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled with fluid economizer
Nonducted
≥ 29,000 Btu/h and
< 65,000 Btu/h
1.93
75°F / 52°F (Class 1)
AHRI 1360
Glycol cooled with fluid economizer
Nonducted
≥ 65,000 Btu/h
1.76
75°F / 52°F (Class 1)
AHRI 1360
a Applicable test procedure and reference year are provided under the definitions.

TABLE 110.2-N Heat Pump and Heat Recovery Chiller Packages – Minimum Efficiency Requirements

Equipment Type
Size Category, (tons)
Cooling-Only Operation Cooling Efficiencya
Full Load Efficiency (EER or kW/ton)
IPLV (EER or kW/ton)
Heating Operation
Test Procedure
Heating Source Conditionsd,e
Heat-Pump Heating Full-Load Efficiency
(COPH ) b
Heat Recovery Chiller Full-Load Efficiency (COPHR b, c
Simultaneous Cooling and Heating Full-Load Efficiency (COPSHC )b
Leaving Heating Water Temperature
Leaving Heating Water Temperature
Low
Med
High
Boost
Low
Med
High
Boost
Path A
Path B
105°F
120°F
140°F
140°F
105°F
120°F
140°F
140°F
Air source
All sizes
≥9.595 EER
≥13.02 IPLV
≥9.215 EER
≥15.01 IPLV
47°F d / 43°F d
≥ 3.290
≥2.770
≥2.310
NA
NA
NA
NA
NA
AHRI 550/590
≥9.595 EER
≥13.30 IPLV
≥9.215 EER
≥15.30 IPLV
17°F d / 15°F d
≥2.230
≥1.950
≥1.630
NA
NA
NA
NA
NA
Water source electrically operated positive displacement
<75
≤0.7885 kW/ton
≤0.6316 IPLV
≤0.7875 kW/ton
≤0.5145 IPLV
54°F e / 44°F e
≥4.640
≥3.680
≥2.680
NA
≥8.330
≥6.410
≥4.420
NA
AHRI 550/590
75°F e / 65°F e
NA
NA
NA
≥3.550
NA
NA
NA
≥6.150
≥75 and <150
≤0.7579 kW/ton ≤0.5895 IPLV
≤0.7140 kW/ton ≤0.4620 IPLV
54°F e / 44°F e
≥4.640
≥3.680
≥2.680
NA
≥8.330
≥6.410
≥4.420
NA
75°F e / 65°F e
NA
NA
NA
≥3.550
NA
NA
NA
≥6.150
≥150 and <300
≤0.6947 kW/ton ≤0.5684 IPLV
≤0.7140 kW/ton ≤0.4620 IPLV
54°F e / 44°F e
≥4.640
≥3.680
≥2.680
NA
≥8.330
≥6.410
≥4.420
NA
75°F e / 65°F e
NA
NA
NA
≥3.550
NA
NA
NA
≥6.150
≥300 and <600
≤0.6421 kW/ton ≤0.5474 IPLV
≤0.6563 kW/ton ≤0.4305 IPLV
54°F e / 44°F e
≥4.930
≥3.960
≥2.970
NA
≥8.900
≥6.980
≥5.000
NA
75°F e / 65°F e
NA
NA
NA
≥3.900
NA
NA
NA
≥6.850
≥600
≤0.5895 kW/ton ≤0.5263 IPLV
≤0.6143 kW/ton ≤0.3990 IPLV
54°F e / 44°F e
≥4.930
≥3.960
≥2.970
NA
≥8.900
≥6.980
≥5.000
NA
54°F e / 44°F e
NA
NA
NA
≥3.900
NA
NA
NA
≥6.850
Water source electrically operated centrifugal
<75
≤0.6421 kW/ton ≤0.5789 IPLV
≤0.7316 kW/ton ≤0.4632 IPLV
75°F e / 65°F e
≥4.640
≥3.680
≥2.680
NA
≥8.330
≥6.410
≥4.420
NA
AHRI 550/590
54°F e / 44°F e
NA
NA
NA
≥3.550
NA
NA
NA
≥6.150
≥75 and <150
≤0.5895 kW/ton ≤0.5474 IPLV
≤0.6684 kW/ton ≤0.4211 IPLV
75°F e / 65°F e
≥4.640
≥3.680
≥2.680
NA
≥8.330
≥6.410
≥4.420
NA
54°F e / 44°F e
NA
NA
NA
≥3.550
NA
NA
NA
≥6.150
≥150 and <300
≤0.5895 kW/ton ≤0.5263 IPLV
≤0.6263 kW/ton ≤0.4105 IPLV
75°F e / 65°F e
≥4.640
≥3.680
≥2.680
NA
≥8.330
≥6.410
≥4.420
NA
54°F e / 44°F e
NA
NA
NA
≥3.550
NA
NA
NA
≥6.150
≥300 and <600
≤0.5895 kW/ton ≤0.5263 IPLV
≤0.6158 kW/ton ≤0.4000 IPLV
75°F e / 65°F e
≥4.930
≥3.960
≥2.970
NA
≥8.900
≥6.980
≥5.000
NA
54°F e / 44°F e
NA
NA
NA
≥3.900
NA
NA
NA
≥6.850
≥600
≤0.5895 kW/ton ≤0.5263 IPLV
≤0.6158 kW/ton ≤0.4000 IPLV
54°F e / 44°F e
≥4.930
≥3.960
≥2.970
NA
≥8.900
≥6.980
≥5.000
NA
75°F e / 65°F e
NA
NA
NA
≥3.900
NA
NA
NA
≥6.850
a. Cooling-only rating conditions are standard rating conditions defined in AHRI550/590, Table 1.
b. Heating full-load rating conditions are at rating conditions defined in AHRI550/590, Table 1.
c. For water-cooled heat recovery chillers that have capabilities for heat rejection to a heat recovery condenser and a tower condenser, the COP applies to operation at full load with 100% heat recovery (no tower rejection). Units that only have capabilities for partial heat recovery shall meet the requirements of TABLE 110.2-D
d. Outdoor air entering dry-bulb ( db ) temperature and wet-bulb ( wb ) temperature.
e. Source-water entering and leaving water temperature.

This panel displays referenced content when certain links are clicked.

This program is funded by California utility customers and administered by Pacific Gas and Electric Company (PG&E), San Diego Gas & Electric Company (SDG&E®), and Southern California Edison Company (SCE) under the auspices of the California Public Utilities Commission.

© 2024 PG&E, SDG&E and SCE. All rights reserved, except that this content may be used, copied, and distributed without modification. Neither PG&E, SDG&E, nor SCE — nor any of their employees makes any warranty, express of implied; or assumes any legal liability or responsibility for the accuracy, completeness or usefulness of any data, information, method, product, policy or process disclosed in this document; or represents that its use will not infringe any privately-owned rights including, but not limited to patents, trademarks or copyrights.