A building complies with this section by being designed with and having constructed and installed a space-conditioning system that meets the applicable prescriptive requirements of Subsections (a) through (q).
In making equipment sizing calculations under Subsection (a), all of the following rules shall apply:

Where
FPAadj = The corrected fan power allowance for the component in w/cfm
Qcomp = The airflow through component in cfm
Qsys = The fan system airflow in cfm
FPAcomp = The fan power allowance of the component from Table 140.4A or Table 140.4B
Airflow
|
Multi-Zone VAV Systems
≤5,000 cfm1 |
Multi-Zone VAV Systems >5,000 and ≤10,000 cfm1
|
Multi-Zone VAV Systems >10,000 cfm1
|
All Other Fan Systems ≤5,000 cfm
|
All Other Fan
Systems >5,000 and ≤10,000 cfm |
All Other Fan Systems>10,000 cfm
|
Supply System Base Allowance for AHU serving spaces ≤ 6 floors away).
|
0.395
|
0.453
|
0.413
|
0.232
|
0.256
|
0.236
|
Supply system base allowance for AHU serving spaces > 6 floors away
|
0.508
|
0.548
|
0.501
|
0.349
|
0.356
|
0.325
|
MERV 13 to MERV 16 Filter upstream of thermal conditioning equipment (two times the clean filter pressure drop)2
|
0.136
|
0.114
|
0.105
|
0.139
|
0.120
|
0.107
|
MERV 13 to MERV 16 Final filter downstream of thermal conditioning equipment. ( two times the clean filter pressure drop)2
|
0.225
|
0.188
|
0.176
|
0.231
|
0.197
|
0.177
|
Filtration allowance for > MERV 16 or HEPA Filter ( two times the clean filter pressure drop)2
|
0.335
|
0.280
|
0.265
|
0.342
|
0.292
|
0.264
|
Central Hydronic heating coil allowance
|
0.046
|
0.048
|
0.052
|
0.046
|
0.050
|
0.054
|
Electric heat allowance
|
0.046
|
0.038
|
0.035
|
0.046
|
0.040
|
0.036
|
Gas heat allowance
|
0.069
|
0.057
|
0.070
|
0.058
|
0.060
|
0.072
|
Hydronic/DX cooling coil or heat pump coil (wet) allowance3
|
0.135
|
0.114
|
0.105
|
0.139
|
0.120
|
0.107
|
Solid or liquid Desiccant system allowance
|
0.157
|
0.132
|
0.123
|
0.163
|
0.139
|
0.124
|
Reheat Coil for Dehumidification Allowance
|
0.045
|
0.038
|
0.035
|
0.046
|
0.040
|
0.036
|
Allowance for Evaporative humidifier/cooler in series with a cooling coil. Value shown is allowed watts/cfm per 1.0 Inches of water gauge (in.w.g.) Determine pressure loss (in.w.g.) at 400 fpm or maximum velocity allowed by the manufacturer, whichever is less. [Calculation required, see note 4]
|
0.224
|
0.188
|
0.176
|
0.231
|
0.197
|
0.177
|
Allowance for 100% Outdoor air system5.
|
0.000
|
0.000
|
0.000
|
0.070
|
0.100
|
0.107
|
Energy recovery allowance for 0.50 ≤ ERR <0.556
|
0.135
|
0.114
|
0.105
|
0.139
|
0.120
|
0.107
|
Energy recovery allowance for 0.55 ≤ ERR <0.606
|
0.160
|
0.134
|
0.124
|
0.165
|
0.141
|
0.126
|
Energy recovery allowance for 0.60 ≤ ERR <0.656
|
0.184
|
0.155
|
0.144
|
0.190
|
0.163
|
0.146
|
Energy recovery allowance for 0.65 ≤ ERR <0.706
|
0.208
|
0.175
|
0.163
|
0.215
|
0.184
|
0.165
|
Energy recovery allowance for 0.70 ≤ ERR <0.756
|
0.232
|
0.196
|
0.183
|
0.240
|
0.205
|
0.184
|
Energy recovery allowance for 0.75 ≤ ERR <0.806
|
0.257
|
0.216
|
0.202
|
0.264
|
0.226
|
0.203
|
Energy recovery allowance for ERR ≥ 0.806
|
0.281
|
0.236
|
0.222
|
0.289
|
0.247
|
0.222
|
Coil Runaround Loop
|
0.135
|
0.114
|
0.105
|
0.139
|
0.120
|
0.107
|
Allowance for Gas phase filtration. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. [Calculation required, see note 4]
|
0.224
|
0.188
|
0.176
|
0.231
|
0.197
|
0.177
|
Economizer Return Damper
|
0.045
|
0.038
|
0.035
|
0.046
|
0.040
|
0.036
|
Air blender allowance
|
0.045
|
0.038
|
0.035
|
0.046
|
0.040
|
0.036
|
Sound attenuation section [fans serving spaces with design background noise goals below NC35]
|
0.034
|
0.029
|
0.026
|
0.035
|
0.030
|
0.027
|
Deduction for systems that feed a terminal unit with a fan with electrical input power < 1kW
|
-0.100
|
-0.100
|
-0.100
|
-0.100
|
-0.100
|
-0.100
|
Low-turndown single-zone VAV fan systems meeting the requirements in note 7.
|
0.000
|
0.000
|
0.000
|
0.070
|
0.100
|
0.089
|
Footnotes to Table 140.4-A
1. See Section 100.1 for the definition of FAN SYSTEM, MULTI-ZONE VARIABLE AIR VOLUME (VAV).
2. Filter fan power allowance can only be counted once per fan system, except fan systems in healthcare facilities, which can claim one of the MERV 13 to 16 filter allowances and the HEPA filter allowance if both are included in the fan system.
3. Healthcare facilities can claim this fan power allowance twice per fan system where coil design leaving air temperature is less than 44 ⁰F.
4. Power allowance requires further calculation by multiplying the actual inches of water gauge (in.w.g.) of the device/ component by the watts/ cfm in Table 140.4-A.
5. The 100% outdoor air system must serve 3 or more HVAC zones and airflow during non-economizer operating periods must not exceed 135% of minimum requirements in Section 120.1(c)3
6. Enthalpy Recovery Ratio (ERR) calculated per ANSI/ASHRAE 84-2020.
7. A low-turndown single-zone VAV fan system must be capable of and configured to reduce airflow to 50 percent of design airflow and use no more than 30 percent of the design wattage at that airflow. No more than 10 percent of the design load served by the equipment shall have fixed loads.
Airflow
|
Multi-Zone VAV Systems1 ≤5,000 cfm
|
Multi-Zone VAV Systems1 >5,000 and ≤10,000 cfm
|
Multi-Zone VAV Systems1 >10,000 cfm
|
All Other Fan Systems ≤5,000 cfm
|
All Other Fan Systems >5,000 and ≤10,000 cfm
|
All Other Fan Systems >10,000 cfm
|
Exhaust System Base Allowance
|
0.221
|
0.246
|
0.236
|
0.186
|
0.184
|
0.190
|
Filter (any MERV value)2
|
0.046
|
0.041
|
0.036
|
0.046
|
0.041
|
0.035
|
Energy Recovery Allowance For 0.50 ≤ ERR <0.55 3
|
0.139
|
0.120
|
0.107
|
0.139
|
0.123
|
0.109
|
Energy Recovery Allowance For 0.55 ≤ ERR <0.60 3
|
0.165
|
0.142
|
0.126
|
0.165
|
0.144
|
0.128
|
Energy Recovery Allowance For 0.60 ≤ ERR <0.65 3
|
0.190
|
0.163
|
0.146
|
0.191
|
0.166
|
0.148
|
Energy Recovery Allowance For 0.65 ≤ ERR <0.70 3
|
0.215
|
0.184
|
0.165
|
0.216
|
0.188
|
0.167
|
Energy Recovery Allowance For 0.70 ≤ ERR <0.75 3
|
0.240
|
0.206
|
0.184
|
0.241
|
0.209
|
0.186
|
Energy Recovery Allowance For 0.75 ≤ ERR <0.80 3
|
0.265
|
0.227
|
0.203
|
0.266
|
0.231
|
0.205
|
Energy Recovery Allowance For ERR ≥ 0.80 3
|
0.289
|
0.248
|
0.222
|
0.291
|
0.252
|
0.225
|
Coil Runaround Loop
|
0.139
|
0.120
|
0.107
|
0.139
|
0.123
|
0.109
|
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms
|
0.116
|
0.100
|
0.089
|
0.116
|
0.102
|
0.091
|
Return and/or exhaust airflow control devices required for space pressurization control
|
0.116
|
0.100
|
0.089
|
0.116
|
0.102
|
0.091
|
Laboratory and vivarium exhaust systems in high-rise buildings for vertical duct exceeding 75 ft. Value shown is allowed w/cfm per 0.25 in. wg for each 100 feet exceeding 75 feet. [Calculation required, see note 4]
|
0.058
|
0.051
|
0.045
|
0.058
|
0.052
|
0.046
|
Biosafety cabinet. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. [Calculation required, see note 4]
|
0.231
|
0.198
|
0.177
|
0.232
|
0.202
|
0.179
|
Exhaust filters, scrubbers, or other exhaust treatment required by code or standard. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. [Calculation required, see note 4]
|
0.231
|
0.198
|
0.177
|
0.232
|
0.202
|
0.179
|
Healthcare facility allowance5
|
0.231
|
0.198
|
0.177
|
0.232
|
0.202
|
0.179
|
Sound attenuation section [Fans serving spaces with design background noise goals below NC35.]
|
0.035
|
0.030
|
0.027
|
0.035
|
0.031
|
0.028
|
Footnotes to Table 140.4-B
1. See FAN SYSTEM, MULTI-ZONE VARIABLE AIR VOLUME (VAV) in definitions for Multizone to be classified as a Multi-Zone VAV System.
2. Filter pressure loss can only be counted once per fan system.
3. Enthalpy Recovery Ratio (ERR) calculated per ANSI/ASHRAE 84-2020.
4. Power allowance requires further calculation, multiplying the actual pressure drop (in. wg.) of the device/ component by the watts/cfm in the Table 140.4-B.
5. This allowance can only be taken for healthcare facilities.
Altitude (ft)
|
Correction Factor
|
<3,000
|
1.000
|
≥3,000 and <4,000
|
0.896
|
≥4,000 and <5,000
|
0.864
|
≥5,000 and <6,000
|
0.832
|
≥6,000
|
0.801
|
Motor Nameplate HP
|
Default Fan kWdesign with variable speed drive (Fan kWdesign)
|
Default Fan kWdesign without variable speed drive(Fan kWdesign)
|
<1
|
0.96
|
0.89
|
≥1 and <1.5
|
1.38
|
1.29
|
≥1.5 and <2
|
1.84
|
1.72
|
≥2 and <3
|
2.73
|
2.57
|
≥3 and <5
|
4.38
|
4.17
|
≥5 and <7.5
|
6.43
|
6.15
|
≥7.5 and <10
|
8.46
|
8.13
|
≥10 and <15
|
12.47
|
12.03
|
≥15 and <20
|
16.55
|
16.04
|
≥20 and <25
|
20.58
|
19.92
|
≥25 and <30
|
24.59
|
23.77
|
≥30 and <40
|
32.74
|
31.70
|
≥40 and <50
|
40.71
|
39.46
|
≥50 and <60
|
48.50
|
47.10
|
≥60 and <75
|
60.45
|
58.87
|
≥75 and ≤100
|
80.40
|
78.17
|
Footnotes to TABLE 140.4-D:
1. This table cannot be used for Motor Nameplate Horsepower values greater than 100.
2. This table is to be used only with motors with a service factor ≤1.15. If the service factor is not provided, this table may not be used.
Climate Zones
|
Total Building Chilled Water System Capacity, Minus Capacity of the Cooling units with Air Economizers
| |
Building Water-Cooled Chilled Water System
|
Air-Cooled Chilled Water Systems or District Chilled Water Systems
| |
15
|
≥ 960,000 Btu/h (280 kW)
|
≥ 1,250,000 Btu/h (365 kW)
|
1-14
|
≥720,000 Btu/h (210 kW)
|
≥940,000 Btu/h (275 kW)
|
16
|
≥1,320,000 Btu/h (385 kW)
|
≥1,720,000 Bu/h (505 kW)
|
Climate Zone | Efficiency Improvement a | a If a unit is rated with an annualized or part-load metric, then to eliminate the required economizer, only the applicable minimum cooling efficiency of the unit must be increased by the percentage shown. If the unit is only rated with a full load metric, like EER or COP cooling, then that metric must be increased by the percentage shown. To determine the efficiency required to eliminate the economizer, when the unit equipment efficiency is rated with an energy-input divided by work-output metric, the metric shall first be converted to COP prior to multiplying by the efficiency improvement percentage and then converted back to the rated metric. |
1 | 70% | |
2 | 65% | |
3 | 65% | |
4 | 65% | |
5 | 70% | |
6 | 30% | |
7 | 30% | |
8 | 30% | |
9 | 30% | |
10 | 30% | |
11 | 30% | |
12 | 30% | |
13 | 30% | |
14 | 30% | |
15 | 30% | |
16 | 70% |
EXCEPTION to Section 140.4(e)2A: Systems that provide 75 percent of the annual energy used for mechanical heating from site-recovered energy or a site-solar energy source.
Device Typea |
Required High Limit (Economizer Off When): |
||
Equationb |
Description |
||
Fixed Dry Bulb |
1, 3, 5, 11-16 |
TOA > 75°F |
Outdoor air temperature exceeds 75°F |
2, 4, 10 |
TOA > 73°F |
Outdoor air temperature exceeds 73°F |
|
6, 8, 9 |
TOA > 71°F |
Outdoor air temperature exceeds 71°F |
|
7 |
TOA > 69°F |
Outdoor air temperature exceeds 69°F |
|
Differential Dry Bulb |
1, 3, 5, 11-16 |
TOA > TRA°F |
Outdoor air temperature exceeds return air temperature |
2, 4, 10 |
TOA > TRA-2°F |
Outdoor air temperature exceeds return air temperature minus 2°F |
|
6, 8, 9 |
TOA > TRA-4°F |
Outdoor air temperature exceeds return air temperature minus 4°F |
|
7 |
TOA > TRA-6°F |
Outdoor air temperature exceeds return air temperature minus 6°F |
|
Fixed Enthalpyc + Fixed Drybulb |
All |
hOA > 28 Btu/lbc or TOA > 75°F |
Outdoor air enthalpy exceeds 28 Btu/lb of dry airc or Outdoor air temperature exceeds 75°F |
a Only the high limit control devices listed are allowed to be used and at the setpoints listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy, and Differential Enthalpy Controls, may not be used in any Climate Zone for compliance with Section 140.4(e)1 unless approval for use is provided by the Energy Commission Executive Director. b Devices with selectable (rather than adjustable) setpoints shall be capable of being set to within 2°F and 2 Btu/lb of the setpoint listed. c At altitudes substantially different than sea level, the Fixed Enthalpy limit value shall be set to the enthalpy value at 75°F and 50% relative humidity. As an example, at approximately 6,000 foot elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb. |
Cooling Capacity
|
Minimum Number of Mechanical Cooling Stages
|
Minimum Compressor Displacement
|
≥ 65,000 Btu/h and
< 240,000 Btu/h |
3 stages
|
≤ 35% full load
|
≥ 240,000 Btu/h
|
4 stages
|
≤ 25% full load
|
EXCEPTION 1 to Section 140.4(h)1: Heat rejection devices included as an integral part of the equipment listed in TABLE 110.2-A through TABLE 110.2-N.
EXCEPTION 2 to Section 140.4(h)1: Condenser fans serving multiple refrigerant circuits.
EXCEPTION 3 to Section 140.4(h)1: Condenser fans serving flooded condensers.
EXCEPTION 4 to Section 140.4(h)1: Up to one third of the fans on a condenser or tower with multiple fans where the lead fans comply with the speed control requirement.
EXCEPTION 1 to Section 140.4(h)3: Cooling towers that are ducted (inlet or discharge) or have an external sound trap that requires external static pressure capability.
EXCEPTION 2 to Section 140.4(h)3: Cooling towers that meet the energy efficiency requirement for propeller fan towers in Section 110.2, Table 110.2-F.
EXCEPTION 1 to Section 140.4(h)5: Replacement of existing cooling towers that are inside an existing building or on an existing roof.
EXCEPTION 2 to Section 140.4(h)5: Cooling towers serving buildings in Climate Zone 1 or 16.
EXCEPTION 1 to Section 140.4(k)1: Systems that include no more than three control valves.
EXCEPTION 2 to Section 140.4(k)1: Systems having a total pump system power less than or equal to 1.5 hp.
EXCEPTION 1 to Section 140.4(k)4: Hydronic systems that use variable flow to reduce pumping energy in accordance with Section 140.4(k)1.
EXCEPTION 2 to Section 140.4(k)4: Systems serving healthcare facilities.
EXCEPTION 1 to Section 140.4(k)6: Heating hot water systems.
EXCEPTION 2 to Section 140.4(k)6: Condenser water systems serving only water-cooled chillers.
EXCEPTION to Section 140.4(k)7: Where a system loop temperature optimization controller is used to determine the most efficient operating temperature based on real-time conditions of demand and capacity, deadbands of less than 20°F shall be allowed.
EXCEPTION 1 to Section 140.4(k)8: Where 25 percent of the annual space heating requirement is provided by on-site renewable energy, site-recovered energy, or heat recovery chillers.
EXCEPTION 2 to Section 140.4(k)8: Space heating boilers installed in individual dwelling units.
EXCEPTION 3 to Section 140.4(k)8: Where 50 percent or more of the design heating load is served using perimeter convective heating, radiant ceiling panels or both.
EXCEPTION 4 to Section 140.4(k)8: Individual gas boilers with input capacity less than 300,000 Btu/h shall not be included in the calculations of the total system input or total system efficiency.
Cooling System Type
|
Fan Motor Size
|
Cooling Capacity
|
DX Cooling
|
any
|
≥ 65,000 Btu/hr
|
Chilled Water and Evaporative
|
≥ 1/4 HP
|
any
|
% Outdoor Air at Full Design Airflow
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
≥10% and <20%
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
≥20% and <30%
|
≥15,000
|
≥20,000
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
≥18,500
|
≥18,500
|
≥18,500
|
≥18,500
|
≥18,500
|
≥18,500
|
≥30% and <40%
|
≥13,000
|
≥15,000
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
≥15,000
|
≥15,000
|
≥15,000
|
≥15,000
|
≥15,000
|
≥15,000
|
≥40% and <50%
|
≥10,000
|
≥12,000
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
≥22,000
|
≥10,000
|
≥10,000
|
≥10,000
|
≥10,000
|
≥10,000
|
≥10,000
|
≥50% and <60%
|
≥9,000
|
≥10,000
|
NR
|
≥18,500
|
NR
|
NR
|
NR
|
NR
|
NR
|
≥17,000
|
≥8,000
|
≥8,000
|
≥8,000
|
≥8,000
|
≥8,000
|
≥8,000
|
≥60% and <70%
|
≥7,000
|
≥7,500
|
NR
|
≥16,500
|
NR
|
NR
|
NR
|
NR
|
≥20,000
|
≥15,000
|
≥7,000
|
≥7,000
|
≥7,000
|
≥7,000
|
≥7,000
|
≥7,000
|
≥70% and <80%
|
≥6,500
|
≥7,000
|
NR
|
≥15,000
|
NR
|
NR
|
NR
|
NR
|
≥17,000
|
≥14,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥80%
|
≥4,500
|
≥6,500
|
NR
|
≥14,000
|
NR
|
NR
|
NR
|
NR
|
≥15,000
|
≥13,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
NOTES to Table 140.4-J:
1. Flow rates in Table 140.4-J represent the design supply fan airflow rate in CFM.
2. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.
% Outdoor Air at Full Design Airflow
|
1
|
2
|
3
|
4
|
5
|
6
|
7
|
8
|
9
|
10
|
11
|
12
|
13
|
14
|
15
|
16
|
≥10% and <20%
|
≥10,000
|
≥10,000
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
NR
|
≥40,000
|
≥40,000
|
≥20,000
|
≥10,000
|
≥10,000
|
≥10,000
|
≥10,000
|
≥20% and <30%
|
≥2,000
|
≥5,000
|
≥13,000
|
≥9,000
|
≥9,000
|
NR
|
NR
|
NR
|
NR
|
≥15,000
|
≥15,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥5,000
|
≥30% and <40%
|
≥2,000
|
≥3,000
|
≥10,000
|
≥6,500
|
≥6,500
|
NR
|
NR
|
NR
|
≥15,000
|
≥7,500
|
≥7,500
|
≥3,000
|
≥3,000
|
≥3,000
|
≥3,000
|
≥3,000
|
≥40% and <50%
|
≥2,000
|
≥2,000
|
≥8,000
|
≥6,000
|
≥6,000
|
NR
|
NR
|
NR
|
≥12,000
|
≥6,000
|
≥6,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥50% and <60%
|
≥2,000
|
≥2,000
|
≥7,000
|
≥6,000
|
≥6,000
|
NR
|
NR
|
≥20,000
|
≥10,000
|
≥5,000
|
≥5,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥60% and <70%
|
≥2,000
|
≥2,000
|
≥6,000
|
≥6,000
|
≥6,000
|
NR
|
NR
|
≥18,000
|
≥9,000
|
≥4,000
|
≥4,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥70% and <80%
|
≥2,000
|
≥2,000
|
≥6,000
|
≥5,000
|
≥5,000
|
NR
|
NR
|
≥15,000
|
≥8,000
|
≥3,000
|
≥3,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥80%
|
≥2,000
|
≥2,000
|
≥6,000
|
≥5,000
|
≥5,000
|
NR
|
NR
|
≥12,000
|
≥7,000
|
≥3,000
|
≥3,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
≥2,000
|
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code