This section addresses §120.6(b) of the Energy Code, which covers mandatory requirements for commercial refrigeration systems in retail food stores. This section explains the mandatory requirements for condensers, compressor systems, refrigerated display cases, and refrigeration heat recovery. All buildings under the Energy Code must also comply with the general provisions of the Energy Code (§100.0 – §100.2, §110.0 – §110.10, §120.0 – §120.9, §130.0 – §130.5) and additions and alterations requirements (§141.1).
The energy efficiency requirements for commercial refrigeration are all mandatory. There are no prescriptive requirements or performance compliance paths for commercial refrigeration. Since the provisions are all mandatory, there are no trade-offs allowed between the various requirements. The application must demonstrate compliance with each of the mandatory measures. Exceptions to each mandatory requirement where provided are described in each of the mandatory measure sections below.
In the 2022 Energy Code, adiabatic condenser efficiency and size requirements have been added. Section 120.6(b) 1D and 1E along with Table 120.6-D have been updated with new requirements for adiabatic condenser systems using halocarbon refrigerant.
Section 120.6(b) of the Energy Code applies to retail food or beverage stores that have 8,000 square feet or more of conditioned area and use either refrigerated display cases or walk-in coolers or freezers. The Energy Code has minimum requirements for the condensers, compressor systems, refrigerated display cases, and refrigeration heat-recovery systems associated with the refrigeration systems in these facilities.
The Energy Code does not have minimum efficiency requirements for walk-ins, as these are deemed appliances and are covered by the California Appliance Efficiency Regulations (Title 20) and federal Energy Independence and Security Act of 2007. Walk-ins are defined as refrigerated spaces with less than 3,000 square feet of floor area that are designed to operate below 55°F (13°C). Furthermore, the Energy Code does not have minimum equipment efficiency requirements for refrigerated display cases, as the minimum efficiency for these units is established by federal law in the Commercial Refrigeration Equipment Final Rule, but there are requirements for display cases that do result in reduced energy consumption.
Example 10-9
Question
The only refrigeration equipment in a retail food store with 10,000 square feet of conditioned area is self-contained refrigerated display cases. Does this store need to comply with the requirements for commercial refrigeration?
Answer
No. Since the refrigerated display cases are not connected to remote compressor units or condensing units, the store does not need to comply with the Energy Code.
Example 10-10
Question
A new retail store with 25,000 square feet conditioned area has two self-contained display cases. The store also has several display case lineups and walk-in boxes connected to remote compressors systems. Do all the refrigeration systems need to comply with the requirements for commercial refrigeration?
Answer
There are no provisions in the Energy Code for the two self-contained display cases. The refrigeration systems serving the other fixtures must comply with the Energy Code.
This section addresses the mandatory requirements for condensers serving commercial refrigeration systems. These requirements apply only to stand-alone refrigeration condensers and do not apply to condensers that are part of a unitary condensing unit.
If the work includes a new condenser replacing an existing condenser, the condenser requirements do not apply if all the following conditions apply:
- The total heat of rejection of the compressor system attached to the condenser or condenser system does not increase.
- Less than 25 percent of the attached refrigeration system compressors (based on compressor capacity at design conditions) are new.
- Less than 25 percent of the display cases (based on display case design load at applied conditions) that the condenser serves are new. Since the compressor system loads commonly include walk-ins (both for storage and point-of-sale boxes with doors), the 25 percent “display case" should be calculated with walk-ins included.
Example 10-11
Question
A supermarket remodel includes a refrigeration system modification where some of the compressors will be replaced, some of the refrigerated display cases will be replaced, and the existing condenser will be replaced. The project does not include any new load, and the design engineer has determined that the total system heat of rejection will not increase. The replacement compressors comprise 20 percent of the suction group capacity at design conditions, and the replacement display cases comprise 20 percent of the portion of the design load that comes from display cases. There are no changes in walk-ins. Does the condenser have to comply with the provisions of the Energy Code?
Answer:
No. This project meets all three criteria of the exception to the mandatory requirements for condensers:
1. The new condenser is replacing an existing condenser.
2. The total heat of rejection of the subject refrigeration system does not increase.
3a. The replacement compressors comprise less than 25 percent of the suction group design capacity at design conditions.
3b. The replacement display cases comprise less than 25 percent of the portion of the design load that comes from display cases.
§120.6(b)1A,B,& C
Condenser fans for new air-cooled, evaporative, or adiabatic condensers; fans on air- or water-cooled fluid coolers; or cooling towers used to reject heat on new refrigeration systems must be continuously variable-speed controlled. Variable-frequency drives are commonly used to provide continuously variable-speed control of condenser fans and controllers designed to vary the speed of electronically commutated motors are increasingly being used for the same purpose. All fans serving a common high side, or indirect condenser water loop, shall be controlled in unison. Thus, in normal operation, the fan speed of all fans within a single condenser or set of condensers serving a common high side should modulate together, rather than running fans at different speeds or staging fans off. However, when fan speed is at the minimum practical level, usually no higher than 10–20 percent, the fans may be staged off to reduce condenser capacity. As load increases, fans should be turned back on before significantly increasing fan speed, recognizing a control band is necessary to avoid excessive fan cycling. Control of air-cooled condensers may also keep fans running and use a holdback valve on the condenser outlet to maintain the minimum condensing temperature. Once all fans have reached minimum speed, the holdback valve is set below the fan control minimum saturated condensing temperature set point.
To minimize overall system energy consumption, the condensing temperature control set point must be continuously reset in response to ambient temperatures, rather than using a fixed set point value. This strategy is also termed ambient-following control, ambient-reset, wet bulb-following, and dry bulb-following — all referring to control logic that changes the condensing temperature control set point in response to ambient conditions at the condenser. The control system calculates a control set point saturated condensing temperature that is higher than the ambient temperature by a predetermined temperature difference (in other words, the condenser control temperature difference). Fan speed is then modulated so that the measured saturated condensing temperature (SCT) matches the calculated SCT control set point. The SCT control set point for evaporative condensers or water-cooled condensers (via cooling towers or fluid coolers) must be reset according to the ambient wet bulb temperature, and the SCT control set point for air-cooled condensers must be reset according to ambient dry bulb temperature. The target SCT for adiabatic condensers when operating in dry mode must be reset according to ambient dry bulb temperature. There is no requirement for SCT control during wet-mode (adiabatic) operation. Systems served by adiabatic condensers in Climate Zone 16 are exempted from this control requirement.
The condenser control TD is not specified in the Energy Code. The nominal control value is often equal to the condenser design TD. However, the value for a particular system is left up to the system designer. Since the intent is to use as much condenser capacity as possible without excessive fan power, the common practice is to optimize the control TD over a period such that the fan speed is in a range of around 60–80 percent during normal operation (that is, when not at minimum SCT and not in heat recovery).
The minimum saturated condensing temperature set point must be 70°F (21°C) or less. For systems using halocarbon refrigerants with glide, the SCT set point shall correlate with a midpoint temperature (between the refrigerant bubble-point and dew point temperatures) of 70°F (21°C) or less. As a practical matter, a maximum SCT set point is also commonly employed to set an upper bound on the control set point in the event of a sensor failure and to force full condenser operation during peak ambient conditions. This value should be set high enough that it does not interfere with normal operation.
Split air-cooled condensers are sometimes used for separate refrigeration systems, with two circuits and two rows of condenser fans. Each condenser half would be controlled as a separate condenser. If a condenser has multiple circuits served by a common fan or set of fans, the control strategy may use the average condensing temperature or the highest condensing temperature of the circuits as the control variable for controlling fan speed.
Alternative control strategies are permitted to the condensing temperature reset control required in §120.6(b)1C. The alternative control strategy must be demonstrated to provide equal or better performance, as approved by the executive director.
Air-cooled condensers with separately installed evaporative precoolers added to the condenser are not considered adiabatic condensers for this standard and must meet the requirements for air-cooled equipment, including specific efficiency and ambient-following control.
Example 10-12:
Question:
A new supermarket with an evaporative condenser is being commissioned. The control system designer has used a wet bulb-following control strategy to reset the system-saturated condensing temperature (SCT) set point. The refrigeration engineer has calculated that adding a TD of 15°F (8.3°C) above the ambient wet bulb temperature should provide a saturated condensing temperature set point that minimizes the combined compressor and condenser fan power usage throughout the year. What might the system SCT and SCT set point trends look like over an example day?
Answer
The following figure illustrates what the actual saturated condensing temperature and SCT set points could be over an example day using the wet bulb-following control strategy with a 15°F (8.3°C) TD and also observing the 70°F (21°C) minimum condensing temperature requirement. As the figure shows, the SCT set point is continuously reset to 15°F (8.3°C) above the ambient wet bulb temperature until the minimum SCT set point of 70°F is reached. The figure also shows a maximum SCT set point (in this example, 90°F (32.2°C), which may be used to limit the maximum control set point, regardless of the ambient temperature value or TD parameter.

All newly installed evaporative condensers, air-cooled condensers, and adiabatic condensers with capacities greater than 150,000 Btuh (at the specific efficiency rating conditions) shall meet the minimum specific efficiency requirements shown in Table 10-2.
Condenser Type | Minimum Specific Efficiency | Rating Condition |
Evaporative-Cooled | 160 Btuh/Watt | 100°F Saturated Condensing Temperature (SCT), 70°F Entering Wet bulb Temperature |
Air-Cooled | 65 Btuh/Watt | 105°F Saturated Condensing Temperature (SCT), 95°F Entering Dry bulb Temperature |
Adiabatic Dry Mode | 45 Btuh/Watt (Halocarbon) | 105°F Saturated Condensing Temperature (SCT), 95°F Entering Dry bulb Temperature |
Source: California Energy Commission
Condenser specific efficiency is defined as:
Condenser Specific Efficiency = Total Heat Rejection (THR) Capacity/Input Power
The total heat rejection capacity is defined at the rating conditions of 100°F SCT and 70°F outdoor wet bulb temperature for evaporative condensers, and 105°F SCT and 95°F outdoor dry bulb temperature for air-cooled and adiabatic (halocarbon refrigerant only) condensers. Total heat of rejection capacity for adiabatic condensers is based on dry mode ratings (in other words, no precooling of the air). Input power is the electric input power draw of the condenser fan motors (at full speed) plus the electric input power of the spray pumps for evaporative condensers. The motor power is the manufacturer’s published applied power for the subject equipment, which is not necessarily equal to the motor nameplate rating. Power input for secondary devices such as sump heaters shall not be included in the specific efficiency calculation.
The data published in the condenser manufacturer’s published rating for capacity and power shall be used to calculate specific efficiency. For evaporative condensers, manufacturers typically provide nominal condenser capacity and tables of correction factors that are used to convert the nominal condenser capacity to the capacity at various applied condensing temperatures and wet bulb temperatures. Usually, the manufacturer publishes two sets of correction factors: one is a set of “heat rejection” capacity factors, while the other is a set of “evaporator ton” capacity factors. Only the “heat rejection” capacity factors shall be used to calculate the condenser capacity at the efficiency rating conditions for determining compliance with this section.
For air-cooled and adiabatic condensers, manufacturers typically provide the capacity at a given temperature difference (TD) between SCT and dry bulb temperature. Manufacturers typically assume that air-cooled condenser capacity is linearly proportional to TD; the catalog capacity at 20°F TD is typically twice as much as at 10°F TD. The condenser capacity for air-cooled and adiabatic condensers at a TD of 10°F shall be used to calculate efficiency. If the capacity at 10°F TD is not provided, the capacity shall be scaled linearly.
Depending on the type of condenser, the actual manufacturer’s rated motor power may vary from motor nameplate in different ways. Air-cooled condensers with direct-drive original equipment manufacturer (OEM) motors may use far greater input power than the nominal motor horsepower would indicate. On the other hand, evaporative condenser fans may have a degree of safety factor to allow for higher motor load in cold weather conditions (vs. the 100°F SCT/70°F WBT specific efficiency rating conditions). Thus, actual motor input power from the manufacturer must be used for direct-drive air-cooled condensers. For evaporative condensers and fluid coolers, the full load motor power, using the minimum allowable motor efficiencies published in the Nonresidential Appendix NA-3: Fan Motor Efficiencies, is generally conservative, but manufacturer’s applied power should be used whenever possible to determine specific efficiency more accurately.
There are three exceptions to the condenser specific efficiency requirements.
- If the store is located in Climate Zone 1 (the cool coastal region in Northern California).
- If an existing condenser is reused for an addition or alteration.
- If the condenser capacity is less than 150,000 Btuh at the specific efficiency rating conditions.
Example 10-13
Question
An air-cooled condenser is being designed for a new supermarket. The refrigerant is R- 507. The condenser manufacturer’s catalog states that the subject condenser has a capacity of 500 MBH at 10°F TD between entering air and saturated condensing temperatures with R-507 refrigerant. Elsewhere in the catalog, it states that the condenser has 101⁄2 hp fan motors that draw 450 watts each. Does this condenser meet the minimum efficiency requirements?
Answer
First, the condenser capacity must be calculated at the specific efficiency rating condition. From Table 10-6, we see that the rating conditions for an air-cooled condenser are 95°F entering dry bulb temperature and 105°F SCT. The catalog capacity is at a 10°F temperature difference, which is deemed suitable for calculating the specific efficiency (105°F SCT - 95°F entering dry bulb = 10°F TD). Input power is equal to the number of motors multiplied by the input power per motor:

The specific efficiency of the condenser is therefore:

This condenser has a specific efficiency of 111 Btuh per watt, which is higher than the 65 Btuh per watt minimum requirement. This condenser meets the minimum specific efficiency requirements.
Example 10-14
Question
An evaporative condenser is being designed for a new supermarket. The manufacturer’s catalog provides a capacity of 2,000 MBH at standard conditions of 105°F SCT and 78°F wet bulb temperature. The condenser manufacturer’s catalog provides the following heat rejection capacity factors:

Elsewhere in the catalog, it states that the condenser model has one 10 HP fan motor and one 2 HP pump motor. Fan motor efficiencies and motor loading factors are not provided by the manufacturer. Does this condenser meet the minimum efficiency requirements?
Answer
First, the condenser capacity must be calculated at the specific efficiency rating condition. From Table 10-6, we see that the rating conditions for an evaporative condenser are 100°F SCT, 70°F WBT, and a minimum specific efficiency requirement is 160 Btuh/watt. From the Heat Rejection Capacity Factors table, we see that the correction factor at 100°F SCT and 70°F WBT is 0.95. The capacity of this model at the specific efficiency rating conditions is:
2,000 MBH/0.95 = 2,105 MBH
To calculate input power, we will assume 100 percent fan and pump motor loading and minimum motor efficiencies since the manufacturer has not yet published actual motor specific efficiency at the specific efficiency rating conditions. We look up the minimum motor efficiency from Nonresidential Appendix NA-3: Fan Motor Efficiencies. For a 10 HP six-pole open fan motor, the minimum efficiency is 91.7 percent. For a 2 HP six-pole open pump motor, the minimum efficiency is 87.5 percent. The fan motor input power is calculated to be:

The pump motor input power is calculated to be:

The combined input power is therefore:
8,135 watts + 1,705 watts = 9,840 watts
Note: Actual motor power should be used when available. (See note in text.)
Finally, the efficiency of the condenser is:

214 Btuh per watt is higher than the 160 Btuh per watt requirement; this condenser meets the minimum efficiency requirements.
Example 10-15
Question
An adiabatic condenser is being designed for a new supermarket. The refrigerant is R- 407A. The condenser manufacturer’s catalogue states that the subject condenser has a capacity of 550 MBH at 10°F TD between entering air dry bulb temperature and saturated condensing temperatures with R-407A refrigerant when operating in dry mode. Elsewhere in the catalog, it states that the condenser has two 5-hp fan motors that draw 4.5 kW each. Does this condenser meet the minimum efficiency requirements?
Answer
First, the condenser capacity must be calculated at the specific efficiency rating condition. From Table 10-2, we see that the rating conditions for an air-cooled condenser are 95°F entering dry bulb temperature and 105°F SCT. The catalog capacity is rated at a 10°F temperature difference, which is deemed suitable for calculating the specific efficiency (105°F SCT - 95°F entering dry bulb = 10°F TD). Input power is equal to the number of motors multiplied by the input power per motor:
2 fan motors x 4,500 watts = 9,000 watts
The specific efficiency of the condenser is therefore:
(550MBH x 1,000 Btu/hr/MBH) / 9000 watts = 61 Btu/hr/watts
This condenser has a specific efficiency of 61 Btuh per watt, which is higher than the 45 Btuh per watt minimum requirement. This condenser meets the minimum specific efficiency requirements.
Air-cooled condensers shall have a fin density no greater than 10 fins per inch. Condensers with higher fin densities have a higher risk of fouling with airborne debris. This requirement does not apply for air-cooled condensers that use a microchannel heat exchange surface, since this type of surface is not as susceptible to permanent fouling in the same manner as traditional tube-and-fin condensers with tight fin spacing.
The fin spacing requirement does not apply to condensers that are reused for an addition or alteration.
New adiabatic condensers on new refrigeration systems must follow the condenser sizing, fan control, and efficiency requirements as described in §120.6(b)1E.
Condensers must be sized to provide sufficient heat rejection capacity under design conditions while maintaining a specified maximum temperature difference between the refrigeration system SCT and ambient temperature. The design condenser capacity shall be greater than the calculated combined total heat of rejection (THR) of the dedicated compressors that are served by the condenser. If multiple condensers are specified, then the combined capacity of the installed condensers shall be greater than the calculated heat of rejection. When determining the design THR for this requirement, reserve or backup compressors may be excluded from the calculations.
Section 120.6(b)1E provides maximum design SCT values for adiabatic condensers. For this section, designers should use the 0.5 percent design dry bulb temperature (DBT) from Table 10-4 – Design Day Data for California Cities in the Reference Joint Appendices JA2. to demonstrate compliance with this requirement.
Standard practice is for published condenser ratings to assume the capacity of adiabatic condensers is proportional to the temperature difference (TD) between SCT and DBT for operation in dry mode, regardless of the actual ambient temperature entering the condenser. For example, the capacity of an adiabatic condenser operating at an SCT of 80°F with a DBT of 70°F is assumed to be equal to the same unit operating at 110°F SCT and 100°F DBT during dry mode operation, since the TD across the condenser is 10°F in both examples. Thus, similar to air-cooled condensers, the requirement for adiabatic condensers does not have varying sizing requirements for different design ambient temperatures.
However, the Energy Code has different requirements for adiabatic condensers depending on the space temperatures served by the refrigeration system. The maximum design SCT requirements are listed in Table 10-5 below.
Refrigerated Load Type | Space Temperature | Maximum SCT (dry mode) |
Cooler | ≥ 28°F | Design DBT plus 30 °F |
Freezer | < 28°F | Design DBT plus 20 °F |
Source: California Energy Commission
Often, a single refrigeration system and the associated condenser will serve a mix of cooler and freezer load. In this instance, the maximum design SCT shall be a weighted average of the requirements for cooler and freezer loads, based on the design evaporator capacity of the spaces served.
Example 10-16
Question
An adiabatic condenser is being sized for a system that has half of the installed capacity serving cooler space and the other half serving freezer space. What is the design TD to be added to the design dry bulb temperature?
Answer
Using adiabatic condensers for coolers has a design approach of 30°F and for freezers a design approach of 20°F. When a system serves freezer and cooler spaces, a weighted average should be used based on the installed capacity. To calculate the weighted average, multiply the percentage of the total installed capacity dedicated to coolers by 30°F. Next, multiply the percentage of the total installed capacity de freezers by 20°F. The sum of the two results is the design condensing temperature approach. In this example, the installed capacity is evenly split between freezer and cooler space. As a result, the design approach for the air-cooled condenser is 25°F.
(50% x 20 °F) + (50% x 30°F) = 10°F + 15 °F = 25 °F
This section addresses mandatory requirements for remote compressor systems and condensing units used for refrigeration. In addition to the requirements described below, all the compressors and all associated components must be designed to operate at a minimum condensing temperature of 70°F (21°C) or less.
Compressors and multiple-compressor suction groups must have floating suction pressure control to reset the saturated suction pressure control set point based on the temperature requirements of the attached refrigeration display cases or walk-ins.
Exceptions to the floating suction pressure requirements are:
- Single compressor systems that do not have continuously variable-capacity capability.
- Suction groups that have a design saturated suction temperature of 30°F or higher.
- Suction groups that comprise the high side of a two-stage or cascade system.
- Suction groups that primarily serve chillers for secondary cooling fluids.
- Existing compressor systems that are reused for an addition or alteration.
The examples of a two-stage system and a cascade system are shown in Figure 10-7 and Figure 10-8, respectively. Figure 10-9 shows a secondary fluid system.
Figure 10-7: Two-Stage System Using a Two-Stage Compressor

Figure 10-8: Cascade System

Figure 10-9: Secondary Fluid System

Example 10-17
Question
A retail food store has four suction groups, A, B1, B2, and C, with design saturated suction temperatures (SST) of -22°F, -13°F, 28°F and 35°F, respectively. System A is a condensing unit. The compressor in the condensing unit is equipped with two unloaders. Suction Group B1 consists of a single compressor with no variable-capacity capability. Suction Group B2 has four compressors with no variable-capacity capability and Suction Group C has three compressors with no variable-capacity capability. Which of these suction groups are required to have floating suction pressure control?
Answer
Suction Groups A and B2 are required to have floating suction pressure control. The rationale is explained below.
Suction Group A: Although the suction group has only one compressor, the compressor has variable-capacity capability in the form of unloaders. Therefore, the suction group is required to have floating suction pressure control.
Suction Group B1: The suction group has only one compressor with no variable-capacity capability. Therefore, the suction group is not required to have floating suction pressure control.
Suction Group B2: Although the suction group has compressors with no variable-capacity capability, the suction group has multiple compressors that can be sequenced to provide variable-capacity capability. Therefore, the suction group is required to have floating suction pressure control.
Suction Group C: The design SST of the suction group is higher than 30°F. Therefore, the suction group is not required to have floating suction pressure control.
Example 10-18
Question
A retail food store has two suction groups, a low-temperature Suction Group A (-22°F design SST) and medium-temperature suction group B (18°F design SST). Suction Group A consists of three compressors. Suction Group B has four compressors that serve a glycol chiller working at 23°F. Which of these suction groups are required to have floating suction pressure control?
Answer
Suction Group A: The suction group has multiple compressors. Therefore, the suction group is required to have floating suction pressure control.
Suction Group B: Although the suction group has multiple compressors, it serves a chiller for secondary cooling fluid (glycol). Therefore, the suction group is not required to have floating suction pressure control.
Example 10-19
Question
A retail food store is undergoing an expansion and has two refrigeration systems: an existing system and a new CO2 cascade system. The existing system consists of four compressors and a design SST of 18°F. The cascade refrigeration system consists of four low-temperature compressors operating at -20°F SST and three medium-temperature compressors operating at 26°F SST. Which of these systems are required to have floating suction pressure control?
Answer
Existing system: Although the system has multiple compressors, the compressor system is being reused, and the existing rack controller and sensors may not support floating suction pressure control. Therefore, the system is not required to have floating suction pressure control.
Cascade system: Only the low-temperature suction group of the system is required to have floating suction pressure control.
Evaporator coils are sized to maintain a design fixture temperature under design load conditions. Design loads are high enough to cover the highest expected load throughout the year and inherently include safety factors. The actual load on evaporator coils varies throughout the day, month, and year, and an evaporator coil operating at the design saturated evaporating temperature (SET) has excess capacity at most times. The SET can be safely raised during these times, reducing evaporator capacity and the required “lift” of the suction group, saving energy at the compressor while maintaining proper fixture (and product) temperature.
In a floating suction pressure control strategy, the suction group target saturated suction temperature (SST) set point is allowed to vary depending on the actual requirements of the attached loads, rather than fixing the SST set point low enough to satisfy the highest expected yearly load. The target set point is adjusted so that it is just low enough to satisfy the lowest current SET requirement of any attached refrigeration load while maintaining target fixture temperatures, but not any higher. The controls are typically bound by low and high set point limits. The maximum float value should be established by the system designer, but a minimum value equal to the design SST (that is no negative float) and a positive float range of 4-6°F of saturation pressure equivalent have been used successfully.
Figure 10-10 shows hourly values for floating suction pressure control over one week, expressed in equivalent saturation temperature. The suction pressure control set point is adjusted to meet the temperature set point at the most demanding fixture or walk-in. The difference in SST between the floating suction pressure control and fixed suction pressure control translates into reduced compressor work and, thus, energy savings for the floating suction control.
Figure 10-10: Example of Floating Suction Pressure Control
Mechanical evaporator pressure regulators (EPR valves) are often used on multiplex systems to maintain temperature by regulating the SET at each evaporator connected to the common suction group and often to function as a suction stop valve during defrost. EPR valves throttle to maintain the pressure at the valve inlet and, thus, indirectly control the temperature at the case or walk-in. The valves are manually adjusted to the pressure necessary to provide the desired fixture or walk-in air temperature. The load (circuit) with the lowest EPR pressure governs the required compressor suction pressure set point.
Floating suction pressure on a system with EPR valves requires special attention to valve settings on the circuit(s) used for floating suction pressure control. EPR valves on these circuit(s) must be adjusted “out of range,” meaning the EPR pressure must be set lower than what would otherwise be used to maintain temperature. This setting keeps the EPR valve from interfering with the floating suction control logic. In some control systems, two circuits are used to govern floating suction control, commonly designated as primary and secondary float circuits. EPR valves may also be equipped with electrically controlled wide-open solenoid pilots for more fully automatic control, if desired.
Similar logic is applied on systems using on/off liquid line solenoid valves for temperature control, with the control of the solenoid adjusted slightly out of range to avoid interference with floating suction pressure.
These procedures have been employed to float suction on supermarket control systems since the mid-1980s; however careful attention is still required during design, start-up, and commissioning to ensure control is effectively coordinated.
Figure 10-11: Evaporators With Evaporative Pressure Regulator Valves
An electronic suction regulator (ESR) valve is an electronically controlled valve used in place of a mechanical evaporator pressure regulator valve. ESRs are also known in the industry as electronic evaporator pressure regulators. ESR valves are not pressure regulators; instead, they control the flow through the evaporator based on a set point air temperature at the case or walk-in. ESR valves are modulated to maintain precise temperature. This modulation provides more accurate temperature compared to an EPR that controls temperature indirectly through pressure and is subject to pressure drop in piping and heat load (and thus TD) on the evaporator coil.
Floating suction pressure strategies with ESR valves vary depending on the controls manufacturer but will generally allow for more flexibility than systems with EPR valves. In general, the control system monitors how much each ESR valve is opened. If an ESR is fully open, indicating that the evaporator connected to the ESR requires more capacity, the control system will respond by decrementing the SST set point. If all ESR valves are less than fully open, the control system increments the suction pressure up until an ESR valve fully opens. At this point, the control system starts floating down the suction pressure again. This allows suction pressure to be no lower than necessary for the most demanding fixture.
Figure 10-12 shows multiple evaporators controlled by ESR valves connected to a common suction group.
Figure 10-12: DX Evaporators with ESRs on a Multiplex System
Liquid subcooling must be provided for all low-temperature compressor systems with a design cooling capacity of 100,000 Btuh or greater and a design saturated suction temperature of -10°F or lower. The subcooled liquid temperature of 50°F or less must be maintained continuously at the exit of the subcooler. Subcooling load may be handled by compressor economizer ports or by the use of a suction group operating at a saturated suction temperature of 18°F or higher. Figure 10-13 and Figure 10-14 show example subcooling configurations.
Exceptions to the liquid subcooling requirements are:
Figure 10-13: Liquid Subcooling Provided by Scroll Compressor Economizer Ports

Figure 10-14: Liquid Subcooling Provided by a Separate Medium-Temperature System

10.5.3.1 Compressors for Transcritical CO2 Refrigeration Systems
Floating head control is one of the largest energy savings measures applied to refrigeration systems. This control attempts to keep condensing temperatures as low as possible (while not consuming too much gas cooler fan energy) as this reduces compressor head pressure, which directly affects compressor energy.
When ambient temperatures are low, the primary constraint on how low the condensing temperature can be reset is the design requirements of the compressor and associated system components.
Section 120.6(b)2C addresses the compatibility of the compressor design and components with the requirements for floating head control. All compressors that discharge to the gas cooler(s) and all associated components (coalescing oil separators, expansion valves for liquid injection oil cooling, etc.) must be capable of operating at a condensing temperature of 60°F (16°C) or less. Oil separator sizing is often governed by the minimum condensing temperature, as well as other factors, such as the maximum suction temperature. Suction temperatures above the design value may occur under floating suction temperature control schemes.
The system designer should also keep in mind that other design parameters such as piping run lengths or evaporator defrost requirements must be considered to meet this requirement.
The exception to the minimum SCT of 60°F for transcritical CO2 systems requirement is:
- Compressors with a design saturated suction temperature greater than or equal to 30°F shall be designed to operate at a minimum condensing temperature of 70°F or less.
- Existing compressor systems that are reused for an addition or alteration.
All lighting for refrigerated display cases and glass doors of walk-in coolers and freezers shall be controlled by either automatic time switch controls or motion sensor controls or both.
Automatic time switch controls shall turn off the lights during nonbusiness hours.
Timed overrides for a display case lineup or walk-in case may be used to turn on the lights for stocking or nonstandard business hours. The override must time-out and automatically turn the lights off again in one hour or less. The override control may be enabled manually (e.g., a push button input to the control system) or may be scheduled by the lighting control or energy management system.
Motion-sensor control can be used to meet this requirement by either dimming or turning off the display case lights when space near the case is vacated. The lighting must dim so that the lighting power reduces to 50 percent or less. The maximum time delay for the motion sensor must be 30 minutes or less.
This section addresses mandatory requirements for the use of heat recovery from refrigeration system(s) to HVAC system(s) for space heating and the charge limitations when implementing heat recovery, including an overview of configurations and design considerations for heat recovery systems. Heat rejected from a refrigeration system is the total of the cooling load taken from display cases and walk-ins in the store plus the electric energy used by the refrigeration compressors. Consequently, there is a natural relationship between the heat available and the heating needed; a store with greater refrigeration loads needs more heat to make up for the cases and walk-ins and has more heat available.
The heat recovery requirements apply only to space heating.
There are many possible heat recovery design configurations due to the variety of refrigeration systems, HVAC systems, and potential arrangement and locations of these systems. Several examples are presented here, but the Energy Code does not require these configurations to be used. The heat recovery design must be consistent with the other requirements in the Energy Code, such as condenser floating head pressure.
At least 25 percent of the sum of the design total heat of rejection (THR) of all refrigeration systems with individual design THR of 150,000 Btu/h or greater must be used for space heat recovery.
Exceptions to the above requirements for heat recovery are:
- Stores in Climate Zone 15, which is the area around Palm Springs, California. Weather and climate data are available in Joint Appendix JA2. – Reference Weather/Climate Data.
- The above requirements for heat recovery do not apply to the HVAC and refrigeration systems that are reused for an addition or alteration.
- Stores that are designed to provide less than 500,000 Btu/h in total heat rejection for all the refrigeration systems in the store combined.
The Energy Code also limits the increase in hydrofluorocarbon (HFC) refrigerant charge associated with refrigeration heat recovery. The increase in HFC refrigerant charge associated with refrigeration heat recovery equipment and piping must not be greater than 0.35 lbs. per 1,000 Btuh of heat recovery heating capacity.
Example 10-20
Question
A store has three new distributed refrigeration systems, A, B and C, with design THR of 140,000 Btuh, 230,000 Btu/h and 410,000 Btuh, respectively. What is the minimum required amount of refrigeration heat recovery?
Answer
Refrigeration Systems B and C have design THR of greater than 150,000 Btu/h, whereas Refrigeration System A has a design THR of less than 150,000 Btuh. Therefore, the store must have the minimum refrigeration heat recovery equal to 25 percent of the sum of THR of refrigeration systems B and C only. The minimum required heat recovery is therefore:
25% x (230,000 Btuh + 410,000 Btuh) = 160,000 Btuh
Example 10-21
Question
How should the THR be calculated for this section?
Answer
The THR value is equal to the total compressor capacity plus the compressor heat of compression.
Example 10-22
Question
A 35,000 ft2 food store is expanding to add 20,000 square feet area. The store refrigeration designer plans to use two existing refrigeration systems with 600,000 Btu/h of design total heat rejection capacity and add a new refrigeration system with a design total heat rejection capacity of 320,000 Btu/h. The store mechanical engineer plans to replace all the existing HVAC units. Is the store required to have refrigeration heat recovery for space heating?
Answer:
Yes. The store must have the minimum required refrigeration heat recovery from the new refrigeration system. The new refrigeration system has a design THR of greater than 150,000 Btu/h threshold. The minimum amount of the refrigeration heat recovery is 25 percent of the new system THR. The existing refrigeration systems are not required to have the refrigeration heat recovery.
The designer of heat recovery systems must consider the arrangement of piping, valves, coils, and heat exchangers as applicable to comply with the Energy Code. Numerous refrigeration heat recovery systems configurations are possible depending upon the refrigeration system type, HVAC system type, and the store size. Some possible configurations are:
- Direct heat recovery.
- Indirect heat recovery.
- Water loop heat pump system.
These configurations are described in more detail with the following sections.
Figure 10-15 shows a series-connected direct condensing heat recovery configuration. In this configuration, the heat recovery coil is placed directly within the HVAC unit airstream (generally the unit serving the main sales area), and the discharge refrigerant vapor from the compressors is routed through the recovery coil and then to the outdoor refrigerant condenser when in heating mode. If two or more refrigeration systems are used for heat recovery, a multicircuit heat recovery coil could be used.
This configuration is very suitable when the compressor racks are close to the air handling units used for heat recovery. If the distance is too far, an alternative design should be considered; the long piping runs may result in a refrigerant charge increase that exceeds the maximum defined in the Energy Code, or there may be excessive pressure losses in the piping that could negatively affect compressor energy.
Figure 10-15: Series Direct Heat Recovery Configuration

Figure 10-16 shows a parallel-connected direct-condensing configuration. In this configuration, the heat recovery coil handles the entire condensing load for the connected refrigeration system(s) when the air-handling unit is in heating mode. Reduced refrigerant charge is the primary advantage of this configuration. Since the unused condenser (either the heat recovery condenser or the outdoor condenser) can be pumped out, there is no increase in refrigerant charge. A high degree of design expertise is required with this configuration in that the heat recovery condenser and associated HVAC system must take the entire heating load while operating at reasonable condensing temperatures — in any event, no higher than the system design SCT and in most instances with reasonable design no higher than 95°F-100°F condensing temperature in the heat recovery condenser. Ducting with under case or low return air design is essential in this type of system to obtain cooler entering air and maintain reasonable condensing temperatures. Provision is required for practical factors such as dirty air filters.
Since the main condenser is not in use during heat recovery, the condenser floating head pressure requirements do not apply.
Figure 10-16: Parallel Direct Condensing Heat Recovery Configuration
Figure 10-17 shows an indirect heat recovery configuration with a fluid loop. In this configuration, the recovered heat is transferred from the refrigerant to an intermediate fluid, normally water or water-glycol, which is circulated through a fluid-to-air heat exchanger located in the air-handling unit airstream. Like the direct condensing configuration, discharge refrigerant gas from the compressors is routed through the refrigerant-to-fluid heat exchanger and then to the outdoor refrigerant condenser when in heating mode.
The refrigerant-to-fluid heat exchanger can be located close to the refrigeration system compressors, maximizing the available heat for recovery while keeping the overall refrigerant charge increase low. This configuration is also suitable when multiple HVAC units are employed for the refrigeration heat recovery. Indirect systems must use a circulation pump to circulate the fluid between the HVAC unit and the recovery heat exchanger.
Figure 10-17: Indirect Heat Recovery With an Indirect Loop

Several refrigeration systems can also be connected in parallel or in series, using a common indirect fluid loop. Figure 10-18 shows three refrigeration systems connected in series by a common fluid loop. The temperatures shown are only examples.
Figure 10-18: Series-Piped Indirect Water Recovery

This configuration allows the refrigerant-to-water condenser temperature difference (TD) to be kept low at each refrigeration system (e.g., 8°-10°F is possible) while maintaining a sufficiently high water-side TD at the air-handling unit (e.g., 20°-25°F depending on specifics) to allow an effective selection of the water-to-air heating coil vs. the available airflow. This method also minimizes both the required fluid flow and pump power.
Water-source heat pumps (WLHP) can be used for in conjunction with water cooled refrigeration systems, connected to a common water loop as shown in Figure 10-19. Refrigeration systems heat pumps serving various zones of the store reject heat into a water loop, which in turn is rejected to ambient by an evaporative fluid cooler. When the heat pumps are in heating mode, they extract the heat rejected by the refrigeration systems from the water loop. Additional heat, if required, is provided by a boiler connected to the water loop. A significant advantage of this design is low refrigerant charge, since the refrigeration systems use a compact water-cooled condenser, typically with less charge than an air-cooled condenser and no heat recovery condenser is required. Compared with other methods, however, the electric penalty is somewhat higher to utilize the available heat.
The floating pressure requirements in the standard would apply to the fluid coolers, i.e., controls to allow refrigeration systems to float to 70°F SCT and use of wet bulb following control logic.
Figure 10-19: Water Loop Heat Pump Example
For direct and indirect systems, a holdback valve is required to control the refrigerant condensing temperature in the heat recovery coil (for direct systems) or the refrigerant-to-water condenser (for indirect systems) during heat recovery. Regulating the refrigerant pressure to achieve condensing recovers the latent heat from the refrigerant. Without condensing, only the sensible heat (i.e., superheat) is obtained, which is only a small fraction of the available heat. Figure 10-20 is a pressure-enthalpy diagram showing the difference in available recovery heat from a refrigeration system with and without a holdback valve.
Figure 10-20: Pressure-Enthalpy Diagram With and Without a Holdback Valve

The holdback valve regulates pressure at the inlet and is at the exit of the recovery heat exchanger. Figure 10-21 shows a direct-condensing configuration with the proper location of the holdback valve.
Figure 10-21: Direct-Condensing Configuration Showing Location of Holdback Valve

A more advanced design uses an electronic holdback valve controlled based on the temperature of the air entering the heat recovery coil. The electronic heat recovery holdback valve controls the valve inlet pressure and thus the heat recovery coil condensing temperature to maintain only the pressure necessary to achieve the required condensing TD (heat recovery SCT less entering air temperature), thereby minimizing compressor efficiency penalty. This is particularly useful when the volume outside air can significantly change the mixed air temperature entering the heat recovery coil. In colder climates, reducing the heat recovery holdback pressure can be important as a means to avoid overcondensing (i.e., subcooling). As shown in the pressure-enthalpy diagram above, there is additional flash gas handled by the condenser (even if the refrigerant fully condenses in the heat recovery coil), which is necessary to maintain piping and condenser velocity and, thus, minimize the charge in the outdoor condenser.
Other designs can replace the three-way valve with a differential pressure regulator and solenoid valve. Figure 10-22 shows a direct-condensing configuration with an electronic heat recovery holdback valve, solenoid valve, and differential pressure regulator.
Figure 10-22: Direct-Condensing Configuration Showing Differential Regulator, Solenoid Valve, Electronic Holdback Valve
There is typically a tradeoff between heat recovery and refrigeration system efficiency, in that compressor discharge pressure must be increased to provide condensing for heat recovery. If implemented properly, the electric penalty at the refrigeration system compressors is small compared to the heating energy savings.
The Energy Codes require that the minimum condensing temperature at the refrigeration condenser shall be 70°F or less. That means that (in the typical case of series-connected heat recovery) the refrigeration “cycle” still benefits from lower refrigerant liquid temperature, even if the compressor power is somewhat increased during heat recovery. The pressure-enthalpy diagram shown in Figure 10-23 shows the incremental energy penalty at the refrigeration compressors due to the higher discharge pressure required for heat recovery, as well as the lower liquid temperature (and thus improved refrigerant cooling capacity) by floating head pressure at the outdoor condenser.
Figure 10-23: Pressure-Enthalpy Diagram for Heat Recovery
Selecting an appropriately sized heat recovery coil is essential to proper heat recovery system operation. The following example details the process of selecting a right-sized heat recovery coil.
Example 10-23
Question
A supermarket is being constructed that will use heat recovery. The refrigeration system selected for recovery has the following parameters:
Design refrigeration load: 455.8 MBH
System design SST: 24°F
Representative compressor capacity at design conditions: 54.2 MBH
Representative compressor power at design conditions: 5.59 kW
The HVAC system serving the supermarket sales area is a central air-handling unit. Heat recovery will be accomplished with a direct-condensing recovery coil inside the air-handling unit, downstream of both the return air duct and the outside air damper. The air-handling unit has the following design parameters:
Design air volume: 25,000 cfm
Design coil face area: 41.7 ft2
To avoid excessive pressure, drop across the recovery coil, the designer will select a coil with a fin density of 10 fins per inch. The heat recovery circuit will use a holdback valve set at 95°F SCT.
What is the procedure for selecting a heat recovery coil?
Answer
To size a heat recovery system, the designer should first establish a design recovery coil capacity by analyzing the refrigeration system from which heat will be recovered. Best practice dictates that the recovery system should be sized to recover most of the available system total heat of rejection at typical operating conditions, not peak conditions. Since we are designing for average operating conditions, the designer assumes the average refrigeration load is 70% of the design load. Therefore, the average system THR for heating design is:
Average System THR = 70% x Design Refrigeration Load x THR Adjustment Factor
where:
THR Adjustments Factor = Representative Compressor THR
Representative Compressor Capacity
and:
Rep. Compressor THR = Rep. Compressor Capacity + Rep. Compressor Heat of Compression
Using values from the example:
Representative Compressor THR = 54.2MBH + (5.50 kW x 3.415 MBH)
kW
Representative Compressor THR = 73.3 MBH
Therefore,
THR Adjustment Factor = 73.3 MBH
54.2 MBH
THR Adjustment Factor = 1.35
Using the values in this example and the calculated THR adjustment factor, the average system THR is:
Average system THR = 70% x 455.8 MBH x1.35
Average system THR = 430.1 MBH
The recovery system will not be capable of extracting 100% of the total heat of rejection since the condenser operates at a lower pressure and will reject additional heat, even if the heat recovery coil achieves full condensing. In addition, the heat recovery coil performance may often be limited by the available airflow across the coil and the consequent temperature rise vs. the heat being transferred. This performance is determined through evaluation of coil performance, considering entering air temperature, and condensing temperature, as well as the coil design (e.g., rows, fins, air velocity and other factors). Airside pressure drop can be minimized by using a larger face area, requiring lower face velocity and fewer rows.
For in this example, it was assumed that after evaluating coil performance, 85% of the average THR could be recovered with a reasonable coil velocity and coil depth.
Available Heat for Reclaim = 85% x Average System THR
Available Heat for Reclaim = 85% x 430.1 MBH
Available heat for Reclaim = 365.6 MBH
The available heat for recovery is the design capacity of the recovery coil we will select for our air-handling unit.
Next, the designer needs to know the face velocity of the airstream in the air-handling unit. The face velocity is:
F.V. = Design cfm
AHU Face Area
F.V. = 25,000 cfm
41.7 ft2
F.V. = 600 ft/min
Finally, the designer needs to know the temperature difference between the condensing temperature (inside the recovery coil) and the temperature of the air entering the recovery coil. Since the coil will be installed in an air-handling unit downstream of the outside air damper, the designer assumes that the air entering the coil is a mix of return air from the store and outside air. The designer must determine an appropriate design temperature for the air entering the recovery coil (entering air temperature or EAT) during average heating hours, which in this instance was determined to be 65°F. From the example, the heat recovery system will have a holdback valve setting of 95°F SCT. Therefore, the temperature difference is:
TD = SCT – EAT
TD = 95oF - 65oF
TD = 30oF
Using the face velocity, design coil capacity, and temperature difference between condensing temperature and entering air temperature, the designer then refers to the air-handling unit catalog to select a recovery coil. Then the designer uses the following two tables
| Heat reclaim correction factor for temperature difference between air and refrigerant. | ||||||||
| Temperature Difference (°F) | 20 | 25 | 30 | 35 | 40 | 45 | 50 | 60 |
|
Correction Factor
|
0.4 | 0.5 | 0.6 | 0.7 | 0.8 | 0.9 | 1.0 | 1.2 |
| Hot Gas Reclaim Heating Capacities MBH per SQ FT of coil face area | ||||
| Rows | FPI | Face Velocity (ft/min) | ||
| 500 | 550 | 600 | ||
| 2 | 8 | 10.9 | 11.38 | 11.85 |
| 10 | 12.15 | 12.73 | 13.18 | |
| 12 | 13.13 | 13.77 | 14.35 | |
| 3 | 8 | 14.56 | 15.25 | 15.9 |
| 10 | 15.93 | 16.8 | 17.63 | |
| 12 | 17.08 | 18.03 | 18.95 | |
| 4 | 8 | 17.43 | 18.47 | 19.47 |
| 10 | 18.75 | 19.92 | 21.07 | |
| 12 | 19.98 | 21.25 | 22.5 | |
The designer enters the first table with the calculated TD of 30°F, finding a correction factor of 0.6. We enter the second table with the value:
MBH per SQ FT = (Design Coil Capacity) / Correction Factor
Coil Face Area
MBH per SQ FT = (4184 MBH) / 0.6
41.7 ft2
MBH per SQ FT = 16.72
Per design requirements, the designer will select a 10-fin-per-inch coil. From the second table, the designer selects the three-row, 10-fin-per-inch coil for this application.
More commonly, computerized selection tools are used to select heat recovery coils, allowing vendors to provide multiple selections for comparison.
In supermarkets, ducting return air from behind display cases or near the floor is beneficial in improving comfort by removing the stagnant cool air that naturally occurs due to product refrigeration cases. This approach also increases the effectiveness of refrigeration heat recovery by increasing the temperature difference between the return air temperature and the refrigerant condensing temperature in the heat recovery coil. Figure 10-24 shows the location of an HVAC return air duct positioned to scavenge cool air from the floor level near refrigerated display cases.
Figure 10-24: Low Return Air Example
Heat recovery can be incorporated into rooftop HVAC units (RTU) by installing the heat recovery coil inside the RTU cabinet or by installing in the return air duct upstream of the RTU, as shown in Figure 10-25. Location inside the RTU is preferable when outside air is a substantial part of the heating load, but location in the return air duct is reasonable and can provide greater flexibility in selecting the heat recovery coil (e.g., for low face velocity and pressure drop), particularly when coupled with low return air on units in the refrigerated space, which predominantly provide heating. The fan design must allow for the additional ductwork and coil pressure drop.
Figure 10-25: Heat Recovery Coil in Return Air Duct
A ducted transfer system is sometimes employed to remove cold air from aisles with refrigerated display cases (rather than blowing warm air into the refrigerated areas) and can be an easy and appropriate way to use heat recovery, particularly from smaller distributed systems. Figure 10-26 depicts a ducted transfer system.
Figure 10-26: Ducted Transfer System
The Energy Code requires that the increase in HFC refrigerant charge from all equipment related to heat recovery for space heating shall be less than 0.35 lbs. for every 1,000 Btuh of heat recovery capacity at design conditions. Refrigerant charge may increase because of the addition of the recovery coil itself (either the refrigerant-to-air heat exchanger for direct configurations, or the refrigerant-to-water heat exchanger for indirect configurations) and the additional piping between the compressor group and the recovery coil. In addition, the refrigerant leaving the recovery coil and entering the refrigerant condenser will be mostly condensed, which increases the charge in the outdoor condenser compared with normal operation. Operating the outdoor condenser at lower pressure (i.e., the required floating heat pressure control) vs. the higher setting at the heat recovery coil holdback valve creates pressure drop, flashing of some liquid to vapor and an increase in velocity due to the much larger volume of a pound of vapor vs. a point of liquid refrigerant. Split condenser control, which is very common in cooler climates, can also be used to close off and pump out half of the outdoor condenser.
It is the responsibility of the system designer to fully understand how the heat recovery system affects overall refrigerant charge.
Example 10-24
Question
A heat recovery system is being designed for a new supermarket. The refrigerant is R-404A. The proposed design is shown below:
Which piping runs should be included in the calculation of refrigerant charge increase in the proposed design?
Answer
Only the additional piping required to route the refrigerant to the heat recovery coil needs to be considered in this calculation. The piping runs shown in red in the following figure should be included in the calculation of refrigerant charge increase from heat recovery.
Example 10-25
Question
What is the refrigerant charge size increase in the example described above?
Answer
The system designer prepares the following analysis to calculate the charge size in the refrigerant piping.
|
|
Saturation Temperature (°F) | Pipe OD (in) | Pipe ID (in) | Pipe Length (ft) | Line Volume (ft³) | % Vapor, Liquid by Mass | % Vapor, Liquid by Volume | Refrigerant Charge (lbs) |
| Discharge Line to Reclaim Coil | 95 | 1 5/8 | 1 1/2 | 100 | 1.2 | 100%, 0% | 100%, 0% | 6.7 |
| Liquid/Vapor Return Line | 80 | 1 3/8 | 1 1/4 | 100 | 0.9 | 9%, 91% | 59%, 41% | 25.5 |
Total Charge: 32.2
The outdoor condenser has a capacity of 350 MBH at a TD of 10°F. Using the manufacturer’s published data, the designer determines that the condenser normal operating charge (without heat recovery) is 26.9 lbs. To calculate the charge, increase in the condenser due to heat reclaim, the designer estimates the condenser could be as much as 75% full of liquid, resulting in a condenser charge of 68.8 lbs. with heat recovery.The heat recovery coil has a capacity of 320 MBH at a design TD of 20°F. The system designer uses manufacturer’s documentation to determine that the heat recovery coil refrigerant charge is 14.1 lbs.
The total refrigerant charge with heat recovery is:
32.2 lbs (piping) + 68.8 lbs (system condenser) + 14.1 lbs (recovery coil) = 115.1 lbs
Therefore, the refrigerant charge increase with heat recovery is: 115.1 lbs – 26.9 lbs = 88.2 lbs
Example 10-26
Question
In the example above, does the recovery design comply with the requirement in the Energy Code that the recovery design shall use at least 25% of the design total heat of rejection (THR) of the refrigeration system?
Answer
The system designer determines that the total THR of all the refrigeration systems in the new supermarket is 800 MBH. From the previous example, the heat recovery capacity is 320 MBH.
100 % x 320 MBH = 40%
800 MBH
Therefore, the design complies with the Energy Code.
Example 10-27
Question
In the example above, does the recovery design comply with the requirement in the Energy Code that the recovery design shall not increase the refrigerant charge size by more than 0.35 lbs. of refrigerant per 1,000 Btuh of recovery capacity?
Answer
From the previous example, the recovery capacity is 320 MBH at design conditions, and the total refrigerant charge size increase is 88.2 lbs.
88.2 lbs = 0.28 lbs/Btuh
320 MBH
Since the refrigerant charge increases by less than 0.35 lbs/MBH, this design complies with the Energy Code.
A typical transcritical CO2 booster system is shown in Figure 10-27 below. The system consists of two suction groups: booster and high stage (HS). The compressors in the booster suction group serve low temperature (LT) loads and discharge into the suction of the high stage suction group. The compressors in the high stage suction group serve the medium temperature (MT) loads, as well as compress the gas from the booster suction group and the intermediate pressure vessel to high pressures. Heat is rejected from the high pressure gas in the gas cooler when the system is operating in supercritical mode. The discharge pressure is commonly controlled by a hold back valve in combination with the gas cooler fans. When operating in subcritical mode the gas cooler operates as a condenser, analogous to other common refrigeration systems. The gas or liquid from the gas cooler/condenser expands in the intermediate pressure vessel/flash tank. The gas from the intermediate pressure vessel is compressed by the high stage compressors, and the liquid from the flash tank is supplied to medium temperature and low temperature evaporators (loads). The evaporated gas in the evaporators is compressed by its respective suction group compressors.
Figure 10-27: Common Transcritical CO2 System Configuration

The critical point of a substance is the point above which the liquid and vapor phases become indistinguishable from each other, forming a “supercritical fluid.” In the supercritical region, temperature and pressure are semi-independent variables. CO2 has a critical point of 87.8°F, which is considered to be a low critical point compared to all commonly used refrigerants. A pressure-enthalpy (PH) diagram for CO2 with its critical point labeled is shown in Figure 10-28. In a transcritical CO2 refrigeration system, the high-stage suction group can operate both above and below the critical point. When ambient temperatures are high, above approximately 75°F, the HS suction group compresses CO2 above its critical point and the system is said to be in supercritical operation. An example of a HS suction group supercritical vapor compression cycle on the PH diagram for CO2 is represented in green in Figure 10-28. During lower ambient conditions, when CO2 is below its critical point after compression, the system is said to be in subcritical operation. An example of a HS suction group subcritical vapor compression cycle on the PH diagram for CO2 is represented in pink in Figure 10-28.
Figure 10-28: Pressure-Enthalpy CO2 Diagram With Transcritical Vapor Compression Cycle (Diagram Created Using REFPROP – NIST Reference Fluid Properties)

In subcritical mode, the system operates very similarly to other refrigeration systems. In supercritical mode, the overall system efficiency decreases compared with subcritical operation. This is because high ambient temperatures result in higher compressor discharge temperatures needed for heat rejection, which increases the suction-to-discharge pressure ratio to be overcome by the compressor. Additionally, when operating in supercritical mode, the gas cooler outlet stream has a higher quality (higher vapor fraction) compared to subcritical mode. Vapor in the intermediate pressure vessel does not contribute to productive refrigeration but needs to be compressed, increasing the nonproductive refrigeration load on the compressors. Available technologies that increase supercritical operation efficiency include gas ejectors and parallel compression.
10.6.1.1 Transcritical CO2 Gas Coolers
New fan-powered gas coolers on all new transcritical CO2 refrigeration systems must follow the gas cooler type, sizing, fan control, and efficiency requirements as described in §120.6(b)5.
Section 120.6(b)5A prohibits the use of air-cooled gas coolers in Climate Zones 10 through 15, which are high ambient temperature climate zones, to reduce the number of supercritical operating hours. Alternatives to air cooled gas coolers include water cooled gas coolers connected to a cooling tower, adiabatic gas coolers, and evaporative gas coolers.
Section 120.6(b)5B and §120.6(b)5C describe minimum sizing requirements for new gas coolers serving new transcritical CO2 refrigeration systems. Fan-powered air-cooled gas coolers are covered by §120.6(b)5B. Fan-powered adiabatic gas coolers are covered by §120.6(b)5C.
Gas coolers must be sized to provide sufficient heat rejection capacity under design conditions while maintaining a specified maximum temperature difference between the gas cooler leaving gas temperature and ambient temperature. The design gas cooler capacity shall be greater than the calculated combined total heat of rejection (THR) of the dedicated compressors that are served by the gas cooler. If multiple gas coolers are specified, then the combined capacity of the installed gas coolers shall be greater than the calculated heat of rejection. When determining the design THR for this requirement, reserve or backup compressors may be excluded from the calculations. Example 10-42 provides an example scenario of which compressors to include in the THR calculation described in this section.
Section 120.6(b)5B provides maximum design gas cooler leaving gas temperature (LGT) values for air-cooled gas coolers. For this section, designers should use the 0.5 percent design dry bulb temperature (DBT) from Table 10-4 – Design Day Data for California Cities in the Reference Joint Appendices JA2. to demonstrate compliance with this requirement.
Standard practice is for published gas cooler ratings to assume the capacity of air-cooled gas coolers is proportional to the temperature difference (TD) between the LGT and DBT, regardless of the actual ambient temperature entering the gas cooler. For example, the capacity of an air-cooled gas cooler operating at a leaving gas temperature of 80°F with a DBT of 70°F is assumed to be equal to the same unit operating at 110°F LGT and 100°F DBT, since the TD across the gas cooler is 10°F in both examples. Thus, the requirement for air-cooled gas coolers is based on the temperature difference between the DBT and gas cooler leaving gas temperature. Air cooled gas coolers shall be sized so the design leaving gas temperature for air-cooled gas coolers shall be less than or equal to the design dry bulb temperature plus 6°F.
Section 120.6(b)5C provides maximum design gas cooler leaving gas temperature (LGT) values for adiabatic gas coolers. For this section, designers should use the 0.5 percent design dry bulb temperature (DBT) from Table 10-4 – Design Day Data for California Cities in the Reference Joint Appendices JA2. to demonstrate compliance with this requirement.
Standard practice is for published gas cooler ratings to assume the capacity of adiabatic gas coolers is proportional to the temperature difference (TD) between the LGT and DBT for operation in dry mode, regardless of the actual ambient temperature entering the gas cooler. For example, the capacity of an adiabatic gas cooler operating at a LGT of 80°F with a DBT of 70°F is assumed to be equal to the same unit operating at 110°F LGT and 100°F DBT during dry mode operation, since the TD across the gas cooler is 10°F in both examples. Thus, similar to air-cooled gas coolers, the requirement for adiabatic gas coolers is based on the temperature difference between the DBT and gas cooler leaving gas temperature. Design leaving gas temperature for adiabatic gas coolers necessary to reject the design total heat of rejection of a refrigeration system assuming dry mode performance shall be less than or equal to the design dry bulb temperature plus 15°F.
Section 120.6(b)5D through §120.6(b)5G describe fan control requirements for new gas coolers serving new transcritical CO2 refrigeration systems. Fan speed control requirements are covered by §120.6(b)5D. Gas cooler pressure control requirements during subcritical and supercritical operation are described by §120.6(b)5E and §120.6(b)5F, respectively. Minimum condensing temperature set point is covered by §120.6(b)5G.
Gas cooler fans for new air-cooled, evaporatively cooled or adiabatic gas coolers, or fans on cooling towers or fluid coolers used to reject heat on new transcritical CO2 refrigeration systems, must use continuously variable speed. Variable-frequency drives are commonly used to provide continuously variable-speed control of gas cooler fans, although controllers designed to vary the speed of electronically commutated motors may be used to control these types of motors. All fans serving a common high side, or cooling water loop for cooling towers and fluid coolers, shall be controlled in unison. Thus, in normal operation, the fan speed of all fans within a single gas cooler or set of gas coolers serving a common high side should modulate together, rather than running fans at different speeds or staging fans off. However, when fan speed is at the minimum practical level usually no higher than 10–20%, the fans may be staged off to reduce gas cooler capacity. As load increases, fans should be turned back on before significantly increasing fan speed, recognizing a control band is necessary to avoid excessive fan cycling.
Section 120.6(b)5E provides pressure control requirements for gas cooler operation below the critical point. These requirements are the same as for §120.6(b)1A with the exception that the minimum condensing temperature set point must be 60°F for transcritical CO2 systems with a design intermediate saturated suction temperature lower than 30°F. See Section 10.4.2.1 for details.
During supercritical mode, the gas cooler pressure set point must be continuously reset in response to ambient conditions to optimize system efficiency, rather than using a fixed set point value.
Specifying the exact relationship to be used to determine the optimal head pressure may depend on several variables beyond ambient air temperature, including the operating saturated suction temperature, system configuration, gas cooler technology type, and current load. The controls manufacturer shall consider the tradeoff between fan energy and compressor energy in developing a pressure and fan control that is responsive to environmental and system conditions.
10.6.1.1.3.4. Minimum SCT Set point
The minimum saturated condensing temperature set point must be 60°F (16°C) or less for air-cooled gas coolers, evaporative-cooled gas coolers, adiabatic gas coolers, air or water-cooled fluid coolers or cooling towers. As a practical matter, a maximum condensing temperature set point is also commonly employed to set an upper bound on the control set point in the event of a sensor failure and to force full gas cooler operation during peak ambient conditions. This value should be set high enough that it does not interfere with normal operation.
Requirements for design leaving gas temperatures relative to design ambient temperatures, as described above for §120.6(b)5B and C, help assure that there is enough gas cooler capacity to keep leaving gas temperatures compressor head pressures at reasonable levels. However, the sizing requirements do not address gas cooler efficiency. For example, rather than providing amply sized gas cooler surface area, a gas cooler selection could consist of a small gas cooler area using a large motor to blow a large amount of air through the heat exchanger surface to achieve the design gas cooler TD. However, this would come at the expense of excessive fan motor horsepower. Also, relatively high fan power consumption can result from using gas cooler fans that have poor fan efficiency or low fan motor efficiency. Section 120.6(b)5H addresses these and other factors affecting gas cooler fan power by setting minimum specific efficiency requirements for gas coolers.
| Condenser Type | Refrigerant Type | Minimum Specific Efficiency | Rating Condition |
| Outdoor Air-Cooled | Transcritical CO 2 | 160 Btuh/Watt | 1400 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature |
| Adiabatic Dry Mode | Transcritical CO 2 | 90 Btuh/Watt | 1100 psig, 100°F Outlet Gas Temperature, 90°F Outdoor Dry bulb Temperature |
Condenser specific efficiency is defined as:
Condenser Specific Efficiency = Total Heat Rejection(THR) Capacity / Input Power
The total heat rejection capacity is at the rating conditions of 100°F outlet gas temperature and 90°F outdoor dry bulb temperature. Input power is the electric input power draw of the gas cooler fan motors (at full speed). The motor power is the manufacturer’s published applied power for the subject equipment, which is not necessarily equal to the motor nameplate rating. Power input for secondary devices shall not be included in the specific efficiency calculation.
As shown in Table 10-6 the Energy Codes have different minimum efficiencies depending on the type of gas cooler that is being used. The different classifications of gas coolers are:
- Outdoor, air-cooled.
- Adiabatic (dry-mode operation).
The data published in the gas cooler manufacturer’s published rating for capacity
and power shall be used to calculate specific efficiency.
For air-cooled and adiabatic gas coolers, manufacturers typically provide the capacity at a given temperature difference (TDR) between SCT and dry bulb temperature. Manufacturers typically assume that gas cooler capacity is linearly proportional to TD; the catalog capacity at 20°F TD is typically twice as much as at 10°F TD. The gas cooler capacity for air-cooled gas cooler at a TD of 10°F shall be used to calculate specific efficiency. For adiabatic gas coolers, the dry mode capacity at a TD of 10°F shall be used to calculate efficiency. If the capacity at 10°F TD is not provided, the capacity shall be scaled linearly.
Depending on the type of gas cooler, the actual manufacturer’s rated motor power may vary from motor nameplate in different ways. Air-cooled gas coolers with direct-drive OEM motors may use far greater input power than the nominal motor horsepower would indicate. Thus, actual motor input power from the manufacturer must be used for direct-drive, air-cooled gas coolers.
Example 10-48 provides an example calculation for the efficiency of a condenser, which is analogous to how the efficiency for a gas cooler would be calculated.