Multifamily buildings, including both dwelling units and common use areas, that comply with the prescriptive standards shall be designed, constructed and equipped to meet all of the requirements for the appropriate climate zone shown in Table 170.2-A. In Table 170.2-A, NA (not allowed) means that feature is not permitted in a particular climate zone and NR (no requirement) means that there is no prescriptive requirement for that feature in a particular climate zone. Installed components shall meet the following requirements:
Note: Demising walls are not exterior walls, and therefore demising wall area is not part of the gross exterior wall area, and fenestration in demising walls is not part of the fenestration area limitation.
Vertical fenestration in demising walls between conditioned and unconditioned spaces is only required to comply with the area-weighted average U-factor requirement in Table 170.2-A.
Exception 1 to Section 170.2(a)3Aii: For each dwelling unit, up to 3 square feet of new glazing area installed in doors shall not be required to meet the U-factor and RSHGC requirements of Table 170.2-A.
Exception 2 to Section 170.2(a)3Aii: For fenestration containing chromogenic type glazing:
-
The lower-rated labeled U-factor and SHGC shall be used with automatic controls to modulate the amount of solar gain and light transmitted into the space in multiple steps in response to daylight levels or solar intensity;
-
Chromogenic glazing shall be considered separately from other fenestration; and
-
Area-weighted averaging with other fenestration that is not chromatic shall not be permitted and shall be determined in accordance with Section 110.6(a).
Exception 3 to Section 170.2(a)3Aii: For dwelling units containing unrated site-built fenestration that meets the maximum area restriction, the U-factor and SHGC can be determined in accordance with the Nonresidential Reference Appendix NA6 or using default values in Table 110.6-A and Table 110.6-B.
Exception 4 to Section 170.2(a)3Aii: Fenestration in dwelling units of buildings in climate zones 1, 3, 5 and 16, is not required to comply with the RSHGC requirements.
Exception 5 to Section 170.2(a)3Aii: Fenestration in dwelling units is not required to comply with the VT requirements.
For the purposes of this paragraph, the RSHGC of a vertical window is:
Exception 1 to Section 170.2(a)3Aiiib: An area-weighted average relative solar heat gain coefficient of 0.56 or less shall be used for windows:
-
That are in the first story of exterior walls that form a display perimeter; and
-
For which codes restrict the use of overhangs to shade the windows.
Exception 2 to Section 170.2(a)3Aiiib: For vertical glazing containing chromogenic type glazing:
-
the lower-rated labeled RSHGC shall be used with automatic controls to modulate the amount of heat flow into the space in multiple steps in response to daylight levels or solar intensity; and
-
chromogenic glazing shall be considered separately from other glazing; and
-
area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Note: Demising walls are not exterior walls, and therefore fenestration in demising walls is not subject to SHGC requirements.
RSHGC = SHGC × [1 + a × (2.72-PF– 1) × (sin(b × Az) + c)]
Where:
Component | a | b | c |
Overhang | 0.150 | 0.008727 | 5.67 |
Exterior Horizontal Slat | 0.144 | 0.008727 | 5.13 |
RSHGC = Relative Solar Heat Gain Coefficient.
SHGC = Solar Heat Gain Coefficient of the vertical fenestration.
Az = Azimuth of the vertical fenestration I degrees.
PF = Projection factor as calculated by Equation 140.3-D.
Exception 1 to Section 170.2(a)3Aiv: When the window’s primary and secondary sidelit daylit zones are completely overlapped by one or more skylit daylit zones, then the window need not comply with Section 170.2(a)3Aiv.
Exception 2 to Section 170.2(a)3Aiv: If the window’s VT is not within the scope of NFRC 200 or ASTM E972, then the VT shall be calculated according to Reference Nonresidential Append ix NA6.
Exception 3 to Section 170.2(a)3Aiv: For vertical windows containing chromogenic type glazing:
-
The higher rated labeled VT shall be used with automatic controls to modulate the amount of light transmitted into the space in multiple steps in response to daylight levels or solar intensity;
-
Chromogenic glazing shall be considered separately from other glazing; and
-
Area-weighted averaging with other glazing that is not chromogenic shall not be permitted.
Exception 4 to Section 170.2(a)3Aiv: Fenestration in dwelling units is not required to comply with the VT requirements.
Note: Demising walls are not exterior walls, and therefore windows in demising walls are not subject to VT requirements.
VT ≥ 0.11/ WWR
Where:
WWR = Window Wall Ratio, the ratio of (i) the total window area of the entire building to (ii) the total gross exterior wall area of the entire building. If the WWR is greater than 0.40, then 0.40 shall be used as the value for WWR in Equation 170.2-B.
VT = Visible Transmittance of framed window.
Exception 1 to Section 170.2(a)3Bi: Buildings with an atrium over 55 feet high shall have a skylight area no greater than 10 percent of the gross exterior roof area.
Exception 2 to Section 170.2(a)3Bii: For each dwelling unit up to 16 square feet of new skylight area with a maximum U-factor of 0.55 and a maximum SHGC of 0.30.
Exception to Sections 170.2(a)3Bii and 170.2(a)3Biii: For skylights containing chromogenic type glazing:
Exception to Section 170.2(a)3Biv: Skylights designed and installed to exclude direct sunlight entering the occupied space by the use of fixed or automated baffles or the geometry of the skylight and light well.
Building Component - Roofs and Ceilings |
CZ 1 |
CZ 2 |
CZ 3 |
CZ 4 |
CZ 5 |
CZ 6 |
CZ 7 |
CZ 8 |
CZ 9 |
CZ 10 |
CZ 11 |
CZ 12 |
CZ 13 |
CZ 14 |
CZ 15 |
CZ 16 |
Option B9 Below Roof Deck Insulation 1,2 (with air space) |
NR |
NR |
NR |
R19 |
NR |
NR |
NR |
R19 |
R19 |
R13 |
R19 |
R19 |
R19 |
R19 |
R19 |
R13 |
Option B9 Ceiling Insulation |
R 38 |
R 38 |
R 30 |
R 38 |
R 30 |
R 30 |
R 30 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
Option B9 Radiant Barrier |
NR |
REQ |
REQ |
NR |
REQ |
REQ |
REQ |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
Option B9 Low-Slope-Aged Solar Reflectance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0.63 |
NR |
0.63 |
NR |
Option B9 Low-Sloped-Thermal Emittance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0.75 |
NR |
0.75 |
NR |
Option B9 Low-Sloped-Solar Reflectance Index |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
75 |
NR |
75 |
NR |
Option B9 Steep-Sloped-Aged Solar Reflectance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0.25 |
0.25 |
0.20 |
0.25 |
0.20 |
0.25 |
NR |
Option B9 Steep-Sloped-Thermal Emittance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0. 75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
NR |
Option B9 Steep-Sloped-Solar Reflectance Index |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
23 |
23 |
16 |
23 |
16 |
23 |
NR |
Option C10-Ceiling Insulation |
R 38 |
R 30 |
R 30 |
R 30 |
R 30 |
R 30 |
R 30 |
R 30 |
R 30 |
R 30 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
R 38 |
Option C10-Radiant Barrier |
NR |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
REQ |
NR |
Option C10 Low-Sloped-Aged Solar Reflectance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0.63 |
NR |
0.63 |
NR |
Option C10 Low-Sloped-Thermal Emittance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0.75 |
NR |
0.75 |
NR |
Option C10 Low-Sloped-Solar Reflectance Index |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
75 |
NR |
75 |
NR |
Option C10 Steep-Sloped-Aged Solar Reflectance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
NR |
Option C10 Steep-Sloped-Thermal Emittance |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
0. 75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
NR |
Option C10 Steep-Sloped-Solar Reflectance Index |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
16 |
16 |
16 |
16 |
16 |
16 |
NR |
Option D11-Metal Building U-factor |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
0.041 |
Option D11-Wood Framed and Other U-factor |
0.028 |
0.028 |
0.034 |
0.028 |
0.034 |
0.034 |
0.039 |
0.028 |
0.028 |
0.028 |
0.028 |
0.028 |
0.028 |
0.028 |
0.028 |
0.028 |
Option D11 Low-Sloped-Aged Solar Reflectance |
NR |
0.63 |
NR |
0.63 |
NR |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
0.63 |
NR |
Option D11 Low-Sloped-Thermal Emittance |
NR |
0.75 |
NR |
0.75 |
NR |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
NR |
Option D11 Low-Sloped-Solar Reflectance Index |
NR |
75 |
NR |
75 |
NR |
75 |
75 |
75 |
75 |
75 |
75 |
75 |
75 |
75 |
75 |
NR |
Option D11 Steep-Sloped-Aged Solar Reflectance |
NR |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
NR |
Option D11 Steep-Sloped-Thermal Emittance |
NR |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
0.75 |
NR |
Option D Steep-Sloped-Solar Reflectance Index |
NR |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
16 |
NR |
TABLE 170.2-A ENVELOPE COMPONENT PACKAGE – Multifamily Standard Building Design (continued)
Building Component - Walls, Floors, Doors, and QII |
CZ 1 |
CZ 2 |
CZ 3 |
CZ 4 |
CZ 5 |
CZ 6 |
CZ 7 |
CZ 8 |
CZ 9 |
CZ 10 |
CZ 11 |
CZ 12 |
CZ 13 |
CZ 14 |
CZ 15 |
CZ 16 |
Walls - Metal Building - Any Fire Rating |
0.061 |
0.061 |
0.061 |
0.061 |
0.061 |
0.061 |
0.061 |
0.061 |
0.061 |
0.061 |
0.057 |
0.057 |
0.057 |
0.057 |
0.057 |
0.057 |
Walls - Framed (wood, metal) and other - >1hr fire rating |
0.059 |
0.059 |
0.059 |
0.059 |
0.059 |
0.065 |
0.065 |
0.059 |
0.059 |
0.059 |
0.051 |
0.059 |
0.059 |
0.051 |
0.051 |
0.051 |
Walls - Framed (wood, metal) and other - ≤1hr fire rating3 |
0.051 |
0.051 |
0.051 |
0.051 |
0.051 |
0.065 |
0.065 |
0.051 |
0.051 |
0.051 |
0.051 |
0.051 |
0.051 |
0.051 |
0.051 |
0.051 |
Walls - Mass Light4,5 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.077 R 13 |
U 0.059 R 17 |
Walls - Mass Heavy |
0.253 |
0.650 |
0.650 |
0.650 |
0.650 |
0.690 |
0.690 |
0.690 |
0.690 |
0.650 |
0.184 |
0.253 |
0.211 |
0.184 |
0.184 |
0.160 |
Floors/Soffits - Slab Perimeter8 |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
NR |
F 0.58 R 7.0 |
Floors/Soffits – Wood Framed |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
U 0.037 R 19 |
Floors/Soffits - Raised Mass |
U 0.092 R 8.0 |
U 0.092 R 8.0 |
U 0.269 R 0 |
U 0.269 R 0 |
U-0.269 R 0 |
U 0.269 R 0 |
U 0.269 R 0 |
U 0.269 R 0 |
U 0.269 R 0 |
U 0.269 R 0 |
U 0.092 R 8.0 |
U 0.138 R 4.0 |
U 0.092 R 8.0 |
U 0.092 R 8.0 |
U 0.138 R 4.0 |
U 0.092 R 8.0 |
Floors/Soffits - Other |
0.048 |
0.039 |
0.071 |
0.071 |
0.071 |
0.071 |
0.071 |
0.071 |
0.071 |
0.071 |
0.039 |
0.071 |
0.071 |
0.039 |
0.039 |
0.039 |
Exterior Doors6 - Max U- Factor Dwelling Unit Entry |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
0.20 |
Exterior Doors6 - Max U-Factor Common Use Area Entry Non-Swinging |
0.50 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
1.45 |
0.50 |
Exterior Doors6 - Max U-Factor Common Use Area Entry Swinging |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
0.70 |
Quality Insulation Installation up to 3 habitable stories |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
NR |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
TABLE 170.2-A ENVELOPE COMPONENT PACKAGE – Multifamily Standard Building Design (continued)11
Building Component - Fenestration | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
Curtain Wall/ Storefront7 - Maximum U-factor | 0.38 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.38 |
Curtain Wall/ Storefront7 - Maximum RSHGC |
NR |
0.26 |
NR |
0.26 |
NR |
0.26 |
0.26 |
0.26 |
0.26 |
0.26 |
0.26 |
0.26 |
0.26 |
0.25 |
0.26 |
NR |
Curtain Wall/ Storefront7 - Minimum VT, common use area |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
0.46 |
NAFS 2017 Performance Class AW5 - Maximum U-factor | 0.38 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.40 | 0.38 |
NAFS 2017 Performance Class AW5 - Maximum RSHGC | NR | 0.24 | NR | 0.24 | NR | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | 0.24 | NR |
NAFS 2017 Performance Class AW5 - Minimum VT, common use areas |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
0.37 |
All Other Fenestration - Maximum U- factor | 0.28 | 0.30 | 0.28 | 0.28 | 0.28 | 0.34 | 0.34 | 0.34 | 0.30 | 0.30 | 0.28 | 0.30 | 0.28 | 0.28 | 0.28 | 0.28 |
All Other Fenestration - Maximum RSHGC | NR | 0.23 | NR | 0.23 | NR | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | 0.23 | NR |
Maximum Window to Floor Ratio | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% | 20% |
Maximum Window to Wall Ratio | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% | 40% |
Maximum Skylight Roof Ratio | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% | 5% |
Exception to Section 170.2(c)3BiaI: Systems that cannot conform to the specifications for hole location in Reference Residential Appendix Figure RA3.2-1, shall not be required to provide holes as described in Figure RA3.2-1.
Exception to Section 170.2(c)3BiaII: Standard ducted systems without zoning dampers may comply with the minimum airflow rate by meeting the applicable requirements in Table 160.3-A and Table 160.3-B as confirmed by field verification and diagnostic testing in accordance with the procedures in Reference Residential Appendix Sections RA3.1.4.4 and RA3.1.4.5. The design clean-filter pressure drop requirements of Section 160.2(b)1D for the system air filter device(s) shall conform to the requirements given in Table 160.3-A and Table 160.3-B.
Exception to Section 170.2(c)3BiaIII: When the outdoor temperature is less than 55 degrees F and the installer utilizes the weigh-in charging procedure in Reference Residential Appendix Section RA3.2.3.1 to verify the refrigerant charge, the installer may elect to utilize the verification procedure in Reference Residential Appendix RA3.2.3.2. If the verification procedure in Section RA3.2.3.2 is used for compliance, the system's thermostat shall conform to the specifications in Section 110.12. Ducted systems shall comply with the minimum system airflow rate requirement in Section 170.2(c)3BiaII.
Exception 1 to Section 170.2(c)3Bi: Packaged systems for which the manufacturer has verified correct system refrigerant charge prior to shipment from the factory are not required to have refrigerant charge confirmed through field verification and diagnostic testing. The installer of these packaged systems shall certify that the packaged system was precharged at the factory and has not been altered in a way that would affect the charge. Ducted systems shall comply with minimum system airflow rate requirement in Section 170.2(c)3Bib, provided that the system is of a type that can be verified using the procedure specified in RA3.3 or an approved alternative in RA1.
Exception 2 to Section 170.2(c)3Bi: The field verification and ECC-Provider data registry requirements of Reference Residential Appendix RA2 and RA3 are not required for multifamily dwelling units in buildings four habitable stories and greater. The installer shall certify that diagnostic testing was performed in accordance with the applicable procedures.
Note: Gas heating appliances installed in conditioned spaces must meet the combustion air requirements of California Mechanical Code Chapter 7, as applicable.
These measures shall be confirmed through field verification in accordance with the procedures in RA3.7.4.4 for buildings with three habitable stories or less, or the procedures in NA2.2.4.1.5 for buildings with four or more habitable stories.
These measures shall be field verified in accordance with NA7.18.4.
Exception to Section 170.2(c)3B: The field verification and ECC-Provider data registry requirements of Reference Residential Appendix RA2 and RA3 are not required for multifamily dwelling units in buildings four habitable stories and greater. The installer shall certify that diagnostic testing was performed in accordance with the applicable procedures.
FPAadj= Qcomp/Qsys X FPAcomp
Where:
FPAadj = The correct/ed fan power allowance for the component in w/cfm
Qcomp = The airflow through component in cfm
Qsys = The fan system airflow in cfm
FPAcomp = The fan power allowance of the component from Table 170.2-B or Table 170.2-C
Component | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm |
Supply System Base Allowance for AHU Serving Spaces ≤ 6 Floors Away | 0.395 | 0.453 | 0.413 | 0.232 | 0.256 | 0.236 |
Supply System Base Allowance for AHU Serving Spaces > 6 Floors Away | 0.508 | 0.548 | 0.501 | 0.349 | 0.356 | 0.325 |
MERV 13 to MERV 16 Filter Upstream of Thermal Conditioning Equipment (two times the clean filter pressure drop)* | 0.136 | 0.114 | 0.105 | 0.139 | 0.120 | 0.107 |
MERV 13 to MERV 16 Final Filter Downstream of Thermal Conditioning Equipment (two times the clean filter pressure drop)* | 0.225 | 0.188 | 0.176 | 0.231 | 0.197 | 0.177 |
Filtration Allowance for > Merv 16 or HEPA Filter (two times the clean filter pressure drop)* | 0.335 | 0.280 | 0.265 | 0.342 | 0.292 | 0.264 |
Central Hydronic Heating Coil Allowance | 0.046 | 0.048 | 0.052 | 0.046 | 0.050 | 0.054 |
Electric Heat Allowance | 0.046 | 0.038 | 0.035 | 0.046 | 0.040 | 0.036 |
TABLE 170.2-B: Supply Fan Power Allowances (watts/cfm)(continued)
Component | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm |
Gas Heat Allowance | 0.069 | 0.057 | 0.070 | 0.058 | 0.072 | 0.060 |
Hydronic/DX Cooling Coil, or Heat Pump (oil) wet Allowance | 0.135 | 0.114 | 0.105 | 0.139 | 0.120 | 0.107 |
Solid or Liquid Desiccant System Allowance | 0.157 | 0.132 | 0.123 | 0.163 | 0.139 | 0.124 |
Reheat Coil for Dehumidification Allowance | 0.045 | 0.038 | 0.035 | 0.046 | 0.040 | 0.036 |
Allowance for evaporative humidifier/cooler in series with a cooling coil. Value shown is allowed w/cfm per 1.0 in. w.g. Determine pressure loss (in. wg) at 400 fpm or maximum velocity allowed by the manufacturer, whichever is less. (Calculation required, see note 4) | 0.224 | 0.188 | 0.176 | 0.231 | 0.197 | 0.177 |
Allowance for 100% outdoor air system meeting the requirements of Note 5. | 0.000 | 0.000 | 0.000 | 0.070 | 0.100 | 0.107 |
Energy Recovery Allowance for 0.50 ≤ ERR ≤0.55 * | 0.135 | 0.114 | 0.105 | 0.139 | 0.120 | 0.107 |
Energy Recovery Allowance for 0.55 ≤ ERR ≤0.60 * | 0.160 | 0.134 | 0.124 | 0.165 | 0.141 | 0.126 |
Energy Recovery Allowance for 0.60 ≤ ERR ≤0.65 * | 0.184 | 0.155 | 0.144 | 0.190 | 0.163 | 0.146 |
Energy Recovery Allowance for 0.65 ≤ ERR ≤0.70 * | 0.208 | 0.175 | 0.163 | 0.215 | 0.184 | 0.165 |
Energy Recovery Allowance for 0.70 ≤ ERR ≤0.75 * | 0.232 | 0.196 | 0.183 | 0.240 | 0.205 | 0.184 |
Energy Recovery Allowance for 0.75 ≤ ERR ≤0.80 * | 0.257 | 0.216 | 0.202 | 0.264 | 0.226 | 0.203 |
Energy Recovery Allowance for ERR ≥0.80 * | 0.281 | 0.236 | 0.222 | 0.289 | 0.247 | 0.222 |
Coil Runaround Loop | 0.135 | 0.114 | 0.105 | 0.139 | 0.120 | 0.107 |
Allowance for gas phase filtration required by code or accredited standard. Value shown is allowed w/cfm per 1.0 in. w.g. of pressure drop. (Calculation required, see note 4) | 0.224 | 0.188 | 0.176 | 0.231 | 0.197 | 0.177 |
TABLE 170.2-B: Supply Fan Power Allowances (watts/cfm)(continued)
Component | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm |
Economizer/Return Damper | 0.045 | 0.038 | 0.035 | 0.035 | 0.046 | 0.036 |
Air Blender Allowance | 0.045 | 0.038 | 0.035 | 0.046 | 0.040 | 0.036 |
Allowance for sound attenuation section (fans serving spaces with design background noise goals below RC35) | 0.034 | 0.029 | 0.026 | 0.035 | 0.030 | 0.027 |
Deduction for systems that feed a terminal unit with a fan with electrical input power < 1kW | -0.100 | -0.100 | -0.100 | -0.100 | -0.100 | -0.100 |
Low-turndown single-zone VAV fan systems meeting the requirements in note 7. | 0.000 | 0.000 | 0.000 | 0.070 | 0.100 | 0.089 |
Footnote to TABLE 170.2-B
1. See FAN SYSTEM, MULTI-ZONE VARIABLE AIR VOLUME (VAV) in definition a Multi-Zone VAV System. 2. Filter fan power allowance can only be counted once per fan system. 3. RESERVED. 4. Power allowance requires further calculation by multiplying the actual in. wg . of the device/ component by the watts/ cfm in Table 170.2-B. 5. The 100% outdoor air system must serve 3 or more HVAC zones and airflow during non-economizer operating periods must not exceed 135% of minimum requirements in Section 120.1(c)3 . 6. Energy Recovery Ratio (ERR) calculated per ANSI/ASHRAE 84-2020. 7. A low-turndown single-zone VAV fan system must be capable of and configured to reduce airflow to 50 percent of design airflow and use no more than 30 percent of the design wattage at that airflow. No more than 10 percent of the design load served by the equipment shall have fixed loads. |
Component | Multi-Zone VAV Systems | All Other Fan Systems | ||||
≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | |
Exhaust System Base Allowance | 0.221 | 0.246 | 0.236 | 0.186 | 0.184 | 0.190 |
Filter (any MERV value)* | 0.046 | 0.041 | 0.036 | 0.046 | 0.041 | 0.035 |
Energy Recovery Allowance for 0.50 ≤ ERR < 0.55 * | 0.139 | 0.120 | 0.107 | 0.139 | 0.123 | 0.109 |
Energy Recovery Allowance for 0.55 ≤ ERR < 0.60 * | 0.165 | 0.142 | 0.126 | 0.165 | 0.144 | 0.128 |
Energy Recovery Allowance for 0.60 ≤ ERR < 0.65 * | 0.190 | 0.163 | 0.146 | 0.191 | 0.166 | 0.148 |
Energy Recovery Allowance for 0.65 ≤ ERR < 0.70 * | 0.215 | 0.184 | 0.165 | 0.216 | 0.188 | 0.167 |
Energy Recovery Allowance for 0.70 ≤ ERR < 0.75 * | 0.240 | 0.206 | 0.184 | 0.241 | 0.209 | 0.186 |
Energy Recovery Allowance for 0.75 ≤ ERR < 0.80 * | 0.265 | 0.227 | 0.203 | 0.266 | 0.231 | 0.205 |
Energy Recovery Allowance for ERR ≥ 0.80 * | 0.289 | 0.248 | 0.222 | 0.291 | 0.252 | 0.225 |
Coil Runaround Loop | 0.139 | 0.120 | 0.107 | 0.139 | 0.123 | 0.109 |
TABLE 170.2-C: Exhaust, Return, Relief, Transfer Fan Power Allowances (WATT/CFM)(continued)
Component | Multi-Zone VAV Systems | All Other Fan Systems | ||||
≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | ≤5,000 cfm | >5,000 and ≤10,000 cfm | >10,000 cfm | |
Return or exhaust systems required by code or accreditation standards to be fully ducted, or systems required to maintain air pressure differentials between adjacent rooms | 0.116 | 0.100 | 0.089 | 0.116 | 0.102 | 0.091 |
Return and/or exhaust airflow control devices required for space pressurization control | 0.116 | 0.100 | 0.089 | 0.116 | 0.102 | 0.091 |
Laboratory and vivarium exhaust systems in high-rise buildings for vertical duct exceeding 75 ft. Value shown is allowed w/cfm per 0.25 in. wg for each 100 feet exceeding 75 feet. (Calculation required, see note 4) | 0.058 | 0.051 | 0.045 | 0.058 | 0.052 | 0.046 |
Biosafety cabinet. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. (Calculation required, see note 4) | 0.231 | 0.198 | 0.177 | 0.232 | 0.202 | 0.179 |
Exhaust filters, scrubbers, or other exhaust treatment required by code or standard. Value shown is allowed w/cfm per 1.0 in. wg air pressure drop. (Calculation required, see note 4) | 0.231 | 0.198 | 0.177 | 0.232 | 0.202 | 0.179 |
Sound attenuation section (Fans serving spaces with design background noise goals below NC35.) | 0.035 | 0.030 | 0.027 | 0.035 | 0.031 | 0.028 |
Footnote to TABLE 170.2-C:
1. For requirements to be classified as a Multi-Zone VAV System see definition for Multi-Zone Variable Air Volume Fan System. 2. Filter pressure loss can only be counted once per fan system. 3. Energy Recovery Ratio (ERR) calculated per ANSI/ASHRAE 84-2020. 4. Power allowance requires further calculation, multiplying the actual pressure drop (in. wg .) of the device/ component by the watts/cfm in the Table 170.2-C |
Altitude (ft) | Correction factor |
<3,000 | 1.000 |
≥3,000 and <4,000 | 0.896 |
≥4,000 and <5,000 | 0.864 |
≥5,000 and <6,000 | 0.832 |
≥6,000 | 0.801 |
Motor Nameplate HP | Default Fan kWinput with variable speed drive (Fan kWVSD) | Default Fan kWinput without variable speed drive (Fan kWconst) |
< 1 | 0.96 | 0.89 |
≥ 1 and < 1.5 | 1.38 | 1.29 |
≥ 1.5 and < 2 | 1.84 | 1.72 |
≥ 2 and < 3 | 2.73 | 2.57 |
≥ 3 and < 5 | 4.38 | 4.17 |
≥ 5 and < 7.5 | 6.43 | 6.15 |
≥ 7.5 and < 10 | 8.46 | 8.13 |
≥ 10 and < 15 | 12.47 | 12.03 |
≥ 15 and < 20 | 16.55 | 16.04 |
≥ 20 and < 25 | 20.58 | 19.92 |
≥ 25 and < 30 | 24.59 | 23.77 |
≥ 30 and < 40 | 32.74 | 31.70 |
≥ 40 and < 50 | 40.71 | 39.46 |
≥ 50 and < 60 | 48.50 | 47.10 |
≥ 60 and < 75 | 60.45 | 58.87 |
≥ 75 and < 100 | 80.40 | 78.17 |
Footnote to TABLE 170.2-E:
1. This table cannot be used for Motor Nameplate Horsepower values greater than 100. 2. This table is to be used only with motors with a service factor ≤1.15. If the service factor is not provided, this table may not be used. |
- 50 percent of the peak primary airflow; or
- The design zone outdoor airflow rate as specified by Section 160.2(c)3.
- 30 percent of the peak primary airflow; or
- The design zone outdoor airflow rate as specified by Section 160.2(c)3.
Exception 1 to Section 170.2(c)4B: Zones with special pressurization relationships or cross-contamination control needs.
Exception 2 to Section 170.2(c)4B: Zones served by space-conditioning systems in which at least 75 percent of the energy for reheating, or providing warm air in mixing systems, is provided from a site-recovered or site-solar energy source.
Exception 3 to Section 170.2(c)4B: Zones in which specific humidity levels are required to satisfy exempt process loads. Computer rooms or other spaces where the only process load is from IT equipment may not use this exception.
Exception 4 to Section 170.2(c)4B: Zones with a peak supply-air quantity of 300 cfm or less.
Exception1 to Section 170.2(c)4Ci: Where special outside air filtration and treatment, for the reduction and treatment of unusual outdoor contaminants, makes compliance infeasible.
Exception 2 to Section 170.2(c)4Ci: Where the use of outdoor air for cooling will affect other systems, such as humidification or dehumidification, so as to increase overall building LSC energy use.
Exception 3 to Section 170.2(c)4Ci: Systems serving dwelling units.
Exception 4 to Section 170.2(c)4Ci: Where comfort cooling systems have the cooling efficiency that meets or exceeds the cooling efficiency improvement requirements in Table 170.2-F.
Exception 5 to Section 170.2(c)4Ci: Fan systems primarily serving computer rooms. See Section 140.9(a) for computer room economizer requirements.
Exception 6 to Section 170.2(c)4Ci: In all climate zones, each air handler that has a design total mechanical cooling capacity less than 54,000 Btu/hr where ventilation is provided by a dedicated outdoor air system (DOAS) with exhaust air heat recovery in accordance with Section 140.4(p) and the following:
A. The DOAS unit shall meet the exhaust air heat recovery ratio as specified in Section 140.4(q)1 and include bypass or control to disable energy recovery as specified in Section 140.4(q)2.
B. The DOAS unit shall provide at least the minimum ventilation air flow rate as specified in Section 120.1(c)3 and provide no less than 0.3 cfm/ft2 during economizer conditions.
Climate Zones | Building Water-Cooled Chilled Water System | Air-Cooled Chilled Water Systems or District Chilled Water Systems |
15 | ≥ 960,000 Btu/h (280 kW) | ≥ 1,250,000 Btu/h (365 kW) |
1-14 | ≥720,000 Btu/h (210 kW) | ≥940,000 Btu/h (275 kW) |
16 | ≥1,320,000 Btu/h (385 kW) | ≥1,720,000 Btu/h (505 kW) |
Note for Table 170.2E-2: Total Building Chilled Water System Capacity, Minus Capacity of the Cooling units with Air Economizers
Climate Zone | Efficiency Improvement a |
1 | 70% |
2 | 65% |
3 | 65% |
4 | 65% |
5 | 70% |
6 | 30% |
7 | 30% |
8 | 30% |
9 | 30% |
10 | 30% |
11 | 30% |
12 | 30% |
13 | 30% |
14 | 30% |
15 | 30% |
16 | 70% |
Footnote to TABLE 170.2-F a. If a unit is rated with an annualized or part-load metric, then to eliminate the required economizer, only the annualized or part-load minimum cooling efficiency of the unit must be increased by the percentage shown. If the unit is only rated with a full load metric, like EER2 or COP cooling, then that metric must be increased by the percentage shown. To determine the efficiency required to eliminate economizer, when the unit equipment efficiency is rated with an energy-input divided by work-output metric, the metric shall first be converted to COP prior to multiplying by the efficiency improvement percentage and then converted back to the rated metric. |
Exception to Section 170.2(c)4Ciia: Systems that provide 75 percent of the annual energy used for mechanical heating from site-recovered energy or a site-solar energy source.
Device Type* | Climate Zones | Required High Limit (Economizer Off When): Equationb | Required High Limit (Economizer Off When): Description |
Fixed Dry Bulb | 1, 3, 5, 11-16 | TOA > 75°F | Outdoor air temperature exceeds 75°F |
Fixed Dry Bulb | 2, 4, 10 | TOA > 73°F | Outdoor air temperature exceeds 73°F |
Fixed Dry Bulb | 6, 8, 9 | TOA > 71°F | Outdoor air temperature exceeds 71°F |
Fixed Dry Bulb | 7 | TOA > 69°F | Outdoor air temperature exceeds 69°F |
Differential Dry Bulb | 1, 3, 5, 11-16 | TOA > TRA | Outdoor air temperature exceeds return air temperature |
Differential Dry Bulb | 2, 4, 10 | TOA > TRA - 2°F | Outdoor air temperature exceeds return air temperature minus 2°F |
Differential Dry Bulb | 6, 8, 9 | TOA > TRA - 4°F | Outdoor air temperature exceeds return air temperature minus 4°F |
Differential Dry Bulb | 7 | TOA > TRA - 6°F | Outdoor air temperature exceeds return air temperature minus 6°F |
Fixed Enthalpy + Fixed Drybulb | All | hOA > 28 Btu/lb* or TOA > 75°F | Outdoor air enthalpy exceeds 28 Btu/lb of dry air* or Outdoor air temperature exceeds 75°F |
Footnote to TABLE 170.2-G:
a Only the high limit control devices listed are allowed to be used and at the setpoints listed. Others such as Dew Point, Fixed Enthalpy, Electronic Enthalpy, and Differential Enthalpy Controls, may not be used in any Climate Zone for compliance with Section 170.2(c)4Ci unless approval for use is provided by the Energy Commission Executive Director. b Devices with selectable (rather than adjustable) setpoints shall be capable of being set to within 2°F and 2 Btu/ lb of the setpoint listed. c At altitudes substantially different than sea level, the Fixed Enthalpy limit value shall be set to the enthalpy value at 75°F and 50% relative humidity. As an example, at approximately 6,000 foot elevation, the fixed enthalpy limit is approximately 30.7 Btu/lb. |
-
Drybulb and wetbulb temperatures accurate to ±2°F over the range of 40°F to 80°F;
-
Enthalpy accurate to ±3 Btu/lb over the range of 20 Btu/lb to 36 Btu/lb;
-
Relative humidity (RH) accurate to ±5 percent over the range of 20 percent to 80 percent RH;
Cooling Capacity | Minimum Number of Mechanical Cooling Stages | Minimum Compressor Displacement |
≥ 65,000 Btu/h and < 240,000 Btu/h | 3 stages | ≤ 35% full load |
≥ 240,000 Btu/h | 4 stages | ≤ 25% full load |
Exception 1 to Section 170.2(c)4Fi: Heat rejection devices included as an integral part of the equipment listed in Table 110.2-A through Table 110.2-N.
Exception 2 to Section 170.2(c)4Fi: Condenser fans serving multiple refrigerant circuits.
Exception 3 to Section 170.2(c)4Fi: Condenser fans serving flooded condensers.
Exception 4 to Section 170.2(c)4Fi: Up to one-third of the fans on a condenser or tower with multiple fans where the lead fans comply with the speed control requirement.
Exception 1 to Section 170.2(c)4Fiii: Cooling towers that are ducted (inlet or discharge) or have an external sound trap that requires external static pressure capability.
Exception 2 to Section 170.2(c)4Fiii: Cooling towers that meet the energy efficiency requirement for propeller fan towers in Section 110.2, Table 110.2-F.
Exception 1 to Section 170.2(c)4Fv: Replacement of existing cooling towers that are inside an existing building or on an existing roof.
Exception 2 to Section 170.2(c)4Fv: Cooling towers serving buildings in Climate Zone 1 or 16.
Table 170.2-I MINIMUM EFFICIENCY FOR PROPELLER OR AXIAL FAN OPEN-CIRCUIT COOLING TOWERS(GPM/hp)
CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
42.1 | 70 | 60 | 70 | 70 | 80 | 80 | 80 | 80 | 80 | 60 | 70 | 80 | 60 | 80 | 42.1 |
Excepti on 1 to Section 170.2(c)4I: Systems that include no more than three control valves.
Exception 2 to Section 170.2(c)4I: Systems having a total pump system power less than or equal to 1.5 hp.
Exception to Section 170.2(c)4Iiv: Hydronic systems that use variable flow to reduce pumping energy in accordance with Section 170.2(c)4Ii.
Exception 1 to Section 170.2(c)4Ivi: Heating hot water systems.
Exception 2 to Section 170.2(c)4Ivi: Condenser water systems serving only water-cooled chillers.
Exception to Section 170.2(c)4Ivii: Where a system loop temperature optimization controller is used to determine the most efficient operating temperature based on real-time conditions of demand and capacity, deadbands of less than 20°F shall be allowed.
Exception 1 to Section 170.2(c)4M: Spaces that are required by applicable codes and standards to be maintained at a positive pressure differential relative to adjacent spaces.
Exception 2 to Section 170.2(c)4M: Spaces where the highest amount of transfer air that could be used for exhaust makeup may exceed the available transfer airflow rate and where the spaces have a required negative pressure relationship.
1. DOAS unit fan systems with input power less than 1 kW shall not exceed a total combined fan power of 1.0 W/cfm. DOAS with fan power greater than or equal to 1 kW shall meet the requirements of Section 140.4 (c).
2. The DOAS supply air shall be delivered directly to the occupied space or at the outlet any terminal or cooling coils and shall cycle off any zone heating and cooling equipment fans, circulation pumps, and terminal unit fans when there is no call for heating or cooling in the zone.
Exception 1 to Section 170.2(c)4N2: Active chilled beam systems.
Exception 2 to Section 170.2(c)4N2: Sensible-only cooling terminal units with pressure-independent variable-airflow regulating devices limiting the DOAS supply air to the greater of latent load or minimum ventilation requirements.
Exception 3 to Section 170.2(c)4N2: Any configuration where a DOAS unit provides ventilation air to a downstream fan (a terminal box, air handling unit or other space-conditioning equipment) where the total system airflow can be reduced to ventilation minimum or the downstream fan power is no greater than 0.12 watts per cfm when space temperatures are within the thermostat deadband (at low speed per manufacturer’s literature).
% Outdoor Air at Full Design Airflow | CZ 1 |
CZ 2 |
CZ 3 | CZ 4 |
CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 |
CZ 12 |
CZ 13 |
CZ 14 |
CZ 15 |
CZ 16 |
<10% and <20% | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR | NR |
>20% and <30% | ≥15,000 | ≥20,000 | NR | NR | NR | NR | NR | NR | NR | NR |
≥18,500 |
≥18,500 |
≥18,500 | ≥18,500 |
≥18,500 |
$18,500 |
>30% and <40% | ≥13,000 | ≥15,000 | NR | NR | NR | NR | NR | NR | NR | NR | ≥15,000 |
≥15,000 | ≥15,000 | ≥15,0000 | ≥15,000 | ≥15,000 |
>40% and <50% | ≥10,000 | ≥12,000 | NR | NR | NR | NR | NR | NR | NR | ≥22,000 |
≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 |
≥10,000 |
$10,000 |
>50% and <60% | ≥9,000 | ≥10,000 | NR | ≥18,500 | NR | NR | NR | NR | NR | ≥17,000 | ≥8,000 |
≥8,000 | ≥8,000 |
≥8,000 |
≥8,000 |
$8,000 |
>60% and <70% | ≥7,000 | ≥7,500 | NR | ≥$16,500 | NR | NR | NR | NR | ≥20,000 | ≥15,000 | ≥7,000 |
≥7,000 | ≥7,000 |
≥7,000 |
≥7,000 |
$7,000 |
>70% and <80% | ≥6,500 | ≥7,000 | NR | ≥15,000 | NR | NR | NR | NR | ≥17,000 | ≥14,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 | $5,000 | $5,000 |
>80% | ≥4,500 | ≥6,500 | NR | ≥14,000 | NR | NR | NR | NR | ≥15,000 | ≥13,000 | ≥2,000 |
≥2,000 | ≥2,000 |
≥2,000 |
≥2,000 |
$3,000 |
Footnotes to TABLE 170.2-I:
1. Flow rates in TABLE 140.4-G represent the design supply fan airflow rate in CFM.
2. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.
% Outdoor Air at Full Design Airflow | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | 14 | 15 | 16 |
≥10% and <20% | ≥10,000 | ≥10,000 | NR | NR | NR | NR | NR | NR | NR | ≥40,000 | ≥40,000 | ≥20,000 | ≥10,000 | ≥10,000 | ≥10,000 | ≥10,000 |
≥20% and <30% | ≥2,000 | ≥5,000 | ≥13,000 | ≥9,000 | ≥9,000 | NR | NR | NR | NR | ≥15,000 | ≥15,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 | ≥5,000 |
≥30% and <40% | ≥2,000 | ≥3,000 | ≥10,000 | ≥6,500 | ≥6,500 | NR | NR | NR | ≥15,000 | ≥7,500 | ≥7,500 | ≥3,000 | ≥3,000 | ≥3,000 | ≥3,000 | ≥3,000 |
≥40% and <50% | ≥2,000 | ≥2,000 | ≥8,000 | ≥6,000 | ≥6,000 | NR | NR | NR | ≥12,000 | ≥6,000 | ≥6,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
≥50% and <60% | ≥2,000 | ≥2,000 | ≥7,000 | ≥6,000 | ≥6,000 | NR | NR | ≥20,000 | ≥10,000 | ≥5,000 | ≥5,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
≥60% and <70% | ≥2,000 | ≥2,000 | ≥6,000 | ≥6,000 | ≥6,000 | NR | NR | ≥18,000 | ≥9,000 | ≥4,000 | ≥4,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
≥70% and <80% | ≥2,000 | ≥2,000 | ≥6,000 | ≥5,000 | ≥5,000 | NR | NR | ≥15,000 | ≥8,000 | ≥3,000 | ≥3,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
≥80% | ≥2,000 | ≥2,000 | ≥6,000 | ≥5,000 | ≥5,000 | NR | NR | ≥12,000 | ≥7,000 | ≥3,000 | ≥3,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 | ≥2,000 |
Footnotes to TABLE 170.2-J:
1. Flow rates in TABLE 140.4-G represent the design supply fan airflow rate in CFM.
2. For a DOAS unit providing outdoor air to another space-conditioning system, the full design supply fan airflow rate shall be the total airflow of only the DOAS unit.
Exception 1 to Section 170.2(d)1: Multifamily buildings four habitable stories or greater may install a gas or propane instantaneous water heater with an input of 200,000 Btu per hour or less and no storage tank.
Exception 2 to Section 170.2(d)1: A 120V HPWH may be installed in place of a 240V HPWH for new dwelling unit with one bedroom or less.
A. For heat pump water-heating systems serving multiple dwelling units, the water-heating system shall be installed according to the manufacturer’s design and installation guidelines and meet the following requirements, or meet the requirements of NEEA Advanced Water Heater Specification for commercial heat pump water heater Tier 2 or higher:
- The primary heat pump water heater shall be a single-pass heat pump water heater.
- The hot water return from the recirculation loop shall connect to a recirculation loop tank and shall not directly connect to the primary heat pump water heater inlet or the primary thermal storage tanks.
- The fuel source for the recirculation loop tank shall be electricity.
- The primary storage tank temperature setpoint shall be at least 135°F.
- The recirculation loop tank temperature setpoint shall be at least 10°F lower than the primary thermal storage tank temperature setpoint.
- The minimum heat pump water heater compressor cut-off temperature shall be equal to or lower than 40°F ambient air temperature.
- Design documentation shall be provided in accordance with JA14.4.
Exception 1 to Section 170.2(d)Bi: Individual gas water heaters with input capacity at or below 100,000 Btu/h shall not be included in the calculations of the total system input or total system efficiency.
Exception 2 to Section 170.2(d)Bi: If 25 percent of the annual water-heating requirement is provided by site-solar energy or site-recovered energy.
a. A minimum solar savings fraction of 0.20 in Climate Zones 1 through 9 or a minimum solar savings fraction of 0.35 in Climate Zones 10 through 16; or
b. A minimum solar savings fraction of 0.15 in Climate Zones 1 through 9 or a minimum solar savings fraction of 0.30 in Climate Zones 10 through 16. In addition, a drain water heat recovery system that is field verified as specified in the Reference Appendix RA3.6.9.
Exception to Section 170.2(d)2D: Buildings with eight or fewer dwelling units.
Component | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
Unitary4 - Balanced Ventilation System1 HRV/ERV Sensible Recovery Efficiency | 0.67 | 0.67 | NR | 0.67 | NR | NR | NR | NR | NR | NR | 0.67 | 0.67 | 0.67 | 0.67 | NR | 0.67 |
Unitary4 - Balanced Ventilation System1 HRV/ERV Fan Efficacy (W/cfm) | 0.6 | 0.6 | 1.0 | 0.6 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 0.6 | 0.6 | 0.6 | 0.6 | 1.0 | 0.6 |
Unitary4 - Balanced Ventilation System1 Non-HRV/ERV Fan Efficacy (W/cfm) | NR | NR | NR | NR | 0.4 | 0.4 | 0.4 | 0.4 | 0.4 | 0.4 | NR | NR | NR | NR | 0.4 | NR |
Unitary4 - Heat Pump*; HSPF22 | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN |
Unitary 4- Dual-Fuel Heat Pump*; AFUE | MIN | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | NA | MIN |
Unitary4- Refrigerant Charge Verification or Fault Indicator Display | NR | REQ | NR | NR | NR | NR | NR | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | NR |
Unitary4 - SEER2 | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN | MIN |
Central5 - Balanced Ventilation System1 Sensible Recovery Efficiency or Effectiveness | 0.67 | 0.67 | NR | 0.67 | NR | NR | NR | NR | NR | NR | 0.67 | 0.67 | 0.67 | 0.67 | NR | 0.67 |
Central5 - Balanced Ventilation Systems1 Bypass Function | REQ | REQ | NR | REQ | NR | NR | NR | NR | NR | REQ | REQ | REQ | REQ | NR | REQ | REQ |
Central5 - Central Fan Integrated Ventilation System Fan Efficacy | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ |
Duct Insulation in Unconditioned Space | R-8 | R-8 | R-6 | R-8 | R-6 | R-6 | R-6 | R-8 | R-8 | R-8 | R-8 | R-8 | R-8 | R-8 | R-8 | R-8 |
Water Heating - All Buildings System Shall meet Section 170.2(d) | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ | REQ |
Footnotes to TABLE 170.2-K:
1. Requirements only apply when using Balanced Ventilation to meet 160.2(b)2Aivb.
2. HSPF2 means "heating seasonal performance factor."
3. A supplemental heating unit may be installed in a space served directly or indirectly by a primary heating system, provided that the unit thermal capacity does not exceed 2 kilowatts or 7,000 Btu/hr and is controlled by a time-limiting device not exceeding 30 minutes.
4. Unitary system serving one dwelling unit
5. Central system serving multiple dwelling units
Exception to Section 170.2(e): Common use areas providing shared provisions for living, eating, cooking, or sanitation to dwelling units that would otherwise lack these provisions may instead comply with Section 160.5(a).
For compliance with Part 6 a nonprogrammable double-throw switch is an electrical switch commonly called a "single pole double throw" or "three-way" switch that is wired as a selector switch allowing one of two loads to be enabled. It can be a line voltage switch or a low voltage switch selecting between two relays. It cannot be overridden or changed in any manner that would permit both loads to operate simultaneously.
When used for determining PAFs for general lighting in offices, furniture mounted luminaires that comply with all of the following conditions shall qualify as permanently installed general lighting systems:
TYPE OF CONTROL | TYPE OF AREA | FACTOR |
1. Daylight Continuous Dimming plus OFF Control | Luminaires in skylit daylit zone or primary sidelit daylit zone | 0.10 |
2. Occupant Sensing Controls in Office Spaces larger than 250 square feet | In open plan offices > 250 square feet: One sensor controlling an area that is: No larger than 125 square feet |
0.30 |
In open plan offices > 250 square feet: One sensor controlling an area that is: From 126 to 250 square feet |
0.20 | |
3.Institutional Tuning | Luminaires in non-daylit areas. Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF. |
0.10 |
Luminaires in daylit areas. Luminaires that qualify for other PAFs in this table may also qualify for this tuning PAF. |
0.05 | |
4. Demand Responsive Control | General lighting luminaires not in the scope of Section 110.12(c). If DR controls are required of Section 110.12(c), this PAF is not available for any lighting in the project. Luminaires that qualify for other PAFs in this table may also qualify for this demand responsive control PAF | 0.05 |
5. Clerestory Fenestration | Luminaires in daylit areas adjacent to the clerestory. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF. | 0.05 |
6. Horizontal Slats | Luminaires in daylit areas adjacent to vertical fenestration with interior or exterior horizontal slats. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF. | 0.05 |
7.Light Shelves | Luminaires in daylit areas adjacent to clerestory fenestration with interior or exterior light shelves. This PAF may be combined with the PAF for clerestory fenestration. Luminaires that qualify for daylight dimming plus OFF control may also qualify for this PAF. | 0.10 |
ii. Small Aperture Tunable-White and Dim-to-Warm Luminaires Lighting Power Adjustment. For qualifying small aperture tunable-white and dim-to-warm LED luminaires, the adjusted indoor lighting power of these luminaires shall be calculated by multiplying their maximum rated wattage by 0.75. Qualifying luminaires shall meet all of the following:
- Small aperture. Qualifying luminaires with a luminaire aperture length longer than 18 inches shall have a luminaire aperture no wider than four inches. Qualifying luminaires with a luminaire aperture length of 18 inches or less shall have a luminaire aperture no wider than 8 inches.
- Color changing. Qualifying tunable-white luminaires shall be capable of a color change greater than or equal to 2000 Kelvin correlated color temperature (CCT). Qualifying dim-to-warm luminaires shall be capable of color change greater than or equal to 500 Kelvin CCT.
- Controls. Qualifying luminaires shall be connected to controls that allow color changing of the luminaires.
i. The Area Category Method, as described in Section 170.2(e)4A, shall be used for all common use areas in the building. Under the Area Category Method as described more fully in Section 170.2(e)4A, and subject to the adjustments listed there, the allowed indoor lighting power allotment for general lighting shall be calculated for each area in the building as follows:
- For conditioned areas, by multiplying the conditioned square feet of the area times the applicable allotment of watts per square foot for the area shown in Table 170.2-Μ.
- For unconditioned areas, by multiplying the unconditioned square feet of the area times the applicable allotment of watts per square foot for the area shown in Table 170.2-M.
The allowed indoor lighting power allotment for general lighting for one area for which the Area Category Method was used may be increased up to the amount that the allowed indoor lighting power allotment for general lighting for another area using the Area Category Method, except that such increases and decreases shall not be made between conditioned and unconditioned space.
v. In addition to the allowed indoor lighting power calculated according to Sections 170.2(e)4Ai through iv, the building may add additional lighting power allowances for qualifying lighting systems as specified in the Qualifying Lighting Systems column in Table 170.2-M under the following conditions:
a. Only primary function areas having a lighting system as specified in the Qualifying Lighting Systems column in Table 170.2-M and in accordance with the corresponding footnote of the table shall qualify for the additional lighting power allowances; and
b. The additional lighting power allowances shall be used only if the plans clearly identify all applicable task areas and the lighting equipment designed to illuminate these tasks; and
c. Tasks that are performed less than two hours per day or poor quality tasks that can be improved are not eligible for the additional lighting power allowances; and
d. The additional lighting power allowances shall not utilize any type of luminaires that are used for general lighting in the building; and
e. RESERVED; and
f. The additional lighting power allowed is the smaller of:
I. the lighting power density listed in the "Allowed Additional Lighting LPD" column in Table 170.2-M, times the square feet of the primary function, or
II. the adjusted indoor lighting power of the applicable lighting; and
g. Floor displays shall not qualify for wall display allowances.
h. Qualifying wall lighting shall:
I. Be mounted within 10 feet of the wall having the wall display. When track lighting is used for wall display, and where portions of that lighting track are more than 10 feet from the wall and other portions are within 10 feet of the wall, portions of track more than 10 feet from the wall shall not be used for the wall display allowance; and
II. Be a lighting system type appropriate for wall lighting. Lighting systems appropriate for wall lighting are lighting track adjacent to the wall, wall-washer luminaires, luminaires behind a wall valance or wall cove, or accent light. (Accent luminaires are adjustable or fixed luminaires providing directional display light.).
i. Mounting height shall be the luminaire mounting height measured from the finished floor to the bottom of the luminaire. If luminaires are mounted at different mounting height within the same space, the average mounting height of the luminaires qualified for the additional lighting power allowances in Table 170.2-M can be used to establish the mounting height of the qualified luminaires for calculations of the additional lighting power allowances of the qualified luminaires.
Primary Function Area | Allowed Lighting Power Density for General Lighting (W/ft²) | Additional Lighting Power Qualified Lighting Systems | Additional Lighting Power Additional Allowance (W/ft², unless noted otherwise) |
Storage | 0.4 | NA | NA |
Conference, Multipurpose and Meeting Area | 0.75 | Display | 0.25 |
Conference, Multipurpose and Meeting Area | 0.75 | Wall Display MH <= 10'6" | 2 W/ft |
Conference, Multipurpose and Meeting Area | 0.75 | Wall Display MH 10'7" to 14' | 2.35 W/ft |
Conference, Multipurpose and Meeting Area | 0.75 | Wall Display MH > 14' | 2.66 W/ft |
Conference, Multipurpose and Meeting Area | 0.75 | Floor Display & Task MH <= 10'6" | 0.30 |
Conference, Multipurpose and Meeting Area | 0.75 | Floor Display & Task MH 10'7" to 14' | 0.35 |
Conference, Multipurpose and Meeting Area | 0.75 | Floor Display & Task MH > 14' | 0.40 |
Copy Room | 0.50 | NA | NA |
Dining Area | 0.40 | Decorative/Display | 0.25 |
Bar/Lounge and Fine Dining Area | 0.45 | Display | 0.35 |
Dining Area | 0.45 | Wall Display MH <= 10'6" | 1.25 W/ft |
Bar/Lounge and Fine Dining Area | 0.45 | Wall Display MH 10'7" to 14' | 1.5 W/ft |
Bar/Lounge and Fine Dining Area | 0.45 | Wall Display MH > 14' | 1.7 W/ft |
Bar/Lounge and Fine Dining Area | 0.45 | Floor Display & Task MH <= 10'6" | 0.45 |
Bar/Lounge and Fine Dining Area | 0.45 | Floor Display & Task MH 10'7" to 14' | 0.52 |
Bar/Lounge and Fine Dining Area | 0.45 | Floor Display & Task MH > 14' | 0.60 |
Bar/Lounge and Fine Dining Area | 0.45 | General Lighting in the enclosed space of ceiling height > 10' | 0.25 |
Dining Area | 0.45 | Display/Decorative | 0.25 |
Dining Area Cafeteria/Fast Food | 0.40 | Display/Decorative | 0.25 |
Family and Leisure | 0.40 | Display/Decorative | 0.25 |
Health Care / Assisted Living Nurse's Station | 0.85 | Tunable white or dim-to-warm | 0.10 |
TABLE 170.2-M AREA CATEGORY METHOD - LIGHTING POWER DENSITY VALUES (WATTS/FT²) (Continued)
Primary Function Area | Allowed Lighting Power Density for General Lighting (W/ft²) | Additional Lighting Power Qualified Lighting Systems | Additional Lighting Power Additional Allowance (W/ft², unless noted otherwise) |
Health Care / Assisted Living | 0.75 | Tunable white or dim-to-warm8 | 0.10 |
Physical Therapy Room | 0.91 | NA | NA |
Kitchen/Food Preparation Area | 0.95 | NA | NA |
Electrical, Mechanical, Telephone Rooms | 0.40 | Detailed Task Work1 | 0.20 |
Exercise/Fitness Center and Gymnasium Area | 0.50 | NA | NA |
Lobby, Main Entry | 0.70 | Display | 0.25 |
Lobby, Main Entry | 0.70 | Wall Display MH <= 10'-6" | 3 W/ft |
Lobby, Main Entry | 0.70 | Wall Display MH 10'7" to 14' | 3.5 W/ft |
Lobby, Main Entry | 0.70 | Wall Display MH > 14' | 4 W/ft |
Locker Room | 0.45 | NA | NA |
Lounge, Breakroom, or Waiting Area | 0.55 | Display/Decorative | 0.25 |
Concourse and Atria Area | 0.60 | Display/Decorative | 0.25 |
Office Area <250 square feet |
0.60 | Decorative/Display and Portable lighting for office areas5 | 0.20 |
Office Area >250 square feet |
0.65 | Decorative/Display and Portable lighting for office areas5 | 0.20 |
Parking Garage Area Parking Zone and Ramps |
0.10 | First ATM or Ticket Machine | 100 W |
Parking Garage Area Parking Zone and Ramps |
0.10 | Additional ATM or Ticket machine | 50 W each |
Parking Garage Area Daylight Adaptation Zones3 |
1.00 | - | - |
Laundry Area | 0.45 | - | - |
Restrooms | 0.65 | Decorative/Display | 0.35 |
Stairwell | 0.60 | Decorative/Display | 0.30 |
All other | 0.40 | - | - |
Aging Eye/Low-vision Lobby, Main Entry6 |
0.85 | Display/Decorative | 0.30 |
Aging Eye/Low-vision Lobby, Main Entry6 |
0.85 | Transition Lighting OFF at night7 | 0.95 |
Aging Eye/Low-vision Stairwell6 |
0.80 | Display/Decorative | 0.30 |
Aging Eye/Low-vision Corridor Area6 |
0.70 | Display/Decorative | 0.30 |
Aging Eye/Low-vision Lounge/Waiting Area6 |
0.80 | Display/Decorative | 0.30 |
Aging Eye/Low-vision Multipurpose Room6 |
0.85 | Display/Decorative | 0.30 |
TABLE 170.2-M AREA CATEGORY METHOD - LIGHTING POWER DENSITY VALUES (WATTS/FT²) (Continued)
Primary Function Area | Allowed Lighting Power Density for General Lighting (W/ft²) | Additional Lighting Power Qualified Lighting Systems | Additional Lighting Power Additional Allowance (W/ft², unless noted otherwise) |
Aging Eye/Low-vision* Dining6 | 0.80 | Display/Decorative | 0.30 |
Aging Eye/Low-vision6 | 1.00 | Display/Decorative | 0.20 |
Footnotes for this table are listed below.
1. Detailed task work – Lighting provides high level of visual acuity required for activities with close attention to small elements and/or extreme close up work.
2. MH denotes the luminaire mounting height of the qualified lighting systems.
3. Daylight Adaptation Zones shall be no longer than 66 feet from the entrance to the parking garage.
4. RESERVED
5. Portable lighting in office areas includes under shelf or furniture-mounted supplemental task lighting qualifies when controlled by a time clock or an occupancy sensor.
6. Aging Eye/Low-vision areas can be documented as being designed to comply with the light levels in ANSI/IES RP-28 and are or will be licensed by local or state authorities for either senior long-term care, adult day care, senior support, and/or people with special visual needs.
7. Transition lighting OFF at night. Lighting power controlled by astronomical time clock or other control to shut off lighting at night. Additional LPD only applies to area within 30 feet of an exit. Not applicable to lighting in daylit zones.
8. Tunable white luminaires capable of color change greater than or equal to 2000K CCT, or dim-to-warm luminaires capable of color change greater than or equal to 500K CCT, connected to controls that allows color changing of the luminaires.
5. RESERVED.
Type of Power Allowance
|
Lighting Zone 0 2
|
Lighting Zone 1 2
|
Lighting Zone 2 2
|
Lighting Zone 3 2
|
Lighting Zone 4 2
|
Area Wattage Allowance (AWA)
|
No allowance 1
|
0.026 W/ft²
|
0.030 W/ft²
|
0.038 W/ft²
|
0.055 W/ft²
|
Initial Wattage Allowance (IWA)
|
No allowance 1
|
300 W
|
350 W
|
400 W
|
450 W
|
Footnotes to TABLE 170.2-R
| |||||
1 Continuous lighting is explicitly prohibited in Lighting Zone 0. A single luminaire of 15 Watts or less may be installed at an entrance to a parking area, trail head, fee payment kiosk, outhouse, or toilet facility, as required to provide safe navigation of the site infrastructure. Luminaires installed shall meet the maximum zonal lumen limits as specified in Section 160.5(c)1.
| |||||
2 Narrow band spectrum light sources with a dominant peak wavelength greater than 580 nm – as mandated by local, state, or federal agencies to minimize the impact on local, active professional astronomy or nocturnal habitat of specific local fauna – shall be allowed a 2.0 lighting power allowance multiplier.
|
All area and distance measurements in plan view unless otherwise noted.
PER APPLICATION: WATTAGE ALLOWANCE PER APPLICATION. Use all that apply as appropriate
Lighting Application | Lighting Zone 0 | Lighting Zone 1 | Lighting Zone 2 | Lighting Zone 3 | Lighting Zone 4 |
Building Entrances or Exits. Allowance per door. Luminaires qualifying for this allowance shall be within 20 feet of the door. | Not applicable | 9 watts | 15 watts | 19 watts | 21 watts |
Primary Entrances to Senior Care Facilities Allowance per primary entrance(s) only. Primary entrances shall provide access for the general public and shall not be used exclusively for staff or service personnel. This allowance shall be in addition to the building entrance or exit allowance above. Luminaires qualifying for this allowance shall be within 100 feet of the primary entrance. | Not applicable | 20 watts | 40 watts | 57 watts | 60 watts |
ATM Lighting. Allowance per ATM. Luminaires qualifying for this allowance shall be within 50 feet of the dispenser. | Not applicable | 100 watts for first ATM, 35 watts for each additional ATM. | 100 watts for first ATM, 35 watts for each additional ATM. | 100 watts for first ATM, 35 watts for each additional ATM. | 100 watts for first ATM, 35 watts for each additional ATM. |
TABLE 170.2-S ADDITIONAL MULTIFAMILY LIGHTING POWER ALLOWANCE FOR SPECIFIC APPLICATIONS
All area and distance measurements in plan view unless otherwise noted.
PER APPLICATION: WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft²). May be used for any illuminated hardscape area on the site.
Lighting Application | Lighting Zone 0 | Lighting Zone 1 | Lighting Zone 2 | Lighting Zone 3 | Lighting Zone 4 |
Hardscape Ornamental Lighting. Allowance for the ground or illuminated hardscape area. BUG rating for luminaires qualifying for this allowance shall be rated for 50 watts or less as determined in accordance with IES TM-15-11, Addendum A, and shall be post-top luminaires, lanterns, pendant luminaires, or chandeliers. | Not applicable | No Allowance | 0.007 W/ft² | 0.013 W/ft² | 0.019 W/ft² |
TABLE 170.2-S ADDITIONAL MULTIFAMILY LIGHTING POWER ALLOWANCE FOR SPECIFIC APPLICATIONS
All area and distance measurements in plan view unless otherwise noted.
PER APPLICATION: WATTAGE ALLOWANCE PER SPECIFIC AREA (W/ft²). Use as appropriate provided that none of the following specific applications shall be used for the same area.
Lighting Application | Lighting Zone 0 | Lighting Zone 1 | Lighting Zone 2 | Lighting Zone 3 | Lighting Zone 4 |
Building Facades. Only areas of building facade that are illuminated shall qualify for this allowance. Luminaires qualifying for this allowance shall be aimed at the facade and shall be capable of illuminating it without obstruction or interference by permanent building features or other objects. This allowance calculation shall not include portions of the building facades within 20 feet of residence bedroom windows. | Not applicable | No Allowance | 0.100 W/ft² | 0.170 W/ft² | 0.225 W/ft² |
Canopies and Tunnels. Allowance for the total area within the drip line of the canopy or inside the tunnel. Luminaires qualifying for this allowance shall be located under the canopy or tunnel. | Not applicable | 0.057 W/ft² | 0.137 W/ft² | 0.270 W/ft² | 0.370 W/ft² |
Student Pick-up/Drop-off zone. Allowance for the area of the student pick-up/drop-off zone, with or without canopy, for preschool through 12th grade school campuses. A student pick-up/drop off zone is a curbside, controlled traffic area on a school campus where students are picked-up and dropped off from vehicles. The allowed area shall be the smaller of the actual width or 25 feet, times the smaller of the actual length or 250 feet. Qualifying luminaires shall be within 2 mounting heights of the student pick-up/drop-off zone. | Not applicable | No Allowance | 0.056 W/ft² | 0.200 W/ft² | No Allowance |
Outdoor Dining. Allowance for the total illuminated hardscape of outdoor dining. Outdoor dining areas are hardscape areas used to serve and consume food and beverages. Qualifying luminaires shall be within 2 mounting heights of the hardscape area of outdoor dining. | Not applicable | 0.004 W/ft² | 0.030 W/ft² | 0.050 W/ft² | 0.075 W/ft² |
TABLE 170.2-S ADDITIONAL MULTIFAMILY LIGHTING POWER ALLOWANCE FOR SPECIFIC APPLICATIONS
All area and distance measurements in plan view unless otherwise noted.
PER SITE: WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft²). May be used as additional allowance for applicable illuminated hardscape area on the site.
Lighting Application | Lighting Zones | ||||
Zone 1 | Zone 2 | Zone 3 | Zone 4 | Zone 5 | |
Special Security Lighting for Retail Parking and Pedestrian Hardscape. This additional allowance is for illuminated retail parking and pedestrian hardscape identified as having special security needs. This allowance shall be in addition to the building entrance or exit allowance. | Not applicable | 0.004 W/ft² | 0.005 W/ft² | 0.010 W/ft² | No Allowance |
TABLE 170.2-S ADDITIONAL MULTIFAMILY LIGHTING POWER ALLOWANCE FOR SPECIFIC APPLICATIONS
All area and distance measurements in plan view unless otherwise noted.
PER SITE: WATTAGE ALLOWANCE PER HARDSCAPE AREA (W/ft²). May be used as additional allowance for applicable illuminated hardscape area on the site.
Lighting Application | Lighting Zone 0 | Lighting Zone 1 | Lighting Zone 2 | Lighting Zone 3 | Lighting Zone 4 |
Security Camera. This additional allowance is for the illumination of license plates and shall apply when a security camera is installed within 2 mounting heights of the general hardscape area and mounted more than 10 feet away from a building. | Not applicable | No Allowance | 0.018 W/ft² | 0.018 W/ft² | 0.018 W/ft² |
The ratio of the output wattage to the input wattage is at 100 percent tubing load.
Exception to Section 170.2(e)7Bv: Single voltage external power supplies that are designed to convert 120 volt AC input into lower voltage DC or AC output, and have a nameplate output power less than or equal to 250 watts, shall comply with the applicable requirements of the Appliance Efficiency Regulations (Title 20).
Exception 1 to Section 170.2(e)7: Unfiltered incandescent lamps that are not part of an electronic message center (EMC), an internally illuminated sign, or an externally illuminated sign.
Exception 2 to Section 170.2(e)7: Exit signs. Exit signs shall meet the requirements of the Appliance Efficiency Regulations.
Exception 3 to Section 170.2(e)7: Traffic signs that meet the requirements of the Appliance Efficiency Regulations, Sections 1601(m), 1602, 1602.1, 1603, 1604(m), 1605, 1605.1(m), 1605.2(m), 1605.3(m), 1606, 1607, 1608, and 1609.
- Other state building code requirements, or
- Local building code requirements if local building code requirements are confirmed by the Executive Director.
kWPV = (CFA × A)/1000 + (NDU × B)
WHERE:
- kWPV = kWdc size of the PV system
- CFA = Conditioned floor area
- NDU = Number of dwelling units
- A = CFA adjustment factor from Table 170.2-T
- B = Dwelling unit adjustment factor from Table 170.2-T
CLIMATE ZONE | A—CFA | B— DWELLING UNITS |
1 | 0.793 | 1.27 |
2 | 0.621 | 1.22 |
3 | 0.628 | 1.12 |
4 | 0.586 | 1.21 |
5 | 0.585 | 1.06 |
6 | 0.594 | 1.23 |
7 | 0.572 | 1.15 |
8 | 0.586 | 1.37 |
9 | 0.613 | 1.36 |
10 | 0.627 | 1.41 |
11 | 0.836 | 1.44 |
12 | 0.613 | 1.40 |
13 | 0.894 | 1.51 |
14 | 0.741 | 1.26 |
15 | 1.56 | 1.47 |
16 | 0.59 | 1.22 |
- Other state building code requirements, or
- Local building code requirements if the local building code requirements are confirmed by the Executive Director.
kWPVdc = (CFA x A)/1000
Where:
- kWPVdc = Size of the PV system in kW.
- CFA = Conditioned floor area in square feet.
- A = PV capacity factor specified in Table 170.2-U for the building type
Building Type | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
Events & Exhibits | 3.48 | 4.28 | 3.16 | 4.28 | 4.05 | 4.05 | 4.83 | 4.83 | 5.04 | 5.04 | 4.44 | 4.43 | 4.36 | 5.48 | 5.04 | 3.38 |
Library | 0.39 | 3.23 | 2.59 | 3.25 | 2.48 | 2.74 | 3.04 | 3.49 | 3.32 | 3.69 | 3.79 | 3.32 | 3.79 | 3.37 | 4.49 | 2.84 |
Hotel/Motel | 1.69 | 1.90 | 1.66 | 1.97 | 1.69 | 1.87 | 1.94 | 2.22 | 2.09 | 2.20 | 2.30 | 2.05 | 2.30 | 2.02 | 2.72 | 1.73 |
Office, Financial Institution Tenant Space, Medical Office Building/Clinic | 2.59 | 3.13 | 2.59 | 3.13 | 2.59 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.13 | 3.80 | 2.59 |
Restaurant | 8.55 | 9.32 | 8.16 | 9.65 | 8.21 | 8.73 | 9.11 | 10.18 | 9.75 | 10.28 | 10.85 | 9.73 | 10.69 | 9.73 | 12.25 | 8.47 |
Retail, Grocery | 3.14 | 3.49 | 3.01 | 3.61 | 3.05 | 3.27 | 3.45 | 3.83 | 3.65 | 3.81 | 4.09 | 3.64 | 3.99 | 3.71 | 4.60 | 3.21 |
School | 1.27 | 1.43 | 1.27 | 1.47 | 1.27 | 1.43 | 1.47 | 1.63 | 1.53 | 1.58 | 1.63 | 1.63 | 1.63 | 1.63 | 2.46 | 1.32 |
Warehouse | 0.39 | 0.44 | 0.39 | 0.44 | 0.39 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.44 | 0.58 | 0.39 |
Religious Worship | 4.25 | 4.65 | 3.49 | 4.57 | 3.72 | 4.29 | 4.46 | 5.89 | 5.30 | 5.67 | 5.89 | 5.89 | 5.78 | 4.63 | 7.22 | 4.99 |
Sports & Recreation | 2.47 | 1.97 | 1.54 | 2.03 | 1.60 | 1.84 | 1.98 | 2.63 | 2.47 | 2.60 | 2.75 | 2.20 | 2.72 | 2.15 | 4.03 | 1.81 |
Multifamily, 4-3 stories | 1.82 | 2.21 | 1.82 | 2.21 | 1.82 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.21 | 2.77 | 1.82 |
kWhbatt = kWPVdc x B / D0.5
WHERE:
- kWhbatt = Rated Useable Energy Capacity of the battery storage system in kWh
- kWPVdc = PV system capacity required by section 170.2(g) in kWdc
- B = Battery energy capacity factor specified in Table 170.2-V for the building type
- D = Rated single charge-discharge cycle AC to AC (round-trip) efficiency of the battery storage system.
kWbatt = kWPVdc x C
WHERE:
- kWbatt = Power capacity of the battery storage system in kWdc
- kWPVdc = PV system capacity required by section 170.2(g) in kWdc
- C = Battery power capacity factor specified in Table 170.2-V for the building type
Exception 1 to Section 170.2(h): No battery storage system is required if the installed PV system size is less than 15 percent of the size determined by Equation 170.2-D.
Exception 2 to Section 170.2(h): No battery storage system is required in buildings with battery storage system requirements with less than 10 kWh rated capacity.
Building Type | CZ 1 | CZ 2 | CZ 3 | CZ 4 | CZ 5 | CZ 6 | CZ 7 | CZ 8 | CZ 9 | CZ 10 | CZ 11 | CZ 12 | CZ 13 | CZ 14 | CZ 15 | CZ 16 |
Events & Exhibits | 1.85 | 1.74 | 2.15 | 1.91 | 2.13 | 2.14 | 2.30 | 2.35 | 2.47 | 2.62 | 2.67 | 2.16 | 2.64 | 3.22 | 3.27 | 1.89 |
Library | 0.37 | 7.17 | 5.97 | 6.75 | 5.64 | 6.08 | 6.19 | 7.13 | 7.18 | 7.56 | 7.17 | 6.93 | 6.88 | 6.81 | 7.93 | 6.40 |
Hotel/Motel | 0.86 | 0.84 | 0.77 | 0.92 | 0.81 | 0.89 | 0.90 | 1.01 | 1.00 | 1.11 | 1.14 | 0.90 | 1.11 | 1.34 | 1.49 | 0.85 |
Office, Financial Tenant Space, Medical Office Building/Clinic | NR* | 5.26 | 4.35 | 5.26 | 4.35 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 5.26 | 6.39 | 4.35 |
Restaurants | 4.36 | 4.11 | 3.78 | 4.37 | 3.89 | 4.02 | 4.11 | 4.49 | 4.47 | 4.82 | 5.05 | 4.43 | 5.05 | 5.24 | 6.23 | 4.11 |
Retail, Grocery | 1.78 | 1.71 | 1.61 | 1.82 | 1.72 | 1.75 | 1.92 | 1.97 | 2.05 | 2.22 | 2.27 | 1.95 | 2.16 | 2.22 | 2.66 | 1.81 |
School | NR† | 3.05 | 2.38 | 3.05 | 2.38 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 3.05 | 1.05 | 3.05 | 3.05 | 4.60 | 2.38 |
Warehouse | 0.41 | 0.37 | 0.41 | 0.37 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.41 | 0.54 | 0.37 | 0.41 |
Religious Worship | 2.21 | 2.25 | 1.74 | 2.42 | 2.08 | 2.75 | 2.94 | 3.37 | 3.17 | 3.37 | 3.58 | 2.72 | 3.62 | 3.21 | 4.89 | 2.37 |
Sports & Recreation | 0.79 | 0.76 | 1.13 | 1.24 | 0.86 | 1.12 | 1.37 | 1.57 | 1.65 | 1.65 | 1.80 | 1.12 | 1.78 | 1.78 | 2.31 | 0.93 |
Multifamily > 3 stories | 1.88 | 2.27 | 1.88 | 2.27 | 1.88 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.27 | 2.85 | 1.88 |
Note: Authority: Sections 25213, 25218, 25218.5, 25402 and 25402.1, Public Resources Code. Reference: Sections 25007, 25008, 25218.5, 25310, 25402, 25402.1, 25402.4, 25402.8, and 25943, Public Resources Code.