- A minimum aged solar reflectance of 0.63 and a minimum thermal emittance of 0.75; or
- A minimum solar reflectance index (SRI) of 75.
Exception 1 to Section 140.3(a)1Aia: Wood-framed roofs in climate zones 3 and 5 are not required to comply with Section 140.3(a)1Aia if the roof assembly has a U-factor of 0.034 or lower.
Exception 2 to Section 140.3(a)1Aia: Roof constructions with a weight of at least 25 lb/ft² over the roof membrane are not required to comply with Section 140.3(a)1Aia.
Exception 3 to Section 140.3(a)1Aia: An aged solar reflectance less than 0.63 is allowed provided the maximum roof/ceiling U-factor in TABLE 140.3 is not exceeded.
- In climate zones 1 and 3 shall have a minimum aged solar reflectance of 0.20 and a minimum thermal emittance of 0.75, or a minimum SRI of 16.
- In climate zones 2 and 4 through 16 shall have a minimum aged solar reflectance of 0.25 and a minimum thermal emittance of 0.80, or a minimum SRI of 23.
Exception to Section 140.3(a)1Aiia: Roof constructions with a weight of at least 25 lb/ft² over the roof membrane.
TABLE 140.3 Roof/Ceiling Insulation Tradeoff For Aged Solar Reflectance – Nonresidential Buildings
Aged Solar Reflectance | Metal Building Climate Zone 1-16 U-factor | Wood framed and Other Climate Zone 6 - 8 U-factor | Wood Framed and Other All Other Climate Zones U-factor |
0.62-0.56 | 0.038 | 0.045 | 0.032 |
0.55-0.46 | 0.035 | 0.042 | 0.030 |
0.45-0.36 | 0.033 | 0.039 | 0.029 |
0.35-0.25 | 0.031 | 0.037 | 0.028 |
Exception to Section 140.3(a)1A: Roof area covered by building integrated photovoltaic panels and building integrated solar thermal panels are not required to meet the minimum requirements for solar reflectance, thermal emittance, or SRI.
Exception to Section 140.3(a)5A: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception 1 to Section 140.3(a)5B: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception 2 to Section 140.3(a)5B: For vertical windows containing chromogenic type glazing:
For purposes of this paragraph, the relative solar heat gain coefficient, RSHGC, of a vertical window is:
Exception 1 to Section 140.3(a)5C: An area-weighted average relative solar heat gain coefficient of 0.56 or less shall be used for windows:
a. That are in the first story of exterior walls that form a display perimeter; and
b. For which codes restrict the use of overhangs to shade the windows.
Exception 2 to Section 140.3(a)5C: For vertical glazing containing chromogenic type glazing:
i. the lower-rated labeled RSHGC shall be used with automatic controls to modulate the amount of heat flow into the space in multiple steps in response to daylight levels or solar intensity; and
ii. chromogenic glazing shall be considered separately from other glazing; and
iii. area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Exception 3 to Section 140.3(a)5C: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Note: Demising walls are not exterior walls, and therefore windows in demising walls are not subject to SHGC requirements.
Exception 1 to Section 140.3(a)5D: When the window’s primary and secondary sidelit daylit zones are completely overlapped by one or more skylit daylit zones, then the window need not comply with Section 140.3(a)5D.
Exception 2 to Section 140.3(a)5D: If the window’s VT is not within the scope of NFRC 200, or ASTM E972, then the VT shall be calculated according to Reference Nonresidential Appendix NA6.
Exception 3 to Section 140.3(a)5D: For vertical glazing containing chromogenic type glazing:
i. The higher-rated labeled VT shall be used with automatic controls to modulate the amount of light transmitted into the space in multiple steps in response to daylight levels or solar intensity; and
ii. Chromogenic glazing shall be considered separately from other glazing; and
iii. Area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Exception 4 to Section 140.3(a)5D: Conditioned greenhouses. The requirements of Section 120.6(h)4 apply.
Note: Demising walls are not exterior walls, and therefore windows in demising walls are not subject to VT requirements.
RSHGC = SHGC × [1 + a × (2.72-PF – 1) × (sin(b × Az) + c]
where:
Feature | a | b | c |
Overhang | 0.150 | 0.008727 | 5.67 |
Exterior Horizontal Slat | 0.144 | 0.008727 | 5.13 |
RSHGC = Relative Solar Heat Gain Coefficient.
SHGC = Solar Heat Gain Coefficient of the vertical fenestration.
Az = Azimuth of the vertical fenestration in degrees.
PF = Projection factor as calculated by Equation 140.3-C.
VT ≥ 0.11/ WWR
where:
WWR = Window Wall Ratio, the ratio of (i) the total window area of the entire building to (ii) the total gross exterior wall area of the entire building. If the WWR is greater than 0.40, then 0.40 shall be used as the value for WWR in Equation 140.3-B.
VT = Visible Transmittance of framed window.
Exception 1 to Section 140.3(a)6A: Buildings with atria over 55 feet high shall have a skylight area no greater than 10 percent of the gross exterior roof area.
Exception 2 to Section 140.3(a)6A: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception 1 to Section 140.3(a)6B: For skylights containing chromogenic type glazing:
i. The lower-rated labeled U-factor shall be used with automatic controls to modulate the amount of heat flow into the space in multiple steps in response to daylight levels or solar intensity; and
ii. chromogenic glazing shall be considered separately from other glazing; and
iii. area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Exception 2 to Section 140.3(a)6B: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception 1 to Section 140.3(a)6C: For skylights containing chromogenic type glazing:
i. the lower-rated labeled SHGC shall be used to demonstrate compliance with this section; and
ii. chromogenic glazing shall be considered separately from other glazing; and
iii. area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Exception 2 to Section 140.3(a)6C: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception 1 to Section 140.3(a)6D: For skylights containing chromogenic type glazing:
i. the higher-rated labeled VT shall be used with automatic controls to modulate the amount of light transmitted into the space in multiple steps in response to daylight levels or solar intensity and;
ii. chromogenic glazing shall be considered separately from other glazing; and
iii. area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Exception 2 to Section 140.3(a)6D: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception 1 to Section 140.3(a)6E: Skylights designed and installed to exclude direct sunlight entering the occupied space by the use of fixed or automated baffles or the geometry of the skylight and light well.
Exception 2 to Section 140.3(a)6E: Conditioned greenhouses. The requirements of Section 120.6(h)3 apply.
Exception to Section 140.3(a)9Bi: Materials in Table 140.3-A shall be deemed to comply with Section 140.3(a)9B provided that all joints are sealed and all of the materials are installed as air barriers in accordance with the manufacturer's instructions.
Exception to Section 140.3(a)9Bii: The following materials shall be deemed to comply with Section 140.3(a)9B if all joints are sealed and all of the materials are installed as air barriers in accordance with the manufacturer's instructions:
a. Concrete masonry walls that have at least two coatings of paint or at least two coatings of sealer coating.
b. Concrete masonry walls with integral rigid board insulation.
c. Structurally insulated panels.
d. Portland cement or Portland sand parge, or stucco, or a gypsum plaster, each with minimum 1/2 inch thickness.
b. For buildings that have more than 50,000 ft2 of conditioned floor area, a sectional test method of co-pressurizing representative test floors and taking data from the specific floors to achieve the requirement in Section 140.3(a)9Ci when following the procedures in Sections NA5.2 to NA5.7. Representative test floors must meet the following conditions:
I. The entire floor area of all stories that have any spaces directly under a roof.
II. The entire floor area of all stories that have a building entrance or loading dock.
III. Representative above grade wall sections of the building totaling at least 25 percent of the wall area enclosing the remaining conditioned space. Floor areas in parts a and b above shall not be included in the 25 percent.
MATERIALS | MINIMUM THICKNESS |
Plywood | Minimum 3/8inches thickness |
Oriented strand board | Minimum 3/8 inches thickness |
Extruded polystyrene insulation board | Minimum 1/2 inches thickness |
Foil-backed polyisocyanurate insulation board | Minimum 1/2 inches thickness |
Closed cell spray foam with a minimum density of 2.0 pcf | Minimum 2 inches thickness |
Open cell spray foam with a density no less than 0.4 pcf and no greater than 1.5 pcf | Minimum 5-1/2 inches thickness |
Exterior and interior gypsum board | Minimum 1/2 inches thickness |
Cement board | Minimum 1/2 inches thickness |
Built up roofing membrane | No minimum thickness |
Modified bituminous roof membrane | No minimum thickness |
Fully adhered single-ply roof membrane | No minimum thickness |
A Portland cement or Portland sand parge, or a gypsum plaster | Each with Minimum 5/8 inches thickness |
Cast-in-place concrete, or precast concrete | No minimum thickness |
Fully grouted concrete block masonry | No minimum thickness |
Sheet steel or sheet aluminum | No minimum thickness |
Envelope Feature | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
Roofs and Ceilings - Metal Building Max U-Factor |
0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 | 0.038 |
Roofs and Ceilings - Wood Framed and Other Max U-Factor |
0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.047 | 0.047 | 0.047 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 |
Walls - Metal Building Max U-Factor |
0.098 | 0.053 | 0.098 | 0.053 | 0.053 | 0.098 | 0.098 | 0.053 | 0.053 | 0.053 | 0.053 | 0.053 | 0.053 | 0.053 | 0.050 | 0.053 |
Walls - Metal-framed Max U-Factor |
0.060 | 0.055 | 0.071 | 0.055 | 0.055 | 0.060 | 0.060 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 | 0.055 |
Walls - Mass, Light¹ Max U-Factor |
0.170 | 0.138 | 0.227 | 0.196 | 0.364 | 0.364 | 0.364 | 0.364 | 0.364 | 0.138 | 0.138 | 0.138 | 0.138 | 0.138 | 0.138 | 0.138 |
Walls - Mass, Heavy² Max U-Factor |
0.211 | 0.650 | 0.650 | 0.650 | 0.650 | 0.690 | 0.690 | 0.690 | 0.690 | 0.650 | 0.160 | 0.211 | 0.184 | 0.160 | 0.160 | 0.153 |
Walls - Wood-framed and Other Max U-Factor |
0.078 | 0.053 | 0.102 | 0.053 | 0.095 | 0.102 | 0.102 | 0.095 | 0.053 | 0.053 | 0.042 | 0.053 | 0.053 | 0.053 | 0.038 | 0.053 |
Floors and Soffits - Raised Mass Max U-Factor |
0.092 | 0.092 | 0.269 | 0.269 | 0.269 | 0.269 | 0.269 | 0.269 | 0.269 | 0.269 | 0.092 | 0.092 | 0.092 | 0.092 | 0.092 | 0.058 |
Floors and Soffits - Other Max U-Factor |
0.048 | 0.039 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.071 | 0.039 | 0.071 | 0.071 | 0.039 | 0.039 | 0.039 |
Roofing Products - Low Sloped Aged Solar Reflectance |
0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 | 0.63 |
Roofing Products - Low-Sloped Thermal Emittance |
0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 |
Roofing Products - Steep-Sloped Aged Solar Reflectance |
0.20 | 0.25 | 0.20 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 |
Roofing Products - Steep-Sloped Thermal Emittance |
0.75 | 0.80 | 0.75 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 | 0.80 |
Air Barrier | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ |
Fenestration – Vertical (All Climate Zones) | CZ 1 | CZ 2 | CZ3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
Fixed Window (Max U-factor) | 0.36 | 0.36 | 0.36 | 0.36 | 0.36 | 0.36 | 0.36 | 0.36 | 0.34 | 0.36 | 0.34 | 0.34 | 0.34 | 0.34 | 0.34 | 0.36 |
Fixed Window (Max RSHGC) | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.25 | 0.22 | 0.25 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.25 |
Fixed Window (Min VT) | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 | 0.42 |
Curtain Wall or Storefront (Max U-factor) | 0.38 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.38 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 |
Curtain Wall or Storefront (Max RSHGC) | 0.25 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.25 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 | 0.26 |
Curtain Wall or Storefront (Min VT) | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 |
Operable Window (Max U-factor) | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 | 0.46 |
Operable Window (Max RSHGC) | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 | 0.22 |
Operable Window (Min VT) | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 | 0.32 |
Glazed Doors (Max U-factor) | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 | 0.45 |
Glazed Doors (Max RSHGC) | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 |
Glazed Doors (Min VT) | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 | 0.17 |
Fenestration (Max WWR %) | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% |
Exterior Doors - Non-Swinging Maximum U-Factor | 0.50 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 0.50 |
Exterior Doors – Swinging Maximum U-Factor | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 |
CONTINUED: TABLE 140.3-B – PRESCRIPTIVE ENVELOPE CRITERIA FOR NONRESIDENTIAL BUILDINGS (INCLUDING RELOCATABLE PUBLIC SCHOOL BUILDINGS WHERE MANUFACTURER CERTIFIES USE ONLY IN SPECIFIC CLIMATE ZONE; NOT INCLUDING HIGH-RISE RESIDENTIAL BUILDINGS AND GUEST ROOMS OF HOTEL/MOTEL BUILDINGS)
Fenestration - Skylights (all Climate Zones) (Area-weighted Performance Rating) |
Glass Curb Mounted |
Glass Deck Mounted |
Plastic Curb Mounted |
Tubular Daylighting Devices (TDDs) | |
Max U-factor | 0.58 | 0.46 | 0.88 | 0.88 | |
Max SHGC | 0.25 | 0.25 | NR | NR | |
Min VT (Min VTannual for TDDs) | 0.49 | 0.49 | 0.64 | 0.38 | |
Maximum SRR% | 5% | 5% | 5% | 5% |
Envelope Feature | Climate Zones | |||||||||||||||
CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 | |
Roofs and Ceilings - Metal Building Max U-Factor | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 | 0.041 |
Roofs and Ceilings - Wood Framed and Other Max U-Factor | 0.028 | 0.028 | 0.034 | 0.028 | 0.034 | 0.034 | 0.039 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 | 0.028 |
Walls - Metal Building Max U-Factor | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.061 | 0.057 | 0.057 | 0.057 | 0.057 | 0.057 | 0.057 |
Walls - Metal-framed Max U-Factor | 0.069 | 0.069 | 0.069 | 0.069 | 0.069 | 0.069 | 0.105 | 0.069 | 0.069 | 0.069 | 0.069 | 0.069 | 0.069 | 0.069 | 0.048 | 0.069 |
Walls - Mass, Light¹ Max U-Factor | 0.170 | 0.170 | 0.170 | 0.170 | 0.170 | 0.227 | 0.227 | 0.227 | 0.196 | 0.170 | 0.170 | 0.170 | 0.170 | 0.170 | 0.170 | 0.170 |
Walls - Mass, Heavy¹ Max U-Factor | 0.160 | 0.160 | 0.160 | 0.184 | 0.211 | 0.690 | 0.690 | 0.690 | 0.690 | 0.690 | 0.184 | 0.253 | 0.211 | 0.184 | 0.184 | 0.160 |
Walls - Wood-framed and Other Max U-Factor | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.059 | 0.042 | 0.059 | 0.059 | 0.042 | 0.042 | 0.042 |
Floors and Soffits - Raised Mass Max U-Factor | 0.045 | 0.045 | 0.058 | 0.058 | 0.058 | 0.069 | 0.092 | 0.092 | 0.092 | 0.069 | 0.058 | 0.058 | 0.058 | 0.045 | 0.058 | 0.037 |
Floors and Soffits - Other Max U-Factor | 0.034 | 0.034 | 0.039 | 0.039 | 0.039 | 0.039 | 0.071 | 0.039 | 0.039 | 0.039 | 0.039 | 0.039 | 0.039 | 0.034 | 0.039 | 0.034 |
Low Sloped Roofing Products Aged Solar Reflectance | NR | NR | NR | NR | NR | NR | NR | NR | 0.55 | 0.55 | 0.55 | NR | 0.55 | 0.55 | 0.55 | NR |
Low Sloped Roofing Products Thermal Emittance | NR | NR | NR | NR | NR | NR | NR | NR | 0.75 | 0.75 | 0.75 | NR | 0.75 | 0.75 | 0.75 | NR |
Steep Sloped Roofing Products Aged Solar Reflectance | NR | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | NR |
Steep Sloped Roofing Products Thermal Emittance | NR | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | 0.75 | NR |
Air Barrier | REQ | REQ | REQ | REQ | REQ | REQ | NR | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ |
Non-Swinging Exterior Doors Max U-Factor | 0.50 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 1.45 | 0.50 |
Swinging Exterior Doors Max U-Factor | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 | 0.70 |
CONTINUED: TABLE 140.3-C – PRESCRIPTIVE ENVELOPE CRITERIA FOR GUEST ROOMS OF HOTEL/MOTEL BUILDINGS
Fenestration – Vertical (All Climate Zones) (Area-Weighted Performance Rating) |
Fixed Window |
Operable Window |
Curtainwall and Storefront |
Glazed Doors* |
Max U-factor | 0.36 | 0.46 | 0.41 | 0.45 |
Max RSHGC | 0.25 | 0.22 | 0.26 | 0.23 |
Min VT | 0.42 | 0.32 | 0.46 | 0.17 |
Maximum WWR% | 40% | 40% | 40% | 40% |
CONTINUED: TABLE 140.3-C – PRESCRIPTIVE ENVELOPE CRITERIA FOR GUEST ROOMS OF HOTEL/MOTEL BUILDINGS
Fenestration - Skylights (All Climate Zones) (Area-Weighted Performance Rating) |
Glass Curb Mounted |
Glass Deck Mounted |
Plastic Curb Mounted |
Max U-factor | 0.58 | 0.46 | 0.88 |
Max SHGC | 0.25 | 0.25 | NR |
Min VT | 0.49 | 0.49 | 0.64 |
Maximum SRR% | 5% | 5% | 5% |
Notes:
b. As defined in Section 100.1, light mass walls are walls with a heat capacity of at least 7.0 Btu/ft²-°F and less than 15.0 Btu/ft²-°F. Heavy mass walls are walls with a heat capacity of at least 15.0 Btu/ft²-°F.
c. Glazed Doors applies to both site-built and to factory-assembled glazed doors.
Envelope Feature | Criteria | Value |
Roofs and Ceilings - Metal Buildings | Maximum U-factor | 0.041 |
Roofs and Ceilings - Non-Metal Buildings | Maximum U-factor | 0.034 |
Walls - Wood frame buildings | Maximum U-factor | 0.042 |
Walls - Metal frame buildings | Maximum U-factor | 0.057 |
Walls - Metal buildings | Maximum U-factor | 0.052 |
Walls - Mass/7.05 HC | Maximum U-factor | 0.170 |
Walls - All Other Walls | Maximum U-factor | 0.059 |
Floors and Soffits | Maximum U-factor | 0.048 |
Roofing Products - Low-Sloped | Aged Solar Reflectance | 0.63 |
Roofing Products - Low-Sloped | Thermal Emittance | 0.75 |
Roofing Products - Steep-Sloped | Aged Solar Reflectance | 0.25 |
Roofing Products - Steep-Sloped | Thermal Emittance | 0.80 |
Fenestration - Windows | Maximum U-factor | 0.47 |
Fenestration - Windows | Maximum SHGC | 0.26 |
Fenestration - Glazed Doors
(Site-Built and Factory Assembled) |
Maximum U-factor | 0.45 |
Fenestration - Glazed Doors
(Site-Built and Factory Assembled) |
Maximum SHGC | 0.23 |
Fenestration - Skylights
Glass with Curb |
Maximum U-factor | 0.99 |
Fenestration - Skylights
Glass with Curb |
Maximum SHGC | 0.57 |
Fenestration - Skylights
Glass without Curb |
Maximum U-factor | 0.87 |
Fenestration -Skylights - Glass Type | 0-2% SRR
Maximum SHGC |
0.46 |
Fenestration -Skylights - Glass Type | 2.1-5% SRR
Maximum SHGC |
0.36 |
Fenestration -Skylights - Plastic Type | 0-2% SRR
Maximum SHGC |
0.69 |
Fenestration -Skylights - Plastic Type | 2.1-5% SRR
Maximum SHGC |
0.57 |
Exterior Doors - Non-Swinging doors | Maximum U-factor | 0.50 |
Exception to Section 140.3(d)2D: Where it is documented that existing adjacent structures or natural objects within view of the vertical fenestration block direct sunlight onto the vertical fenestration between 8 a.m. and 5 p.m. for less than 500 daytime hours per year.
Exception to Section 140.3(d)3E: Where it is documented that existing adjacent structures or natural objects within view of the vertical fenestration block direct sunlight onto the vertical fenestration between 8 a.m. and 5 p.m. for less than 750 daytime hours per year.
TABLE 140.3-E Daylighting Devices
Daylighting Device
|
Orientation of the Vertical Fenestration
|
Projection Factor
|
Horizontal Slats
|
East or West
|
2.0 to 3.0
|
Interior Light Shelf
|
South
|
1.0 to 2.0
|
Exterior Light Shelf
|
South |
0.25 to 1.25
|
EQUATION 140.3-C PROJECTION AND DISTANCE FACTOR CALCULATION
Projection Factor = Projection / Spacing
Distance Factor – D / (HAS x Projection Factor)
Where:
Projection = The horizontal distance between the base edge and the projected edge of the overhang, slat, or light shelf..
Spacing = For overhangs, the vertical distance between the projected edge of the overhang and sill of the vertical fenestration below it.
For horizontal slats, the vertical distance between the projected edge of a slat to the base edge of the slat below it.
For interior light shelves, the vertical distance between the projected edge of the light shelf and head of the clerestory fenestration above it.
For exterior light shelves, the vertical distance between the projected edge of the light shelf and sill of the vertical fenestration below it.
D = Distance between the existing structure or nature object and the fenestration
HAS = Height difference between the top of the existing structure or nature object and the bottom of the fenestration
NOTE: The base edge is the edge of an overhang, slat, or light shelf that is adjacent to the vertical fenestration. The projected edge is the opposite edge from the base edge.